Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | RIO drop adaptor module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Product Compatibility | Quantum |
| Maximum Number of I/O Expansion Module | 27 |
| Type of cable | 75 Ohm coaxial |
| Transmission Rate | 1544 Mbit/s |
| Dynamic range | 35 dB |
| Isolation voltage | 500 V DC coaxial center and ground |
| Electrical connection | 2 female connectors F, elbowed with redundant cable |
| Diagnostics startup | Power up and runtime RAM address/data Executive checksum |
| Power dissipation in W | 3.8 W 2 channels |
| Bus current requirement | 750 mA 2 channels |
| Module format | Standard |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | RIO head-end adaptor module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Product Compatibility | Quantum 200/500/800 series Symax (any mix) |
| Maximum drops/network | 31 |
| I/O words/drop | 64 I/64 O |
| Type of cable | 75 Ohm coaxial |
| Transmission Rate | 1544 Mbit/s |
| Dynamic range | 35 dB |
| Isolation voltage | 500 V DC coaxial center and ground |
| Electrical connection | 1 female connector F, elbowed with single cable |
| Diagnostics startup | Power up Memory check LAN controller check |
| Power dissipation in W | 3 W 1 channel |
| Marking | CE |
| Bus current requirement | 600 mA 1 channel |
| Module format | Standard |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | RIO head-end adaptor module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Product Compatibility | Quantum 200/500/800 series Symax (any mix) |
| Maximum drops/network | 31 |
| I/O words/drop | 64 I/64 O |
| Type of cable | 75 Ohm coaxial |
| Transmission Rate | 1544 Mbit/s |
| Dynamic range | 35 dB |
| Isolation voltage | 500 V DC coaxial center and ground |
| Electrical connection | 1 female connector F, elbowed with single cable |
| Diagnostics startup | LAN controller check Memory check Power up |
| Power dissipation in W | 3 W 1 channel |
| Marking | CE |
| Bus current requirement | 600 mA 1 channel |
| Module format | Standard |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | RIO head-end adaptor module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Product Compatibility | Symax (any mix) Quantum 200/500/800 series |
| Maximum drops/network | 31 |
| I/O words/drop | 64 I/64 O |
| Type of cable | 75 Ohm coaxial |
| Transmission Rate | 1544 Mbit/s |
| Dynamic range | 35 dB |
| Isolation voltage | 500 V DC coaxial center and ground |
| Electrical connection | 2 female connectors F, elbowed with redundant cable |
| Diagnostics startup | Memory check LAN controller check Power up |
| Power dissipation in W | 3 W 2 channels |
| Marking | CE |
| Bus current requirement | 750 mA 2 channels |
| Module format | Standard |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | RIO head-end adaptor module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Product Compatibility | Symax (any mix) Quantum 200/500/800 series |
| Maximum drops/network | 31 |
| I/O words/drop | 64 I/64 O |
| Type of cable | 75 Ohm coaxial |
| Transmission Rate | 1544 Mbit/s |
| Dynamic range | 35 dB |
| Isolation voltage | 500 V DC coaxial center and ground |
| Electrical connection | 2 female connectors F, elbowed with redundant cable |
| Diagnostics startup | Power up LAN controller check Memory check |
| Power dissipation in W | 3 W 2 channels |
| Marking | CE |
| Bus current requirement | 750 mA 2 channels |
| Module format | Standard |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | VAC discrete input modules |
| Software name | Concept ProWORX 32 Unity Pro |
| Discrete input number | 16 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Group of channels | 16 |
| Addressing requirement | 1 input word |
| Discrete input voltage | 24 V AC |
