3RT2036-1AC20 Siemens
Siemens 3RT2036-1AC20 Siemens
Sale price $174.59
Only 9 units left
Product
Article Number (Market Facing Number) 3RT20361AC20 | 3RT20361AC20
Product Description power contactor, AC-3e/AC-3, 51 A, 22 kW / 400 V, 3-pole, 24 V AC, 50/60 Hz, auxiliary contacts: 1 NO + 1 NC, screw terminal, size: S2
Product family SIRIUS 3RT contactors, 3-pole, up to 250 kW
Product Lifecycle (PLM) PM300:Active Product
Additional Product Information
EAN 4011209939592
UPC 887621916183
Commodity Code 85364190
LKZ_FDB/ CatalogID CC-IC10
Product Group 5338
Group Code R711
Country of origin Germany
SCIP number Not available
Delivery information
Net Weight (lb) 2.196 lb
Package size unit of measure Inch
Packaging Quantity 1
Siemens New Stock Image
Siemens 3RT6016-1AN21 Siemens
Sale price $74.93
Only 7 units left
PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.
3RH2921-1DA11 Siemens
Siemens 3RH2921-1DA11 Siemens
Sale price $75.17
In stock, 11 units
Product
Article Number (Market Facing Number) 3RH29211DA11 | 3RH29211DA11
Product Description auxiliary switch, lateral, 1 NO + 1 NC, on the left: 51/52, 63/64, on the right: 31/32, 43/44, current path: 1 NC, 1 NO, screw terminal, for contactors 3RT2 and contactor relays 3RH2
Product family Instantaneous
Product Lifecycle (PLM) PM300:Active Product
Additional Product Information
EAN 4011209790285
UPC 662643908497
Commodity Code 85365080
LKZ_FDB/ CatalogID CC-IC10
Product Group 5344
Group Code R711
Country of origin Romania
SCIP number Not available
Delivery information
Net Weight (lb) 0.086 lb
Package size unit of measure in
Packaging Quantity 1
3RH2911-1XA40-0MA0 Siemens
Siemens 3RH2911-1XA40-0MA0 Siemens
Sale price $73.07
Only 7 units left
Product
Article Number (Market Facing Number) 3RH29111XA400MA0 | 3RH29111XA400MA0
Product Description auxiliary switch, on the front, 4 NO, 53/54, 63/64, 73/74, 83/84, current path: 1 NO, 1 NO, 1 NO, 1 NO, screw terminal, for contactors 3RT2 and contactor relays 3RH2
Product family Instantaneous
Product Lifecycle (PLM) PM300:Active Product
Additional Product Information
EAN 4011209896048
UPC 040892957358
Commodity Code 85365080
LKZ_FDB/ CatalogID CC-IC10
Product Group 5344
Group Code R711
Country of origin Czech Republic
SCIP number Not available
Delivery information
Net Weight (lb) 0.113 lb
Package size unit of measure Inch
Packaging Quantity 1
Schneider New Stock Image
Schneider LC1D115M7С Schneider
Sale price $178.85
In stock, 11 units

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

LC1D09M7 Schneider Electric
Schneider LC1D09M7 Schneider Electric
Sale price $89.01
Only 8 units left

TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3/3e (4kW@400V). They can be used to create motor starters for almost any type of application. It provides a 220V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability to demanding applications. Compact (45mm width), DIN-rail mounting or screw fixing. Contactor is rated for 20HP at 200-208VAC, 25HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 25A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 220 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.

Main

Characteristic Value(s)
Range of Product TeSys Deca
Product or Component Type Contactor
Device short name LC1D
Contactor application Motor control
Resistive load
Utilisation category AC-4
AC-3
AC-1
AC-3e
Poles description 3P
[Ue] rated operational voltage Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current 9 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
25 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
9 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage 220 V AC 50/60 Hz

