PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

This Acti9 iRLI product is a changeover relay. It has a changeover contact (C/O) and a normally open contact (NO). The Uc control circuit voltage is 230VAV to 240VAC with a 50/60Hz frequency.
Main
| Characteristic | Value(s) |
|---|---|
| range of product | Acti9 |
| product name | Acti9 iRLI |
| Product or component type | Relay |
| Device short name | iRLI |
| Device application | Changeover relay |
| Signal contacts composition | 1 C/O + 1 NO |
| [Uc] control circuit voltage | 230...240 V AC 50/60 Hz |
Complementary
| Characteristic | Value(s) |
|---|---|
| [Ie] rated operational current | 10 A at 230 V AC (cos Phi = 1) |
| [Ui] rated insulation voltage | 250 V AC |
| Supply holding power | 4 VA |
| Supply inrush power | 4 VA |
| Mounting mode | Fixed |
| Mounting support | 35 mm symmetrical DIN rail |
| 9 mm pitches | 2 |
| Height | 88 mm |
| Width | 18 mm |
| Depth | 70 mm |
| Product weight | 0.112 kg |
| Colour | White |
| Electrical durability | AC-21: 100000 cycles |
| Connections - terminals | Tunnel type terminals 0.5â¦6 mm² |

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

This MSU product is an overvoltage release auxiliary. It is mounting on left side of circuit-breaker. The Uc control circuit voltage is 230VAC with a 50/60Hz frequency. The dimensions are (W) 18mm x (H) 82.5mm x (D) 73.5mm.
Main
| Characteristic | Value(s) |
|---|---|
| range of product | Acti9 |
| Product or component type | Overvoltage release |
| Device short name | MSU |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| Threshold tripping voltage | 255 V 275 V 3...15 s 300 V 1...5 s 350 V 0.25...0.75 s 400 V 0.07...0.2 s |
| 9 mm pitches | 2 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Range compatibility | Acti9 iDPN Acti9 C120 Acti9 C40 Acti9 C60H-DC Acti9 C60NA-DC Acti9 C60PV-DC Acti9 DPN Vigi Acti9 DT40 Acti9 ID C40 Acti9 IDc Acti9 ITG40 Acti9 ID Acti9 DPN |
| Local signalling | Action indicator |
| Mounting mode | Fixed |
| Mounting support | 35 mm symmetrical DIN rail |
| Comb busbar and distribution block compatibility | Top: YES |
| Height | 82.5 mm |
| Width | 18 mm |
| Depth | 73.5 mm |
| Product weight | 66 g |
| Colour | White |
| Connections - terminals | Screw clamp terminal (bottom) - 2 cable(s) 1.5 mm² - flexible Screw clamp terminal (bottom) - 2 cable(s) 1.5 mm² - flexible with ferrule Screw clamp terminal (bottom) - 1 cable(s) 0.5â¦2.5 mm² - rigid |
| Wire stripping length | 9 mm 10 mm for bottom connection |
| Tightening torque | 1 N.m bottom |
| Compatibility code | MSU |