| Input current | 12 mA 57...63 Hz 10.7 mA 47...53 Hz |
| Voltage state 1 guaranteed | 16...30 V AC 57...63 Hz 18...30 V AC 47...53 Hz |
| Voltage state 0 guaranteed | 0...6 V 57...63 Hz 0...5 V 47...53 Hz |
| Input impedance | 2600 Ohm capacitive 57...63 Hz 3100 Ohm capacitive 47...53 Hz |
| Network frequency limits | 47â¦63 Hz |
| Maximum leakage current | 1.9 mA |
| Absolute maximum input | 30 V continuous 32 V 10 s 50 V 1 cycle |
| Response Time | 4.9...0.75 ms x line cycle Off-On 7.3...12.3 ms On-Off |
| Isolation between channels | 1780 Vrms for 1 minute |
| Isolation between channels and bus | 1780 Vrms for 1 minute |
| Bus current requirement | 180 mA |
| Maximum power dissipation in W | 5.5 W |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) for input status 16 LEDs (green) |
| Marking | CE |
| Module format | Standard |
| Product Weight | 0.7 lb(US) (0.3 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | VAC discrete input modules |
| Software name | ProWORX 32 Concept Unity Pro |
| Discrete input number | 32 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Group of channels | 4 |
| Addressing requirement | 2 input words |
| Discrete input voltage | 24 V AC |
| Input current | 11.1 mA 57...63 Hz 13.2 mA 47...53 Hz |
| Voltage state 1 guaranteed | 12...30 V AC 57...63 Hz 14...30 V AC 47...53 Hz |
| Voltage state 0 guaranteed | 0...5 V 57...63 Hz 0...5 V 47...53 Hz |
| Input impedance | 2600 Ohm capacitive 57...63 Hz 3100 Ohm capacitive 47...53 Hz |
| Network frequency limits | 47â¦63 Hz |
| Maximum leakage current | 1.9 mA |
| Absolute maximum input | 30 V continuous 32 V 10 s 50 V 1 cycle |
| Response Time | 4.9...0.75 ms x line cycle Off-On 7.3...12.3 ms On-Off |
| Isolation between group | 1780 Vrms for 1 minute |
| Isolation between group and bus | 1780 Vrms for 1 minute |
| Bus current requirement | 250 mA |
| Maximum power dissipation in W | 10.9 W |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 32 LEDs (green) for input status |
| Marking | CE |
| Module format | Standard |
| Product Weight | 0.75 lb(US) (0.34 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | VAC discrete input modules |
| Software name | Concept Unity Pro ProWORX 32 |
| Discrete input number | 16 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Group of channels | 16 |
| Addressing requirement | 1 input word |
| Discrete input voltage | 48 V AC |
| Input current | 11 mA 57...63 Hz 9.3 mA 47...53 Hz |
| Voltage state 1 guaranteed | 34...56 V AC 57...63 Hz 36...56 V AC 47...53 Hz |
| Voltage state 0 guaranteed | 0...10 V 57...63 Hz 0...10 V 47...53 Hz |
| Input impedance | 5600 Ohm capacitive 57...63 Hz 6800 Ohm capacitive 47...53 Hz |
| Network frequency limits | 47â¦63 Hz |
| Maximum leakage current | 1.7 mA |
| Absolute maximum input | 100 V 1 cycle 56 V continuous 63 V 10 s |
| Response Time | 4.9...0.75 ms x line cycle Off-On 7.3...12.3 ms On-Off |
| Isolation between channels | 1780 Vrms for 1 minute |
| Isolation between channels and bus | 1780 Vrms for 1 minute |
| Bus current requirement | 180 mA |
| Maximum power dissipation in W | 5.5 W |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 16 LEDs (green) for input status |
| Marking | CE |
| Module format | Standard |
| Product Weight | 0.7 lb(US) (0.3 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | VAC discrete input modules |
| Software name | Concept ProWORX 32 Unity Pro |
| Discrete input number | 16 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Group of channels | 16 |
| Addressing requirement | 1 input word |
| Discrete input voltage | 115 V AC |
| Input current | 11.1 mA 57...63 Hz 13.2 mA 47...53 Hz |
| Voltage state 1 guaranteed | 79...132 V AC 57...63 Hz 85...132 V AC 47...53 Hz |