Complementary

Characteristic Value(s)
Motor power kW 2.2 kW at 220...230 V AC 50/60 Hz (AC-3)
4 kW at 380...400 V AC 50/60 Hz (AC-3)
4 kW at 415...440 V AC 50/60 Hz (AC-3)
5.5 kW at 500 V AC 50/60 Hz (AC-3)
5.5 kW at 660...690 V AC 50/60 Hz (AC-3)
2.2 kW at 400 V AC 50/60 Hz (AC-4)
2.2 kW at 220...230 V AC 50/60 Hz (AC-3e)
4 kW at 380...400 V AC 50/60 Hz (AC-3e)
4 kW at 415...440 V AC 50/60 Hz (AC-3e)
5.5 kW at 500 V AC 50/60 Hz (AC-3e)
5.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating 1 hp at 230/240 V AC 50/60 Hz for 1 phase motors
2 hp at 200/208 V AC 50/60 Hz for 3 phase motors
2 hp at 230/240 V AC 50/60 Hz for 3 phase motors
5 hp at 460/480 V AC 50/60 Hz for 3 phase motors
7.5 hp at 575/600 V AC 50/60 Hz for 3 phase motors
0.33 hp at 115 V AC 50/60 Hz for 1 phase motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover With
[Ith] conventional free air thermal current 25 A (at 140 °F (60 °C)) for power circuit
10 A (at 140 °F (60 °C)) for signalling circuit
Irms rated making capacity 250 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity 250 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 105 A 104 °F (40 °C) - 10 s for power circuit
210 A 104 °F (40 °C) - 1 s for power circuit
30 A 104 °F (40 °C) - 10 min for power circuit
61 A 104 °F (40 °C) - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
25 A gG at <= 690 V coordination type 1 for power circuit
20 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2.5 mOhm - Ith 25 A 50 Hz for power circuit
Power dissipation per pole 1.56 W AC-1
0.2 W AC-3
0.2 W AC-3e
[Ui] rated insulation voltage Power circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Overvoltage category III
pollution degree 3
[Uimp] rated impulse withstand voltage 6 kV IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 15 Mcycles
Electrical durability 0.6 Mcycles 25 A AC-1 <= 440 V
2 Mcycles 9 A AC-3 <= 440 V
2 Mcycles 9 A AC-3e <= 440 V
Control circuit type AC 50/60 Hz standard
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3...0.6 Uc (-40…158 °F (-40…70 °C)):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC 50 Hz
0.85...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC 60 Hz
1...1.1 Uc (140…158 °F (60…70 °C)):operational AC 50/60 Hz
Inrush power in VA 70 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))
70 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA 7.5 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
7 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation 2…3 W at 50/60 Hz
Operating time 12...22 ms closing
4...19 ms opening
Maximum operating rate 3600 cyc/h at 60 °C
Connections - terminals Power circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Tightening torque Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support Plate
Rail
LP1D65008BD Schneider Electric
Schneider LP1D65008BD Schneider Electric
Sale price$0.00
Sold Out

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 80A resistive load rating. Contactor is supplied with a 24 VDC coil with transient suppressor module. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 7.17 inches deep. It weighs 4.89 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.

Main

Characteristic Value(s)
Range TeSys
Range of Product TeSys Deca
Product or Component Type Contactor
Device short name LP1D
Contactor application Resistive load
Utilisation category AC-1
Poles description 4P
[Ue] rated operational voltage Power circuit <= 1000 V AC 25...400 Hz
[Ie] rated operational current 80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage 24 V DC

