LC1DT60AB7 Schneider Electric
Schneider LC1DT60AB7 Schneider Electric
Sale price$0.00
Sold Out

TeSys Deca contactor, 4 poles (4NO), for non-inductive load applications up to 60A/440V AC-1. They can be used to create motor starters for almost any type of application. It provides a 24V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror contact), power connection by EverLink BTR screw connectors and control by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (70mm width), DIN-rail mounting or screw fixing. Power contacts have a 60A resistive load rating. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.76 inches wide and 4.72 inches deep. It weighs 2.40 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.

Main

Characteristic Value(s)
Range TeSys
TeSys Deca
Range of Product TeSys Deca
Product or Component Type Contactor
Device short name LC1D
Contactor application Resistive load
Utilisation category AC-1
Poles description 4P
[Ue] rated operational voltage Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current 60 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage 24 V AC 50/60 Hz

Complementary

Characteristic Value(s)
Compatibility code LC1D
Pole contact composition 4 NO
Protective cover With
[Ith] conventional free air thermal current 10 A (at 140 °F (60 °C)) for signalling circuit
60 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 800 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 320 A 104 °F (40 °C) - 10 s for power circuit
720 A 104 °F (40 °C) - 1 s for power circuit
72 A 104 °F (40 °C) - 10 min for power circuit
165 A 104 °F (40 °C) - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
80 A gG at <= 690 V coordination type 1 for power circuit
80 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 1.6 mOhm - Ith 60 A 50 Hz for power circuit
Power dissipation per pole 5.8 W AC-1
[Ui] rated insulation voltage Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Power circuit 690 V IEC 60947-4-1
Overvoltage category III
pollution degree 3
[Uimp] rated impulse withstand voltage 6 kV IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 6 Mcycles
Electrical durability 1.4 Mcycles 60 A AC-1 <= 440 V
Control circuit type AC 50/60 Hz
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3...0.6 Uc (-40…158 °F (-40…70 °C)):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC 50 Hz
0.85...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC 60 Hz
1...1.1 Uc (140…158 °F (60…70 °C)):operational AC 50/60 Hz
Inrush power in VA 140 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))
160 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA 13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
15 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation 4…5 W at 50/60 Hz
Operating time 4...19 ms opening
12...26 ms closing
Maximum operating rate 3600 cyc/h at 60 °C
Connections - terminals Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Power circuit: EverLink BTR screw connectors 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: flexible without cable end
Power circuit: EverLink BTR screw connectors 2 0.002…0.04 in² (1…25 mm²) - cable stiffness: flexible without cable end
Power circuit: EverLink BTR screw connectors 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: flexible with cable end
Power circuit: EverLink BTR screw connectors 2 0.002…0.04 in² (1…25 mm²) - cable stiffness: flexible with cable end
Power circuit: EverLink BTR screw connectors 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: solid without cable end
Power circuit: EverLink BTR screw connectors 2 0.002…0.04 in² (1…25 mm²) - cable stiffness: solid without cable end
Tightening torque Control circuit 15.05 lbf.in (1.7 N.m) EverLink BTR screw connectors flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) EverLink BTR screw connectors Philips No 2
Power circuit 70.8 lbf.in (8 N.m) EverLink BTR screw connectors 0.04…0.05 in² (25…35 mm²) hexagonal 0.2 in (4 mm)
Power circuit 44.3 lbf.in (5 N.m) EverLink BTR screw connectors 0.002…0.04 in² (1…25 mm²) hexagonal 0.2 in (4 mm)
Control circuit 15.05 lbf.in (1.7 N.m) EverLink BTR screw connectors pozidriv No 2
Power circuit 22.1 lbf.in (2.5 N.m) EverLink BTR screw connectors pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support Rail
Plate
LC1DT80AE7 Schneider Electric
Schneider LC1DT80AE7 Schneider Electric
Sale price$0.00
Sold Out

TeSys Deca contactor, 4 poles (4NO), for non-inductive load applications up to 80A/440V AC-1. They can be used to create motor starters for almost any type of application. It provides a 48V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), power connection by EverLink BTR screw connectors, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (70mm width), DIN-rail mounting or screw fixing. Power contacts have a 80A resistive load rating. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.76 inches wide and 4.72 inches deep. It weighs 2.54 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.