| Voltage state 0 guaranteed | 0...20 V AC 57...63 Hz 0...20 V AC 47...53 Hz |
| Input impedance | 12000 Ohm capacitive 57...63 Hz 14400 Ohm capacitive 47...53 Hz |
| Network frequency limits | 47â¦63 Hz |
| Maximum leakage current | 2.1 mA |
| Absolute maximum input | 132 V continuous 156 V 10 s 200 V 1 cycle |
| Response Time | 4.9...0.75 ms x line cycle Off-On 7.3...12.3 ms On-Off |
| Isolation between channels | 1780 Vrms for 1 minute |
| Isolation between channels and bus | 1780 Vrms for 1 minute |
| Bus current requirement | 180 mA |
| Maximum power dissipation in W | 5.5 W |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 16 LEDs (green) for input status |
| Marking | CE |
| Module format | Standard |
| Product Weight | 0.68 lb(US) (0.31 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | VAC discrete input modules |
| Software name | Concept ProWORX 32 Unity Pro |
| Discrete input number | 16 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Group of channels | 16 |
| Addressing requirement | 1 input word |
| Discrete input voltage | 230 V AC |
| Input current | 11.5 mA 57...63 Hz 9.7 mA 47...53 Hz |
| Voltage state 1 guaranteed | 165...264 V AC 57...63 Hz 175...264 V AC 47...53 Hz |
| Voltage state 0 guaranteed | 0...40 V AC 57...63 Hz 0...40 V AC 47...53 Hz |
| Input impedance | 26500 Ohm capacitive 57...63 Hz 31800 Ohm capacitive 47...53 Hz |
| Network frequency limits | 47â¦63 Hz |
| Maximum leakage current | 2.6 mA |
| Absolute maximum input | 264 V continuous 300 V 10 s 400 V 1 cycle |
| Response Time | 4.9...0.75 ms x line cycle Off-On 7.3...12.3 ms On-Off |
| Isolation between channels | 1780 Vrms for 1 minute |
| Isolation between channels and bus | 1780 Vrms for 1 minute |
| Bus current requirement | 180 mA |
| Maximum power dissipation in W | 5.5 W |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) for input status 16 LEDs (green) |
| Marking | CE |
| Module format | Standard |
| Product Weight | 0.77 lb(US) (0.35 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | VAC discrete input modules |
| Software name | Concept Unity Pro ProWORX 32 |
| Discrete input number | 32 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Group of channels | 4 |
| Addressing requirement | 2 input words |
| Discrete input voltage | 230 V AC |
| Input current | 11.5 mA 57...63 Hz 9.7 mA 47...53 Hz |
| Voltage state 1 guaranteed | 165...264 V AC 57...63 Hz 175...264 V AC 47...53 Hz |
| Voltage state 0 guaranteed | 0...40 V AC 57...63 Hz 0...40 V AC 47...53 Hz |
| Input impedance | 26500 Ohm capacitive 57...63 Hz 31800 Ohm capacitive 47...53 Hz |
| Network frequency limits | 47â¦63 Hz |
| Maximum leakage current | 2.6 mA |
| Absolute maximum input | 264 V continuous 312 V 10 s 400 V 1 cycle |
| Response Time | 4.9...0.75 ms x line cycle Off-On 7.3...12.3 ms On-Off |
| Isolation between group | 1780 Vrms for 1 minute |
| Isolation between group and bus | 1780 Vrms for 1 minute |
| Bus current requirement | 250 mA |
| Maximum power dissipation in W | 5 W |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 32 LEDs (green) for input status |
| Marking | CE |
| Module format | Standard |
| Product Weight | 0.7 lb(US) (0.3 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | AC discrete output modules |
| Discrete output number | 16 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Discrete output type | Isolated |
| Group of channels | 16 groups of 1 channel |
| Supply frequency | 47...63 Hz |
| Maximum voltage drop | 1.5 V |
| Discrete output voltage | 20...253 V AC |
| Addressing requirement | 1 output word |
| Absolute maximum output | 300 Vrms 10 s AC 400 Vrms 1 cycle AC |