Complementary

Characteristic Value(s)
Compatibility code LP1D
Pole contact composition 2 NO + 2 NC
Protective cover With
[Ith] conventional free air thermal current 80 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity 1000 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 110 A 104 °F (40 °C) - 10 min for power circuit
260 A 104 °F (40 °C) - 1 min for power circuit
520 A 104 °F (40 °C) - 10 s for power circuit
900 A 104 °F (40 °C) - 1 s for power circuit
Associated fuse rating 125 A gG at <= 690 V coordination type 1 for power circuit
125 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole 9.6 W AC-1
[Ui] rated insulation voltage Power circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Overvoltage category III
pollution degree 3
[Uimp] rated impulse withstand voltage 6 kV IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 10 Mcycles
Electrical durability 1.5 Mcycles 80 A AC-1 <= 440 V
Control circuit type DC DC standard
Coil technology Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits 0.1...0.3 Uc (-40…131 °F (-40…55 °C)):drop-out DC
0.85...1.1 Uc (-40…131 °F (-40…55 °C)):operational DC
Inrush power in W 22 W 68 °F (20 °C))
Hold-in power consumption in W 22 W 68 °F (20 °C)
Operating time 4...19 ms opening
12...26 ms closing
Time constant 75 ms
Maximum operating rate 3600 cyc/h at 60 °C
Connections - terminals Power circuit: screw clamp terminals 1 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 2 0.004…0.02 in² (2.5…16 mm²) - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 0.004…0.02 in² (2.5…10 mm²) - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: solid
Power circuit: screw clamp terminals 2 0.004…0.02 in² (2.5…16 mm²) - cable stiffness: solid
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid
Tightening torque Power circuit 70.8 lbf.in (8 N.m) screw clamp terminals 0.04…0.05 in² (25…35 mm²) hexagonal 0.2 in (4 mm)
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Power circuit 44.3 lbf.in (5 N.m) screw clamp terminals 0.002…0.04 in² (1…25 mm²) hexagonal 0.2 in (4 mm)
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Mounting Support Plate
Rail
Schneider New Stock Image
Schneider LC1G800KUEN Schneider
Sale price $2,882.81
Only 6 units left
PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.
Schneider New Stock Image
Schneider LC1D115G6 Schneider
Sale price $1,500.84
Only 2 units left

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 115A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 30HP at 200 to 208VAC, 40HP at 240VAC, 75HP at 480VAC and 100HP at 600VAC three phase. When used with a 480VAC up to 250A circuit breaker, this contactor can have a SCCR up to 100kA. When used with a 600VAC up to 250A circuit breaker, this contactor can have a SCCR up to 50kA. When used with 600VAC Class J or CC fuses up to 250A, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 120 VAC 60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.

Main

Characteristic Value(s)
Range TeSys
Range of Product TeSys Deca
Product or Component Type Contactor
Device short name LC1D
Contactor application Motor control
Resistive load
Utilisation category AC-3
AC-4
AC-1
AC-3e
Poles description 3P
[Ue] rated operational voltage Power circuit <= 1000 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current 200 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
115 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
115 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage 120 V AC 60 Hz

Complementary

Characteristic Value(s)
Motor power kW 30 kW at 220...230 V AC 50/60 Hz (AC-3)
55 kW at 380...400 V AC 50/60 Hz (AC-3)
59 kW at 415...440 V AC 50/60 Hz (AC-3)
75 kW at 500 V AC 50/60 Hz (AC-3)
80 kW at 660...690 V AC 50/60 Hz (AC-3)
65 kW at 1000 V AC 50/60 Hz (AC-3)
18.5 kW at 400 V AC 50/60 Hz (AC-4)
30 kW at 220...230 V AC 50/60 Hz (AC-3e)
55 kW at 380...400 V AC 50/60 Hz (AC-3e)
59 kW at 415...440 V AC 50/60 Hz (AC-3e)
75 kW at 500 V AC 50/60 Hz (AC-3e)
80 kW at 660...690 V AC 50/60 Hz (AC-3e)
65 kW at 1000 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating 30 hp at 200/208 V AC 50/60 Hz for 3 phase motors
40 hp at 230/240 V AC 50/60 Hz for 3 phase motors
75 hp at 460/480 V AC 50/60 Hz for 3 phase motors
100 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover With
[Ith] conventional free air thermal current 200 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity 1260 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity 1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 250 A 104 °F (40 °C) - 10 min for power circuit
550 A 104 °F (40 °C) - 1 min for power circuit
950 A 104 °F (40 °C) - 10 s for power circuit
1100 A 104 °F (40 °C) - 1 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating 250 A gG at <= 690 V coordination type 1 for power circuit
200 A gG at <= 690 V coordination type 2 for power circuit
10 A gG for signalling circuit
Average impedance 0.6 mOhm - Ith 200 A 50 Hz for power circuit
Power dissipation per pole 24 W AC-1
7.9 W AC-3
7.9 W AC-3e
[Ui] rated insulation voltage Power circuit 600 V CSA
Power circuit 600 V UL
Power circuit 1000 V IEC 60947-4-1
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Overvoltage category III
pollution degree 3
[Uimp] rated impulse withstand voltage 8 kV IEC 60947
Safety reliability level B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1
B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 8 Mcycles
Electrical durability 0.8 Mcycles 200 A AC-1 <= 440 V
0.95 Mcycles 115 A AC-3 <= 440 V
0.95 Mcycles 115 A AC-3e <= 440 V
Control circuit type AC 60 Hz
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.85...1.1 Uc (-40…131 °F (-40…55 °C)):operational AC 60 Hz
0.3...0.6 Uc (-40…158 °F (-40…70 °C)):drop-out AC 60 Hz
1...1.1 Uc (131…158 °F (55…70 °C)):operational AC 60 Hz
Inrush power in VA 300 VA 60 Hz cos phi 0.8 (at 68 °F (20 °C))
Hold-in power consumption in VA 22 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation 3…8 W at 60 Hz
Operating time 6...20 ms opening
20...50 ms closing
Maximum operating rate 2400 cyc/h at 60 °C
Connections - terminals Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: solid without cable end
Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: flexible without cable end
Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: flexible without cable end
Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: flexible with cable end
Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: flexible with cable end
Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: solid without cable end
Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: solid without cable end
Tightening torque Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2
Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm)
Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support Plate
Rail
LC1D80M7C Schneider
Schneider LC1D80M7C Schneider
Sale price $126.36
In stock, 11 units