This Acti9 Vigi C120 is a modular add-on residual current devices. It has 3P with 3 protected poles, rated current is 125A and operating voltage is 230VAC to 415VAC. The earth leakage protection class is A type with a sensitivity of 500mA and a voltage independent technology. This product protects against short circuit, cable overload, electrical shock by indirect contact and fire hazards. This product is compliant with EN 61009 standard. Electrical endurance goes up to 20000 cycles. The Ue rated operational voltage is from 230VAC to 415VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The pollution degree is 3. It can be mounted on 35 mm symmetrical DIN rail. The width in 9mm pitches is 10. The product color is white (RAL9003). The dimensions are (W) 171mm x (H) 95mm x (D) 73mm. The weight is 0.5kg. The degree of protection is IP20 and IP40 in an enclosure. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 60°C.
Main
| Characteristic | Value(s) |
|---|---|
| Product or component type | Add-on residual current device |
| Device short name | Vigi C120 |
| Poles description | 3P |
| [In] rated current | 125 A |
| Network type | AC |
| Earth-leakage sensitivity | 500 mA |
| Earth-leakage protection time delay | Instantaneous |
| Earth-leakage protection class | Type A |
| Standards | EN 61009 IEC/EN 61009-2-1 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Device location in system | Outgoer Group incomer |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 230...415 V AC 50/60 Hz |
| Residual current tripping technology | Voltage independent |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to IEC 60947-1 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Mounting mode | Clip-on |
| Mounting support | 35 mm symmetrical DIN rail |
| Electrical connection to mcb | By screws |
| 9 mm pitches | 10 |
| Height | 95 mm |
| Width | 171 mm |
| Depth | 73 mm |
| Product weight | 0.5 kg |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Connections - terminals | Tunnel type terminals 1â¦35 mm² flexible Tunnel type terminals 1â¦50 mm² rigid |
| Wire stripping length | 15 mm |
| Tightening torque | 3.5 N.m |

It is a 4P circuit breaker with protected poles, 10 A rated current and C tripping curve. As circuit breaker, its breaking capacity, according to IEC/EN 60947-2, is 20kA at 220VAC to 240VAC, and 10kA at 380VAC to 415VAC. It allows to execute remote control, to indicate the state of the control circuit and circuit breaker state information, to connect it to the Acti9 Smartlink thanks to the prefabricated cables.
Main
| Characteristic | Value(s) |
|---|---|
| Device application | Control Distribution |
| Range | Acti9 |
| product name | Reflex iC60 |
| Device short name | Reflex iC60N |
| Product or component type | Integrated control circuit breaker |
| Poles description | 4P |
| Number of protected poles | 4 |
| Network type | AC |
| Trip unit technology | Thermal-magnetic |
| Curve code | C |
Complementary
| Characteristic | Value(s) |
|---|---|
| [In] rated current | 10 A |
| Network frequency | 50/60 Hz |
| Breaking capacity code | N |
| Breaking capacity | 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| [Ui] rated insulation voltage | 500 V AC |
| Contact position indicator | Yes |
| control type | ON/OFF button Remote control by continuous command Toggle Remote control by pulse |
| Control signal type | Maintained Maintained very low voltage Impulse |
| Local signalling | Flashing LED: device overheat Red LED: fault Flashing LED: device tripped Green LED: device ON Flashing LED: device ready |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC |
| [Us] rated supply voltage | 230 V AC at 50/60 Hz |
| Mounting mode | Fixed |
| Mounting support | 35 mm symmetrical DIN rail |
| 9 mm pitches | 13 |
| Height | 84 mm |
| Width | 117 mm |
| Depth | 77 mm |
| Colour | White |
| Mechanical durability | 50000 cycles |
| Electrical durability | AC-1: 50000 cycles AC 50 Hz |
| Provision for padlocking | Padlockable |
| Locking options description | Padlock in OFF position |
| Earth-leakage protection | Separate block |
| Product compatibility | With PLC |