Main

Characteristic Value(s)
Range TeSys
TeSys Deca
Range of Product TeSys Deca
Product or Component Type Contactor
Device short name LC1D
Contactor application Resistive load
Utilisation category AC-1
Poles description 4P
[Ue] rated operational voltage Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current 80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage 48 V AC 50/60 Hz

Complementary

Characteristic Value(s)
Compatibility code LC1D
Pole contact composition 4 NO
Protective cover With
[Ith] conventional free air thermal current 10 A (at 140 °F (60 °C)) for signalling circuit
80 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1000 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 640 A 104 °F (40 °C) - 10 s for power circuit
900 A 104 °F (40 °C) - 1 s for power circuit
110 A 104 °F (40 °C) - 10 min for power circuit
260 A 104 °F (40 °C) - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
125 A gG at <= 690 V coordination type 1 for power circuit
125 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 1.6 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole 10.2 W AC-1
[Ui] rated insulation voltage Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Power circuit 690 V IEC 60947-4-1
Overvoltage category III
pollution degree 3
[Uimp] rated impulse withstand voltage 6 kV IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 6 Mcycles
Electrical durability 1.4 Mcycles 80 A AC-1 <= 440 V
Control circuit type AC 50/60 Hz
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3...0.6 Uc (-40…158 °F (-40…70 °C)):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC 50 Hz
0.85...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC 60 Hz
1...1.1 Uc (140…158 °F (60…70 °C)):operational AC 50/60 Hz
Inrush power in VA 140 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))
160 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA 13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
15 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation 4…5 W at 50/60 Hz
Operating time 4...19 ms opening
12...26 ms closing
Maximum operating rate 3600 cyc/h at 60 °C
Connections - terminals Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Power circuit: EverLink BTR screw connectors 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: flexible without cable end
Power circuit: EverLink BTR screw connectors 2 0.002…0.04 in² (1…25 mm²) - cable stiffness: flexible without cable end
Power circuit: EverLink BTR screw connectors 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: flexible with cable end
Power circuit: EverLink BTR screw connectors 2 0.002…0.04 in² (1…25 mm²) - cable stiffness: flexible with cable end
Power circuit: EverLink BTR screw connectors 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: solid without cable end
Power circuit: EverLink BTR screw connectors 2 0.002…0.04 in² (1…25 mm²) - cable stiffness: solid without cable end
Tightening torque Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Power circuit 70.8 lbf.in (8 N.m) screw clamp terminals 0.04…0.05 in² (25…35 mm²) hexagonal 0.2 in (4 mm)
Power circuit 44.3 lbf.in (5 N.m) screw clamp terminals 0.002…0.04 in² (1…25 mm²) hexagonal 0.2 in (4 mm)
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Power circuit 22.1 lbf.in (2.5 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support Plate
Rail
LC1DT32F7 Schneider Electric
Schneider LC1DT32F7 Schneider Electric
Sale price$0.00
Sold Out

TeSys D contactor - 4P(4 NO) - AC-1 - <= 440 V 32 A - 110 V AC 50/60 Hz coil

LC1D183Q7 Schneider Electric
Schneider LC1D183Q7 Schneider Electric
Sale price$0.00
Sold Out

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 18 A - 380 V AC coil

Schneider Stock Image
Schneider LC2D150 Schneider
Sale price $1,184.11
Only 3 units left
Buy the Schneider Electric LC2D150 Contactor/Motor Starter - an industrial motor switching device for reliable AC motor start/stop control. Features high mechanical and electrical endurance, auxiliary contacts, and standard mounting. The Schneider Electric LC2D150 is a direct replacement for existing motor control installations.
LC1DWK12P7 Schneider Electric
Schneider LC1DWK12P7 Schneider Electric
Sale price $548.97
Only 1 unit left

Capacitor contactor, TeSys D, 63 kVAR at 400 V/50 Hz, coil 230 V AC 50/60 Hz

LC1F115M5 Schneider Electric
Schneider LC1F115M5 Schneider Electric
Sale price $971.63
Only 1 unit left

Main

Characteristic Value(s)
Range TeSys
Range of Product TeSys F
Product or Component Type Contactor
Device short name LC1F
Contactor application Resistive load
Motor control
Utilisation category AC-4
AC-3
AC-1
Poles description 3P
[Ue] rated operational voltage <= 690 V AC 50/60 Hz
<= 460 V DC
[Uc] control circuit voltage 220 V AC 50 Hz
[Ie] rated operational current 200 A (at <104 °F (40 °C)) at <= 440 V AC-1
115 A (at <131 °F (55 °C)) at <= 440 V AC-3