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 80 A - 220 V AC 50/60 Hz coil

LC1D32BL Schneider Electric
Schneider LC1D32BL Schneider Electric
Sale price $234.17
Only 9 units left

TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 32A/690V AC-3/3e (15kW@400V). They can be used to create motor starters for almost any type of application. It provides a low consumption 24V DC coil with transient suppressor module, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a low consumption 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.18 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.

Main

Characteristic Value(s)
Range of Product TeSys Deca
Product or Component Type Contactor
Device short name LC1D
Contactor application Motor control
Resistive load
Utilisation category AC-3
AC-1
AC-4
AC-3e
Poles description 3P
[Ue] rated operational voltage Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current 32 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
50 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
32 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage 24 V DC

Complementary

Characteristic Value(s)
Motor power kW 7.5 kW at 220...230 V AC 50/60 Hz (AC-3)
15 kW at 380...400 V AC 50/60 Hz (AC-3)
15 kW at 415...440 V AC 50/60 Hz (AC-3)
18.5 kW at 500 V AC 50/60 Hz (AC-3)
18.5 kW at 660...690 V AC 50/60 Hz (AC-3)
7.5 kW at 400 V AC 50/60 Hz (AC-4)
7.5 kW at 220...230 V AC 50/60 Hz (AC-3e)
15 kW at 380...400 V AC 50/60 Hz (AC-3e)
15 kW at 415...440 V AC 50/60 Hz (AC-3e)
18.5 kW at 500 V AC 50/60 Hz (AC-3e)
18.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating 2 hp at 115 V AC 50/60 Hz for 1 phase motors
5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
10 hp at 200/208 V AC 50/60 Hz for 3 phase motors
10 hp at 230/240 V AC 50/60 Hz for 3 phase motors
20 hp at 460/480 V AC 50/60 Hz for 3 phase motors
25 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover With
[Ith] conventional free air thermal current 10 A (at 140 °F (60 °C)) for signalling circuit
50 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
550 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 550 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 260 A 104 °F (40 °C) - 10 s for power circuit
430 A 104 °F (40 °C) - 1 s for power circuit
60 A 104 °F (40 °C) - 10 min for power circuit
138 A 104 °F (40 °C) - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
63 A gG at <= 690 V coordination type 1 for power circuit
63 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2 mOhm - Ith 50 A 50 Hz for power circuit
Power dissipation per pole 2 W AC-3
5 W AC-1
2 W AC-3e
[Ui] rated insulation voltage Power circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Overvoltage category III
pollution degree 3
[Uimp] rated impulse withstand voltage 6 kV IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 30 Mcycles
Electrical durability 1.65 Mcycles 32 A AC-3 <= 440 V
1.4 Mcycles 50 A AC-1 <= 440 V
1.65 Mcycles 32 A AC-3e <= 440 V
Control circuit type DC low consumption
Coil technology Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits 0.1...0.3 Uc (-40…158 °F (-40…70 °C)):drop-out DC
0.8...1.25 Uc (-40…140 °F (-40…60 °C)):operational DC
1...1.25 Uc (140…158 °F (60…70 °C)):operational DC
Inrush power in W 2.4 W 68 °F (20 °C))
Hold-in power consumption in W 2.4 W 68 °F (20 °C)
Operating time 77 ±15 % ms closing
25 ±20 % ms opening
Time constant 40 ms
Maximum operating rate 3600 cyc/h at 60 °C
Connections - terminals Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 1 0.004…0.02 in² (2.5…10 mm²) - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 2 0.004…0.02 in² (2.5…10 mm²) - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 0.002…0.02 in² (1…10 mm²) - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 0.002…0.009 in² (1.5…6 mm²) - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 0.002…0.02 in² (1.5…10 mm²) - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 0.004…0.02 in² (2.5…10 mm²) - cable stiffness: solid without cable end
Tightening torque Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Power circuit 22.1 lbf.in (2.5 N.m) screw clamp terminals flat Ø 6 mm
Power circuit 22.1 lbf.in (2.5 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Power circuit 22.1 lbf.in (2.5 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support Plate
Rail
LC1D65AM7C Schneider
Schneider LC1D65AM7C Schneider
Sale price $117.54
Only 5 units left