This Acti9 iCT is a modular contactor. It is a 2P remote control device with 2 normally open contact. The In rated current is 25A for AC-7a and 8.5A for AC-7b. The Ue rated operational voltage is 250VAC. The Uc control voltage is 230VAC to 240VAC. This device could be used for control circuits. It is compatible with all the Acti9 control auxiliaries, for heating & ventilation control applications. This product is compliant with IEC/EN 61095. Electrical endurance goes up to 100000 cycles for AC-7A or AC-1, 30000 cycles for AC-7C, AC-7B, AC-3, AC-5A or AC-5B. The maximum switching operations is 100 per day. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 4kV. Pollution degree is 2. It is DIN rail mountable. Its width is 2 pitches of 9mm. The product color is white (RAL9003). The dimensions are (W) 81mm x (H) 18mm x (D) 60mm. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is from -5°C to 60 °C. The storage temperature is from -40°C to 70°C.
Main
| Characteristic | Value(s) |
|---|---|
| range of product | Acti9 |
| product name | Acti9 iCT |
| Product or component type | Contactor |
| Device short name | iCT |
| Device application | Motor-heating-lighting |
| Poles | 2P |
| [Ie] rated operational current | 25 A AC-7A 8.5 A AC-7B |
| Pole contact composition | 2 NO |
| Network type | AC |
| control type | Remote and manual control |
| [Uc] control circuit voltage | 230...240 V AC 50 Hz |
Complementary
| Characteristic | Value(s) |
|---|---|
| Network frequency | 50 Hz |
| [Ue] rated operational voltage | 250 V AC 50 Hz |
| Maximum power | 1.2 W at 250 V AC |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 4 kV |
| Control signal type | Maintained |
| Switching frequency | 100 switching operations/day |
| Local signalling | Action indicator |
| Hold-in power consumption in VA | 2.7 VA |
| Inrush power in VA | 9.2 VA |
| Mounting mode | Clip-on |
| Mounting support | 35 mm symmetrical DIN rail |
| 9 mm pitches | 2 |
| Height | 81 mm |
| Width | 18 mm |
| Depth | 60 mm |
| Colour | White |
| Mechanical durability | 1000000 cycles |
| Electrical durability | 100000 cycles IEC/EN 61095 25 A 50 Hz AC-7A 30000 cycles IEC/EN 61095 8.5 A 50 Hz AC-7B 30000 cycles IEC/EN 61095 50 Hz AC-7C 100000 cycles EN/IEC 60947-4-1 50 Hz AC-1 30000 cycles EN/IEC 60947-4-1 50 Hz AC-3 30000 cycles EN/IEC 60947-4-1 50 Hz AC-5a 30000 cycles EN/IEC 60947-4-1 50 Hz AC-5b |
| Connections - terminals | Control circuit: tunnel type terminals2 cable(s) 1.5 mm² rigid Power circuit: tunnel type terminals1 cable(s) 1â¦4 mm² flexible Power circuit: tunnel type terminals1 cable(s) 1.5â¦6 mm² rigid Control circuit: tunnel type terminals1 cable(s) 1.5â¦2.5 mm² rigid Control circuit: tunnel type terminals2 cable(s) 1.5â¦2.5 mm² flexible |
| Tightening torque | Control circuit: 0.8 N.m Power circuit: 0.8 N.m |
| Product compatibility | IACTs IACTc IACTp IATEt |
| Compatibility code | ICT |
| Market segment | Small commercial Residential |