Complementary

Characteristic Value(s)
[Uimp] rated impulse withstand voltage 8 kV
[Ith] conventional free air thermal current 200 A (at 104 °F (40 °C))
Rated breaking capacity 920 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current 1100 A 104 °F (40 °C) - 10 s
640 A 104 °F (40 °C) - 30 s
520 A 104 °F (40 °C) - 1 min
400 A 104 °F (40 °C) - 3 min
320 A 104 °F (40 °C) - 10 min
Associated fuse rating 125 A aM at <= 440 V
200 A gG at <= 440 V
Average impedance 0.37 mOhm - Ith 200 A 50 Hz
[Ui] rated insulation voltage 1000 V IEC 60947-4-1
1500 V VDE 0110 group C
Power dissipation per pole 15 W AC-1
5 W AC-3
Overvoltage category III
power pole contact composition 3 NO
Motor power kW 55 kW at 380...400 V AC 50/60 Hz (AC-3)
59 kW at 415 V AC 50/60 Hz (AC-3)
59 kW at 440 V AC 50/60 Hz (AC-3)
75 kW at 500 V AC 50/60 Hz (AC-3)
80 kW at 660...690 V AC 50/60 Hz (AC-3)
30 kW at 220...230 V AC 50/60 Hz (AC-3)
18.5 kW at 400 V AC 50/60 Hz (AC-4)
Control circuit voltage limits Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))
Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))
Mechanical durability 10 Mcycles
Inrush power in VA 550 VA, 50 Hz 0.3 68 °F (20 °C))
Hold-in power consumption in VA 45 VA, 50 Hz 0.3 68 °F (20 °C))
Maximum operating rate 2400 cyc/h 131 °F (55 °C)
Operating time 23...35 ms closing
5...15 ms opening
Connections - terminals Power circuit bar 2 20 x 3 mm
Power circuit lugs-ring terminals 1 0.1 in² (95 mm²)
Power circuit connector 1 0.1 in² (95 mm²)
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end
Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end
Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end
Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end
Power circuit bolted connection
Tightening torque Power circuit 88.5 lbf.in (10 N.m)
Control circuit 10.6 lbf.in (1.2 N.m)
Mounting Support Plate
Heat dissipation 12…16 W
Standards EN 60947-4-1
IEC 60947-1
JIS C8201-4-1
EN 60947-1
IEC 60947-4-1
Product Certifications RINA
BV
RMRoS
ABS
CB
CCC
UL
DNV
LROS (Lloyds register of shipping)
Compatibility code LC1F
Control circuit type AC 50 Hz
Schneider New Stock Image
Schneider LC1D09E7C Schneider
Sale price $87.29
In stock, 11 units
PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.
LC1K06016FLS207 Schneider Electric

TeSys K contactor - 3P - AC-3 <= 440 V 6 A - 1 NC aux. - 110 V DC low

Schneider Stock Image
Schneider LC2DT25G7 Schneider
Sale price $471.45
Only 5 units left

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

Schneider New Stock Image
Schneider LC1D258M7C Schneider
Sale price $98.75
Only 1 unit left
PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.
LC1K0910R7 Schneider Electric
Schneider LC1K0910R7 Schneider Electric
Sale price$0.00
Sold Out

TeSys K contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3 (4kW@400V), and for non-inductive load control applications up to 20A/690V AC-1. It provides a 440V 50/60Hz AC coil, 1NO built-in auxiliary contact, connection by screw clamp terminals. For operating rates until 600 cycles/hour and environments until 50°C, it procures reliability and durability to standard applications. Very compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).

Main

Characteristic Value(s)
Range TeSys
Product or Component Type Contactor
Device Application Control
Contactor application Motor control
Resistive load