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC 50/60 Hz coil

3RT2017-2BB41 Siemens
Siemens 3RT2017-2BB41 Siemens
Sale price $115.47
Only 9 units left
Product
Article Number (Market Facing Number) 3RT20172BB41 | 3RT20172BB41
Product Description power contactor, AC-3e/AC-3, 12 A, 5.5 kW / 400 V, 3-pole, 24 V DC, auxiliary contacts: 1 NO, spring-loaded terminal, size: S00
Product family SIRIUS 3RT contactors, 3-pole, up to 250 kW
Product Lifecycle (PLM) PM300:Active Product
Additional Product Information
EAN 4011209785489
UPC 662643911572
Commodity Code 85364190
LKZ_FDB/ CatalogID CC-IC10
Product Group 5330
Group Code R711
Country of origin Germany
SCIP number Not available
Delivery information
Net Weight (lb) 0.686 lb
Package size unit of measure in
Packaging Quantity 1
Siemens New Stock Image
Siemens 3RT1066-6AF36 Siemens
Sale price $1,391.06
Only 8 units left
Product
Article Number (Market Facing Number) 3RT10666AF36 | 3RT10666AF36
Product Description power contactor, AC-3e/AC-3 300 A, 160 kW / 400 V, AC (50-60 Hz) / DC Uc: 110-127 V 3-pole, auxiliary contacts 2 NO + 2 NC drive: conventional main circuit: busbar control and auxiliary circuit: screw terminal
Product family SIRIUS 3RT contactors, 3-pole, up to 250 kW
Product Lifecycle (PLM) PM300:Active Product
Additional Product Information
EAN 4011209508118
UPC 754554766713
Commodity Code 85364900
LKZ_FDB/ CatalogID CC-IC10
Product Group 3706
Group Code R711
Country of origin Germany
SCIP number Not available
Delivery information
Net Weight (lb) 14.343 lb
Package size unit of measure in
Packaging Quantity 1
Siemens New Stock Image
Siemens 3RT1064-6AF36 Siemens
Sale price $890.57
Only 9 units left
Product
Article Number (Market Facing Number) 3RT10646AF36 | 3RT10646AF36
Product Description power contactor, AC-3e/AC-3 225 A, 110 kW / 400 V AC (50-60 Hz) / DC Uc: 110-127 V 3-pole, auxiliary contacts 2 NO + 2 NC drive: conventional main circuit: busbar control and auxiliary circuit: screw terminal
Product family SIRIUS 3RT contactors, 3-pole, up to 250 kW
Product Lifecycle (PLM) PM300:Active Product
Additional Product Information
EAN 4011209507715
UPC 754554771090
Commodity Code 85364900
LKZ_FDB/ CatalogID CC-IC10
Product Group 3706
Group Code R711
Country of origin Germany
SCIP number Not available
Delivery information
Net Weight (lb) 14.286 lb
Package size unit of measure in
Packaging Quantity 1
Siemens New Stock Image
Siemens 3RT1064-6AP36 Siemens
Sale price $964.89
In stock, 19 units
Product
Article Number (Market Facing Number) 3RT10646AP36 | 3RT10646AP36
Product Description power contactor, AC-3e/AC-3 225 A, 110 kW / 400 V AC (50-60 Hz) / DC Uc: 220-240 V 3-pole, auxiliary contacts 2 NO + 2 NC drive: conventional main circuit: busbar control and auxiliary circuit: screw terminal
Product family SIRIUS 3RT contactors, 3-pole, up to 250 kW
Product Lifecycle (PLM) PM300:Active Product
Additional Product Information
EAN 4011209507739
UPC 754554772400
Commodity Code 85364900
LKZ_FDB/ CatalogID CC-IC10
Product Group 3706
Group Code R711
Country of origin Germany
SCIP number Not available
Delivery information
Net Weight (lb) 14.154 lb
Package size unit of measure in
Packaging Quantity 1
Siemens Stock Image
Siemens 3RT6016-1BB41 Siemens
Sale price $132.96
Only 6 units left