This PowerTag A9 M63 1PW for Acti 9 and Multi 9 Monoconnect offers is a Class 1 wireless-communication energy sensor. It is dedicated to Acti9 and Multi9 1P Monoconnect devices rating less than or equal 63A. The neutral blue wire is to be connected to a neutral terminal block. It has to be associated with a concentror or a gateway to provide circuit monitoring and diagnosis down to load level. It is designed specifically for Energy Management, Load Monitoring and Power Availability applications. It incorporates accurate real-time measurements of active energy, active power, current, voltage and power factor. In case of power outage, it sends a voltage loss alarm and the current-per-phase value before being de-energized. PowerTag Energy 63A complies with IEC 61557-12 standard. It is a PMD-I/DD/K55/1. The Performance category is Class 1. The Imax Maximum current is 63A. The Ib Base current is 10A. The Saturation current is 130A. The Ist Starting current is 40mA. The Un rated voltage is Phase-to-neutral 200VAC to 240VAC +/- 20%. The maximum consumption is below or equal to 1VA. The degree of protection is IP20 and IK05 The Operating temperature is between -25°C to +60°C. The Storage temperature is between 40°C to +85°C. The Performance category is Class 1. PowerTag Energy 63A complies with IEC 61557-12 standard.
Main
| Characteristic | Value(s) |
|---|---|
| Range of product | PowerLogic |
| product name | PowerTag A9 M63 |
| Product or component type | Energy sensor |
| Poles | 1P |
| Maximum current [Imax] | 63 A |
| [Ib] Basic current | 10 A |
| Starting current | 40 mA |
| Saturation current | 130 A |
| Product specific application | Load monitoring Overload alarm Cost allocation Circuit monitoring Energy management |
| Concentrator compatibility | Acti9 Smartlink SI B Acti9 Smartlink SI D Acti9 PowerTag Link C Acti9 PowerTag Link Acti9 PowerTag Link HD Wiser IP module EcoStruxure Panel Server Universal EcoStruxure Panel Server Advanced PrismaSet Active |
| Application | Buildings: breaker voltage monitoring Buildings: cost allocation Buildings: overload alarm |
| Range compatibility | Acti 9 Acti9 iKQE RCBO Multi9 Multi9 C60 Multi9 Multi9 ID Multi9 Multi9 C32N Multi9 Multi9 C65 Acti 9 Acti9 iID Acti 9 Acti9 iID K Acti 9 Acti9 iK60 Acti 9 Acti9 iKQ Acti 9 Acti9 K60 Acti 9 Acti9 Reflex iC60 Acti 9 Acti9 iC65 Acti 9 Acti9 DT60 Acti 9 Acti9 iC60 single terminal |
| Type of measurement | Voltage Power factor Active energy Current Active power |
| Accuracy class | Class 1 current conforming to IEC 61557-12 Class 0.5 voltage conforming to IEC 61557-12 Class 1 active power conforming to IEC 61557-12 Class 1 active energy conforming to IEC 61557-12 Class 1 power factor conforming to IEC 61557-12 |
| Mounting location | Top or bottom |
| Mounting support | On circuit breaker |
| Product destination | Switchboard |
| Event management | Voltage loss with measured current at voltage loss |
| Transmission support medium | Radio frequency 2.4â¦2.4835 GHz conforming to IEEE 802.15.4 |
| Emission power | 10 mW |
Complementary
| Characteristic | Value(s) |
|---|---|
| Form factor | Monoconnect |
| Mounting mode | By screws (terminals) |
| Electrical connection (voltage sensing & power supply) | Connector tooth and wire |
| Cable cross section | 1 rigid cable 1.5â¦16 mm² 2 stranded cable 1.5â¦2.5 mm² 2 rigid cable 1.5â¦2.5 mm² 1 stranded cable 1.5â¦16 mm² |
| Cable length | 1 m |
| supply voltage | 200...240 V AC, +/- 20 % |
| Cable composition | 1 x 0.33 mm² |
| Network frequency | 50 Hz 60 Hz |
| Maximum power consumption | 1 VA |
| Standards | IEC 61557-12 IEC 61010-1 IEC 61010-2-030 IEC 61326-1 ETSI EN 300 328 ETSI EN 301 489-1 |
| Height | 16.5 mm |
| Width | 18 mm |
| Depth | 43 mm |
| Product weight | 16.4 g |
| Colour | White (RAL 9003) |
| Compatibility code | PowerTag A9 M63 |

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

It is a 2P circuit breaker with protected poles, 16 A rated current and B tripping curve. As circuit breaker, its breaking capacity, according to IEC/EN 60947-2, is 20kA at 220VAC to 240VAC, and 10kA at 380VAC to 415VAC. It allows to execute remote control, to indicate the state of the control circuit and circuit breaker state information, to connect it to the Acti9 Smartlink thanks to the prefabricated cables.
Main
| Characteristic | Value(s) |
|---|---|
| Device application | Distribution Control |
| Range | Acti9 |
| product name | Reflex iC60 |
| Device short name | Reflex iC60N |
| Product or component type | Integrated control circuit breaker |
| Poles description | 2P |
| Number of protected poles | 2 |
| Network type | AC |
| Trip unit technology | Thermal-magnetic |
| Curve code | B |
Complementary
| Characteristic | Value(s) |
|---|---|
| [In] rated current | 16 A |
| Network frequency | 50/60 Hz |
| Breaking capacity code | N |
| Breaking capacity | 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| [Ui] rated insulation voltage | 500 V AC |
| Contact position indicator | Yes |
| control type | ON/OFF button Remote control by pulse Toggle Remote control by continuous command |
| Control signal type | Impulse Maintained Maintained very low voltage |
| Local signalling | Green LED: device ON Flashing LED: device ready Flashing LED: device tripped Flashing LED: device overheat Red LED: fault |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC |
| [Us] rated supply voltage | 230 V AC at 50/60 Hz |
| Mounting mode | Fixed |
| Mounting support | 35 mm symmetrical DIN rail |
| 9 mm pitches | 9 |
| Height | 84 mm |
| Width | 81 mm |
| Depth | 77 mm |
| Colour | White |
| Mechanical durability | 50000 cycles |
| Electrical durability | AC-1: 50000 cycles AC 50 Hz |
| Provision for padlocking | Padlockable |
| Locking options description | Padlock in OFF position |
| Earth-leakage protection | Separate block |
| Product compatibility | With PLC |