| Maximum load current | 1 mA rms 24 Vrms off state leakage per output 1 mA rms 48 Vrms off state leakage per output 2 mA rms 115 Vrms off state leakage per output 2.5 mA rms 230 Vrms off state leakage per output 3 A rms 200...230 V per output 4 A rms 24...115 V per output 16 A rms per module 4 A rms sum of four points, continuous |
| Surge current | 10 A during 3 cycles per point 20 A during 2 cycles per point 30 A during 1 cycle per point |
| DV/dt | 400 V/ms |
| Response Time | <= 0.5 ms at state 0 to state 1 <= 0.5 ms at state 1 to state 0 |
| Protection Type | Internal by RC filter |
| Power dissipation | 1.85 + (1.1 V x total module load current) |
| Associated fuse rating | 5 A |
| Marking | CE |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) for input status 16 LEDs (green) |
| Bus current requirement | 350 mA |
| Module format | Standard |
| Product Weight | 1.069 lb(US) (0.485 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | AC discrete output modules |
| Discrete output number | 16 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Group of channels | 4 groups of 4 channels |
| Supply frequency | 47...63 Hz |
| Maximum voltage drop | 1.5 V |
| Discrete output voltage | 83...253 V AC |
| Addressing requirement | 1 output word |
| Absolute maximum output | 300 Vrms 10 s AC 400 Vrms 1 cycle AC |
| Maximum load current | 2 mA rms 115 Vrms off state leakage per output 2.5 mA rms 230 Vrms off state leakage per output 3 A rms 170...253 V per output 4 A rms 85...132 V per output 16 A rms per module 4 A rms per group |
| Surge current | 10 A during 3 cycles per point 20 A during 2 cycles per point 30 A during 1 cycle per point 25 A during 3 cycles per group 30 A during 2 cycles per group 45 A during 1 cycle per group |
| DV/dt | 400 V/ms |
| Response Time | <= 0.5 ms at state 0 to state 1 <= 0.5 ms at state 1 to state 0 |
| Fault indication | Blown fuse Loss of field power |
| Protection Type | Internal by RC filter Internal output protection by 5 A fuse |
| Power dissipation | 1.85 + (1.1 V x total module load current) |
| Marking | CE |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) for input status 16 LEDs (green) |
| Bus current requirement | 350 mA |
| Module format | Standard |
| Product Weight | 0.99 lb(US) (0.45 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | AC discrete output modules |
| Discrete output number | 32 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Group of channels | 4 groups of 8 channels |
| Supply frequency | 47...63 Hz |
| Maximum voltage drop | 1.5 V |
| Discrete output voltage | 20...253 V AC |
| Addressing requirement | 2 output words |
| Absolute maximum output | 300 Vrms 10 s AC 400 Vrms 1 cycle AC |
| Maximum load current | 16 A rms per module 4 A rms per group 0.88 mA 230 V off state leakage per output 1 A rms 20...253 V per output |
| Surge current | 2.5 A 1 ms |
| DV/dt | 400 V/ms |
| Response Time | <= 0.5 ms at state 0 to state 1 <= 0.5 ms at state 1 to state 0 |
| Protection Type | Internal output protection by 4 A fuse Internal by RC filter |
| Power dissipation | 1.60 + (1.0 V x total module load current) |
| Marking | CE |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 32 LEDs (green) for input status |
| Bus current requirement | 320 mA |
| Module format | Standard |
| Product Weight | 0.99 lb(US) (0.45 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | Low voltage dc discrete input modules |
| Discrete input number | 32 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Group of channels | 4 |
| Logic input | Positive (sink) |
| Discrete input voltage | 24 V DC |
| Input voltage limits | 19.2...30 V |
| Voltage state 1 guaranteed | 15...30 V DC |
| Voltage state 0 guaranteed | -3...5 V DC |
| Current state 1 guaranteed | >= 2 mA at Us = 5.5 V and Uin = 0 V |
| Current state 0 guaranteed | <= 0.5 mA |
| Addressing requirement | 2 input words |
| Input impedance | 2500 Ohm |