Complementary

Characteristic Value(s)
Utilisation category AC-3
AC-3e
AC-1
AC-4
Poles description 3P
power pole contact composition 3 NO
[Ue] rated operational voltage Power circuit <= 690 V AC <= 400 Hz
Signalling circuit <= 690 V AC <= 400 Hz
[Ie] rated operational current 9 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
9 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
20 A (at <140 °F (60 °C)) at <= 690 V AC AC-1 for power circuit
Control circuit type AC 50/60 Hz
[Uc] control circuit voltage 440 V AC 50/60 Hz
Motor power kW 2.2 kW 220...230 V AC 50/60 Hz AC-3
4 kW 380...415 V AC 50/60 Hz AC-3
4 kW 440/690 V AC 50/60 Hz AC-3
2.2 kW 220...230 V AC 50/60 Hz AC-3e
4 kW 380...415 V AC 50/60 Hz AC-3e
4 kW 440/690 V AC 50/60 Hz AC-3e
2.2 kW 220...230 V AC 50/60 Hz AC-4
4 kW 380...415 V AC 50/60 Hz AC-4
4 kW 440/690 V AC 50/60 Hz AC-4
Auxiliary contact composition 1 NO
[Uimp] rated impulse withstand voltage 8 kV
Overvoltage category III
[Ith] conventional free air thermal current 20 A (at 140 °F (60 °C)) for power circuit
10 A (at 122 °F (50 °C)) for signalling circuit
Irms rated making capacity 110 A AC for power circuit conforming to IEC 60947
110 A AC for signalling circuit conforming to IEC 60947
Rated breaking capacity 110 A at 220...230 V conforming to IEC 60947
110 A at 380...400 V conforming to IEC 60947
110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand current 90 A 122 °F (50 °C) - 1 s for power circuit
85 A 122 °F (50 °C) - 5 s for power circuit
80 A 122 °F (50 °C) - 10 s for power circuit
60 A 122 °F (50 °C) - 30 s for power circuit
45 A 122 °F (50 °C) - 1 min for power circuit
40 A 122 °F (50 °C) - 3 min for power circuit
20 A 122 °F (50 °C) - >= 15 min for power circuit
80 A - 1 s for signalling circuit
90 A - 500 ms for signalling circuit
110 A - 100 ms for signalling circuit
Associated fuse rating 25 A gG at <= 440 V for power circuit
25 A aM for power circuit
10 A gG for signalling circuit conforming to IEC 60947
10 A gG for signalling circuit conforming to VDE 0660
Average impedance 3 mOhm - Ith 20 A 50 Hz for power circuit
Insulation resistance > 10 MOhm for signalling circuit
Inrush power in VA 30 VA (at 68 °F (20 °C))
Hold-in power consumption in VA 4.5 VA (at 68 °F (20 °C))
Heat dissipation 1.3 W
Control circuit voltage limits Operational: 0.8...1.15 Uc (at <122 °F (50 °C))
Drop-out: >= 0.20 Uc (at <122 °F (50 °C))
Connections - terminals screw clamp terminals 1 0.002…0.006 in² (1.5…4 mm²)solid
screw clamp terminals 1 0.001…0.006 in² (0.75…4 mm²)flexible without cable end
screw clamp terminals 1 0.0005…0.004 in² (0.34…2.5 mm²)flexible with cable end
screw clamp terminals 2 0.002…0.006 in² (1.5…4 mm²)solid
screw clamp terminals 2 0.001…0.006 in² (0.75…4 mm²)flexible without cable end
screw clamp terminals 2 0.0005…0.002 in² (0.34…1.5 mm²)flexible with cable end
Maximum operating rate 3600 cyc/h
Auxiliary contacts type Instantaneous 1 NO
Signalling circuit frequency <= 400 Hz
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Operating time 10...20 ms coil de-energisation and NO opening
10...20 ms coil energisation and NO closing
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Non overlap distance 0.02 in (0.5 mm)
Mechanical durability 10 Mcycles
Electrical durability 1.3 Mcycles 9 A AC-3 <= 440 V
1.3 Mcycles 9 A AC-3e <= 440 V
0.16 Mcycles 20 A AC-1 <= 690 V
0.02 Mcycles 54 A AC-4 <= 440 V
Mechanical robustness Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27
Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6
Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6
Height 2.3 in (58 mm)
Width 1.8 in (45 mm)
Depth 2.2 in (57 mm)
LC1K06106BLS207 Schneider Electric

TeSys K contactor - 3P - AC-3 <= 440 V 6 A - 1 NO aux. - 24 V DC low

LC1DTKP7 Schneider Electric
Schneider LC1DTKP7 Schneider Electric
Sale price $1,468.13
Only 2 units left

Capacitor contactor, TeSys D, 40 kVAR at 400 V/50 Hz, coil 230 V AC 50/60 Hz

LC1D80AR7 Schneider Electric
Schneider LC1D80AR7 Schneider Electric
Sale price$0.00
Sold Out

TeSys D contactor 3P 66A AC-3 up to 440V coil 440V AC 50/60Hz

LC2D32ED Schneider Electric
Schneider LC2D32ED Schneider Electric
Sale price$0.00
Sold Out