This Acti9 Vigi C120 is a modular add-on residual current devices. It has 2P with 2 protected poles, rated current is 125A and operating voltage is 230VAC to 240VAC. The earth leakage protection class is A type with a sensitivity of 30mA and a voltage independent technology. This product protects against short circuit, cable overload, electrical shock by indirect contact and fire hazards. This product is compliant with EN 61009 standard. Electrical endurance goes up to 20000 cycles. The Ue rated operational voltage is from 230VAC to 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The pollution degree is 3. It can be mounted on 35 mm symmetrical DIN rail. The width in 9mm pitches is 7. The product color is white (RAL9003). The dimensions are (W) 117mm x (H) 95mm x (D) 73mm. The weight is 0.325kg. The degree of protection is IP20 and IP40 in an enclosure. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 60°C.
Main
| Characteristic | Value(s) |
|---|---|
| Range | Acti9 |
| product name | Acti9 Vigi C120 |
| Product or component type | Add-on residual current device |
| Device short name | Vigi C120 |
| Poles description | 2P |
| [In] rated current | 125 A |
| Network type | AC |
| Earth-leakage sensitivity | 30 mA |
| Earth-leakage protection time delay | Instantaneous |
| Earth-leakage protection class | Type A |
| Standards | EN 61009 IEC/EN 61009-2-1 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Device location in system | Outgoer Group incomer |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 230...240 V AC 50/60 Hz |
| Residual current tripping technology | Voltage independent |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to IEC 60947-1 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Mounting mode | Clip-on |
| Mounting support | 35 mm symmetrical DIN rail |
| Electrical connection to mcb | By screws |
| 9 mm pitches | 7 |
| Height | 95 mm |
| Width | 117 mm |
| Depth | 73 mm |
| Product weight | 0.325 kg |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Connections - terminals | Tunnel type terminals 1â¦35 mm² flexible Tunnel type terminals 1â¦50 mm² rigid |
| Wire stripping length | 15 mm |
| Tightening torque | 3.5 N.m |

Main
| Characteristic | Value(s) |
|---|---|
| range of product | Acti9 |
| product name | Acti9 iIL |
| Product or component type | Modular pilot light |
| Device short name | iIL |
| [Us] rated supply voltage | 12...48 V AC at 50/60 Hz 12...48 V DC |
Complementary
| Characteristic | Value(s) |
|---|---|
| indicator light | 1 LED white, service life 100000 h of constant lighting efficiency (consumption 0.3 W) |
| Mounting mode | Fixed |
| Mounting support | Symmetrical DIN rail |
| Comb busbar and distribution block compatibility | Upside: ProDis |
| 9 mm pitches | 2 |
| Height | 82 mm |
| Width | 18 mm |
| Depth | 69.5 mm |
| Colour | White (RAL 9003) |
| Auxiliary connection terminal | Tunnel type terminal 1 cable(s) rigid 0.5 mm² Tunnel type terminal 2 cable(s) rigid 2.5 mm² Tunnel type terminal 1 cable(s) flexible 0.5 mm² Tunnel type terminal 2 cable(s) flexible 2.5 mm² Tunnel type terminal 2 cable(s) flexible with ferrule 2.5 mm² |
| Wire stripping length | 9 mm |
| Tightening torque | 1 N.m |