| Maximum leakage current | 200 mA at Us = 5.5 V and Uin = 4 V |
| Absolute maximum input | 30 V continuous 56 V during 1.3 ms decaying pulse |
| Response Time | <= 1 ms from state 0 to state 1 <= 1 ms from state 1 to state 0 |
| Protection Type | Input protection by resistor limited |
| Power dissipation | 1.7 W + (0.36 x number of points on) |
| Isolation between group and bus | 1780 Vrms for 1 minute |
| Isolation between group | 500 Vrms for 1 minute |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 32 LEDs (green) for input status |
| Marking | CE |
| Bus current requirement | 330 mA |
| Module format | Standard |
| Product Weight | 0.7 lb(US) (0.3 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | Low voltage dc discrete input modules |
| Discrete input number | 32 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Group of channels | 4 |
| Logic input | Negative (source) |
| Discrete input voltage | 24 V DC |
| Input voltage limits | 19.2...30 V |
| Voltage state 1 guaranteed | -30...-15 V DC |
| Voltage state 0 guaranteed | -5...0 V DC |
| Current state 1 guaranteed | >= 2.5 mA at Us = - 14 V |
| Current state 0 guaranteed | <= 0.5 mA |
| Addressing requirement | 2 input words |
| Input impedance | 2400 Ohm |
| Maximum leakage current | 200 mA at Us = 5.5 V and Uin = 4 V |
| Absolute maximum input | 30 V continuous 50 V during 1 ms decaying pulse |
| Response Time | <= 1 ms from state 0 to state 1 <= 1 ms from state 1 to state 0 |
| Protection Type | Input protection by resistor limited |
| Power dissipation | 1.5 W + (0.26 x number of points on) |
| Isolation between group and bus | 1780 Vrms for 1 minute |
| Isolation between group | 500 Vrms for 1 minute |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 32 LEDs (green) for input status |
| Marking | CE |
| Bus current requirement | 330 mA |
| Module format | Standard |
| Product Weight | 0.7 lb(US) (0.3 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | Low voltage dc discrete input modules |
| Discrete input number | 96 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Group of channels | 6 |
| Logic input | Positive (sink) |
| Discrete input voltage | 24 V DC |
| Input voltage limits | 19.2...30 V |
| Voltage state 1 guaranteed | 15...30 V DC |
| Voltage state 0 guaranteed | 5 V DC |
| Current state 1 guaranteed | >= 2.5 mA |
| Current state 0 guaranteed | >= 0.7 mA |
| Addressing requirement | 6 words |
| Input impedance | 6700 Ohm |
| Absolute maximum input | 30 V continuous 50 V decaying pulse |
| Response Time | <= 2 ms from state 0 to state 1 <= 3 ms from state 1 to state 0 |
| Power dissipation | 1.35 W + (0.13 x number of points on) |
| Isolation between group | 500 Vrms for 1 minute |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) for input status 96 LEDs (green) |
| Marking | CE |
| Bus current requirement | 270 mA |
| Module format | Standard |
| Product Weight | 0.7 lb(US) (0.3 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | Dc discrete input modules |
| Discrete input number | 16 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Group of channels | 8 |
| Logic input | Positive (sink) |
| Input voltage limits | 10...60 V |
| Input voltage | 12 V 5â¦10 mA DC 24 V 6â¦30 mA DC 48 V 2â¦15 mA DC 60 V 1â¦5 mA DC |
| Voltage state 1 guaranteed | 11...24 V 24 V +/- 20 % 34...48 V 48 V +/- 20 % 45...60 V 60 V +/- 20 % 9...12 V 12 V +/- 5 % |
| Voltage state 0 guaranteed | 0...1.8 V 12 V +/- 5 % 0...10 V 48 V +/- 20 % 0...5 V 24 V +/- 20 % 0...9 V 60 V +/- 20 % |
| Absolute maximum voltage | 75 V |
| Addressing requirement | 1 input word |
| Response Time | 4 ms from state 0 to state 1 4 ms from state 1 to state 0 |
| Switching frequency | <= 100 Hz |
| Isolation between group and bus | 2500 Vrms DC for 1 minute |