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

3RT2017-1AK61 Siemens
Siemens 3RT2017-1AK61 Siemens
Sale price $84.75
Only 6 units left
Product
Article Number (Market Facing Number) 3RT20171AK61 | 3RT20171AK61
Product Description power contactor, AC-3e/AC-3, 12 A, 5.5 kW / 400 V, 3-pole, 110 V AC, 50 Hz / 120 V, 60 Hz, auxiliary contacts: 1 NO, screw terminal, size: S00
Product family SIRIUS 3RT contactors, 3-pole, up to 250 kW
Product Lifecycle (PLM) PM300:Active Product
Additional Product Information
EAN 4011209828216
UPC 662643911022
Commodity Code 85364900
LKZ_FDB/ CatalogID CC-IC10
Product Group 5330
Group Code R711
Country of origin Germany
SCIP number Not available
Delivery information
Net Weight (lb) 0.514 lb
Package size unit of measure in
Packaging Quantity 1
3RT1036-1AL20 Siemens
Siemens 3RT1036-1AL20 Siemens
Sale price $167.72
Only 9 units left
Product
Article Number (Market Facing Number) 3RT10361AL20 | 3RT10361AL20
Product Description Power contactor, AC-3 50 A, 22 kW / 400 V 230 V AC, 50 / 60 Hz, 3-pole, Size S2, Screw terminal !!! Phased-out product !!! Successor is SIRIUS 3RT2 Preferred successor type is >>3RT2036-1AL20<<
Product family Not available
Product Lifecycle (PLM) PM500:Discontinued Product or end of PLM & Support
Additional Product Information
EAN 4011209336551
UPC 754554627038
Commodity Code 85364900
LKZ_FDB/ CatalogID CC-IC10
Product Group 3705
Group Code R711
Country of origin Germany
SCIP number Not available
Delivery information
Net Weight (lb) 1.852 lb
Package size unit of measure Inch
Packaging Quantity 1
LC1D80ABNE Schneider Electric
Schneider LC1D80ABNE Schneider Electric
Sale price$0.00
Sold Out

TeSys D contactor 3P 66A AC-3 up to 440V coil 24-60V AC/DC EverLink

LC1D18M7 Schneider Electric
Schneider LC1D18M7 Schneider Electric
Sale price $109.17
Only 5 units left

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 18 A - 220 V AC coil

Schneider New Stock Image
Schneider LC1G330EHEA Schneider
Sale price $3,057.26
Only 2 units left
PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.
LC1D12M7C Schneider
Schneider LC1D12M7C Schneider
Sale price $89.37
Only 9 units left

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A - 220 V AC coil

LC1DT60ABD Schneider Electric
Schneider LC1DT60ABD Schneider Electric
Sale price$0.00
Sold Out

TeSys D contactor - 4P(4 NO) - AC-1 - <= 440 V 60 A - 24 V DC standard coil

Recently viewed