This Acti9 iPRD8 surge arrester protects 4P installations. It allows quick replacement of damaged cartridges. The Imax maximum discharge current is 8kA .The In nominal discharge current is 2.5kA. The iPRD8r ensures secondary protection of loads to be protected and is placed in cascade with the incoming surge arresters. This surge arrester is required when the loads to be protected are at a distance of more than 10 m from the incoming surge arrester. The Uc maximum continuous operating voltage in common mode (between neutral and earth) is 260VAC. The Uc maximum continuous operating voltage in common mode (between phase and earth) is 350VAC. The Up Voltage protection level in common mode (between phase and earth) is 1.1kV in type 2. The Up Voltage protection level in common mode (between phase and earth) is 1.2kV in type 3. The Ue rated operational voltage is 230VAC +/- 10%. The product colour is white (RAL9003).The dimensions are (W) 36mm x (H) 85mm x (D) 69mm. The weight is 416g. The degree of protection is IP20 and IP40 in modular enclosure. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 85°C. This product is compliant with EN 61643-11 and IEC 61643-11 standards.
Main
| Characteristic | Value(s) |
|---|---|
| Range of product | IPRD |
| range of product | Acti9 |
| product name | Acti9 iPRD |
| Product or component type | Surge arrester with pluggable cartridge |
| Device short name | iPRD8 |
| Device application | Distribution |
| Standards | EN 61643-11:2012 IEC 61643-11:2011 |
| Product certifications | CE |
| Quality labels | KEMA-KEUR NF |
| Poles description | 4P |
| Remote signalling | Without |
| Surge arrester type | Electrical distribution network |
| Earthing system | TN-C-S |
Complementary
| Characteristic | Value(s) |
|---|---|
| Surge arrester class type | Type 2 + 3 |
| Surge arrester technology | MOV + GDT |
| [Ue] rated operational voltage | 230/400 V AC (+/- 10 %) at 50/60 Hz |
| Nominal discharge current | Common mode: 2.5 kA (L/PE) Common mode: 2.5 kA (N/PE) |
| Maximum discharge current | Common mode: 8 kA L/PE Common mode: 8 kA N/PE |
| [Uoc] open circuit voltage | 10 kV type 3 common mode L/PE 10 kV type 3 common mode N/PE |
| [Uc] maximum continuous operating voltage | Common mode: 260 V N/PE Common mode: 350 V L/PE |
| Maximum [Up] voltage protection level | Common mode <1.1 kV type 2 L/PE Common mode <1.1 kV type 2 N/PE Common mode <1.2 kV type 3 N/PE Common mode <1.2 kV type 3 L/PE |
| [Ut] temporary overvoltage | 337 V L/N 5 s withstand 1200 V N/PE 200 ms safe failure mode |
| Disconnector device type | Associated circuit breaker iC60L 10 A curve C - Icu 25 kA Associated circuit breaker IC60N 10 A curve C - Icu 10 kA Associated circuit breaker iC60H 10 A curve C - Icu 15 kA Associated fuse gG 25 A - Icu 15 kA Associated fuse gG 80 A - Icu 50 kA |
| Mounting mode | Clip-on (DIN rail) |
| 9 mm pitches | 8 |
| Height | 85 mm |
| Width | 72 mm |
| Depth | 69 mm |
| Product weight | 0.416 kg |
| Colour | White (RAL 9003) |
| [Ipe] Ground residual current | 0.003 mA 0.6 mA |
| Connections - terminals | Tunnel type terminal (downside) 2.5â¦35 mm² Tunnel type terminal (upside) 2.5â¦35 mm² |
| Tightening torque | 2.5 N.m |
| Compatibility code | IPRD8r |