| Isolation between group | 700 Vrms DC for 1 minute |
| Power dissipation | 1 W + (0.62 x number of points on) |
| Marking | CE |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 16 LEDs (green) for input status |
| Bus current requirement | 200 mA |
| Module format | Standard |
| Product Weight | 0.7 lb(US) (0.3 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | Dc discrete input modules |
| Discrete input number | 32 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Group of channels | 4 |
| Logic input | Positive (sink) |
| Input voltage limits | 10...60 V |
| Input voltage | 12 V 5â¦10 mA DC 24 V 6â¦30 mA DC 48 V 2â¦15 mA DC 60 V 1â¦5 mA DC |
| Voltage state 1 guaranteed | 9...12 V 12 V +/- 5 % 11...24 V 24 V - 15...20 % 34...48 V 48 V - 15...20 % 45...60 V 60 V - 15...20 % |
| Voltage state 0 guaranteed | 0...1.8 V 12 V +/- 5 % 0...10 V 48 V - 15...20 % 0...12.5 V 60 V - 15...20 % 0...5 V 24 V - 15...20 % |
| Absolute maximum voltage | 75 V |
| Addressing requirement | 2 input words |
| Response Time | 4 ms from state 0 to state 1 4 ms from state 1 to state 0 |
| Switching frequency | <= 100 Hz |
| Isolation between group and bus | 2500 Vrms DC for 1 minute |
| Isolation between group | 700 Vrms DC for 1 minute |
| Power dissipation | 1 W + (0.25 x number of points on) |
| Marking | CE |
| Local signalling | 1 LED (green) for bus communication is present (Active) 32 LEDs (green) for input status |
| Bus current requirement | 300 mA |
| Module format | Standard |
| Product Weight | 0.650 lb(US) (0.295 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | Mixed discrete I/O module |
| Discrete I/O number | 24 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Discrete input number | 16 2 groups of 8 |
| Discrete input logic | Sink |
| Addressing requirement | 1 input word 0.5 output word |
| Network frequency limits | 47â¦63 Hz |
| Discrete input voltage | 24 V DC |
| Input voltage limits | 30 V <= 1 V during one cycle 56 V during 1.3 ms <= 1 V during 10 s |
| Voltage state 0 guaranteed | -3...5 V |
| Voltage state 1 guaranteed | 15...30 V |
| Current state 0 guaranteed | <= 0.5 mA |
| Current state 1 guaranteed | >= 2 mA |
| Input impedance | 2500 Ohm |
| Discrete output number | 8 2 groups of 4 |
| Discrete output type | Solid state |
| Discrete output logic | Sink |
| Discrete output voltage | 24 V |
| Output voltage limits | 19.2...30 V DC typical 56 V DC during 1.3 ms |
| Maximum load current | <= 0.5 A per point <= 2 A per group <= 4 A per module |
| Maximum voltage drop | <0.4 V 0.5 A |
| Absolute maximum output | 5 A during 500 µs per point |
| Maximum load inductance | 500 mH 4 Hz |
| Maximum load capacitance | 50 µF |
| Maximum leakage current | 0.4 mA 30 V DC |
| Response time on output | <= 1 ms at state 0 to state 1 <= 1 ms at state 1 to state 0 |
| Protection Type | On output by transient voltage suppression On input by resistor limited Internal output protection by 5 A fuse per group |
| Associated fuse rating | 5 A per group |
| Isolation between group | 500 Vrms for 1 minute |
| Isolation between group and bus | 1780 Vrms for 1 minute |
| Fault indication | Blown fuse on output Loss of field power on output |
| Power dissipation | 1.75 W + (0.36 x input point on) + (1.1 total output load current) |
| Local signalling | 1 LED (green) for bus communication is present (Active) for no voltage in output and input (F) 1 LED (red) for output is turned on 2 LEDs (green) for fault detected on the input point 2 LEDs (red) for fault detected on the output point 2 LEDs (red) |
| Marking | CE |
| Bus current requirement | 330 mA |
| Product Weight | 0.7 lb(US) (0.3 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | TTL discrete output module |
| Discrete output number | 32 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Group of channels | 4 groups of 8 channels |
| Discrete output type | TTL Positive (sink) |
| Addressing requirement | 2 output words |
| Discrete output voltage | 5 V DC |
| Voltage state 1 guaranteed | <= 0.2 V |
| [Us] rated supply voltage | 4...5.5 V DC |
| Absolute maximum output | 15 V 0.0013 s decaying voltage pulse DC |
| Internal pullup resistor | 440 Ohm |
| Maximum load current | <= 2.4 A per module <= 600 mA each group <= 75 mA each point |
| Surge current | 750 A 0.5 ms between each point |
| Response time | <= 250 µs at state 0 to state 1 resistive <= 250 µs at state 1 to state 0 resistive |
| Protection Type | Output protection by transient voltage suppression Internal by fuse |
| Fault indication | Blown fuse Loss of field power |
| Power dissipation | 4 W |
| Maximum supply current | 0.4 A |
| Isolation between group | 500 Vrms for 1 minute |
| Marking | CE |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 32 LEDs (green) for input status |
| Bus current requirement | 350 mA |
| Current consumption | 2800 mA 5 V DC |
| Module format | Standard |
| Product Weight | 0.99 lb(US) (0.45 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | Dc discrete output module |
| Discrete output number | 32 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Group of channels | 4 groups of 8 |
| Discrete output logic | Positive logic (source) |
| Addressing requirement | 2 output words |
| Discrete output voltage | 24 V DC |
| Output voltage limits | 19.2...30 V |
| Absolute maximum output | 56 V 1.3 s decaying pulse |
| Maximum voltage drop | <0.4 V 0.5 A |
| Maximum load current | 16 A per module 4 A per group |
| Surge current | 5 A 0.0005 s |
| Response Time | <= 1 ms at state 0 to state 1 <= 1 ms at state 1 to state 0 |
| Maximum leakage current | 0.4 mA 30 V |
| Load inductance | Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz))) 50 Hz |
| Fault indication | Blown fuse Loss of field power |
| Associated fuse rating | 3 A each point 5 A per group |
| Isolation between channels and bus | 1780 Vrms DC for 1 minute |
| Isolation between group | 500 Vrms DC for 1 minute |
| Protection Type | Internal output protection by 5 A fuse per group |
| Power dissipation | 1.75 W + (0.4 V x total module load current) |
| Marking | CE |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 32 LEDs (green) for input status |
| Bus current requirement | 330 mA |
| Module format | Standard |
| Product Weight | 0.99 lb(US) (0.45 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | Dc discrete output module |
| Discrete output number | 32 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Group of channels | 4 groups of 8 |
| Discrete output logic | Positive logic (source) |
| Addressing requirement | 2 output words |
| Discrete output voltage | 24 V DC |
| Output voltage limits | 19.2...30 V |
| Absolute maximum output | 50 V 1 s decaying pulse |
| Maximum voltage drop | <0.4 V 0.5 A |
| Maximum load current | 16 A per module 4 A per group |
| Surge current | 2 A |
| Response Time | <= 0.1 ms at state 1 to state 0 <= 1 ms at state 0 to state 1 |
| Maximum leakage current | 1 mA 24 V |
| Load inductance | Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz))) |
| Fault indication | Loss of field power Blown fuse |
| Associated fuse rating | 3 A each point 5 A per group |
| Isolation between channels and bus | 1780 Vrms DC for 1 minute |
| Isolation between group | 500 Vrms DC for 1 minute |
| Protection Type | Internal output protection by 5 A fuse per group |
| Power dissipation | 5 W |
| Marking | CE |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 32 LEDs (green) for input status |
| Bus current requirement | 330 mA |
| Module format | Standard |
| Product Weight | 0.99 lb(US) (0.45 kg) |