TeSys Deca reversing contactor, 3 poles (3NO), for motor control applications up to 32A/690V AC-3 (15kW@400V). It provides 48V DC coils with transient suppressor module, 2NO+2NC built-in auxiliary contacts (NC mirror contacts), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Main

Characteristic Value(s)
Range TeSys
product name TeSys Deca
Product or Component Type Reversing contactor
Device short name LC2D
Contactor application Resistive load
Motor control
Utilisation category AC-3
AC-1
Device presentation Preassembled with reversing power busbar
Poles description 3P
power pole contact composition 3 NO
[Ue] rated operational voltage Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current 32 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
50 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
Motor power kW 7.5 kW at 220...230 V AC 50 Hz
15 kW at 380...400 V AC 50 Hz
15 kW at 415...440 V AC 50 Hz
18.5 kW at 500 V AC 50 Hz
18.5 kW at 660...690 V AC 50 Hz
motor power HP (UL / CSA) 2 hp at 115 V AC 60 Hz for 1 phase motors
5 hp at 230/240 V AC 60 Hz for 1 phase motors
7.5 hp at 200/208 V AC 60 Hz for 3 phase motors
10 hp at 230/240 V AC 60 Hz for 3 phase motors
20 hp at 460/480 V AC 60 Hz for 3 phase motors
30 hp at 575/600 V AC 60 Hz for 3 phase motors
Control circuit type DC standard
[Uc] control circuit voltage 48 V DC
Auxiliary contact composition 1 NO + 1 NC
[Uimp] rated impulse withstand voltage 6 kV IEC 60947
Overvoltage category III
[Ith] conventional free air thermal current 10 A (at 140 °F (60 °C)) for signalling circuit
50 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
550 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 550 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 60 A 104 °F (40 °C) - 10 min for power circuit
138 A 104 °F (40 °C) - 1 min for power circuit
260 A 104 °F (40 °C) - 10 s for power circuit
430 A 104 °F (40 °C) - 1 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
63 A gG at <= 690 V coordination type 1 for power circuit
63 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2 mOhm - Ith 50 A 50 Hz for power circuit
[Ui] rated insulation voltage Power circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Electrical durability 1.65 Mcycles 32 A AC-3 <= 440 V
1.4 Mcycles 50 A AC-1 <= 440 V
Power dissipation per pole 2 W AC-3
5 W AC-1
Front cover With
Interlocking type Mechanical
Mounting Support Plate
Rail
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
Product Certifications DNV
RINA
CCC
CSA
GL
BV
GOST
UL
LROS (Lloyds register of shipping)
Connections - terminals Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end
Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end
Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid
Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid
Power circuit screw clamp terminals 1 0.004…0.02 in² (2.5…10 mm²)flexible without cable end
Power circuit screw clamp terminals 2 0.004…0.02 in² (2.5…10 mm²)flexible without cable end
Power circuit screw clamp terminals 1 0.002…0.02 in² (1…10 mm²)flexible with cable end
Power circuit screw clamp terminals 2 0.002…0.009 in² (1.5…6 mm²)flexible with cable end
Power circuit screw clamp terminals 1 0.002…0.02 in² (1.5…10 mm²)solid
Power circuit screw clamp terminals 2 0.004…0.02 in² (2.5…10 mm²)solid
Tightening torque Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Power circuit 22.1 lbf.in (2.5 N.m) screw clamp terminals flat Ø 6 mm
Power circuit 22.1 lbf.in (2.5 N.m) screw clamp terminals Philips No 2
Operating time 53.55...72.45 ms closing
16...24 ms opening
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 30 Mcycles
Maximum operating rate 3600 cyc/h 140 °F (60 °C)

Complementary

Characteristic Value(s)
Coil technology Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits 0.1...0.25 Uc (-40…158 °F (-40…70 °C)):drop-out DC
0.7...1.25 Uc (-40…140 °F (-40…60 °C)):operational DC
1...1.25 Uc (140…158 °F (60…70 °C)):operational DC
Time constant 28 ms
Inrush power in W 5.4 W 68 °F (20 °C))
Hold-in power consumption in W 5.4 W 68 °F (20 °C)
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Insulation resistance > 10 MOhm for signalling circuit
LC2D38E7 Schneider Electric
Schneider LC2D38E7 Schneider Electric
Sale price$0.00
Sold Out

TeSys D reversing contactor, 3 poles (3NO), for motor control applications up to 38A/690V AC-3 (18.5kW@400V). It provides 48V 50/60Hz AC coils, 2NO+2NC built-in auxiliary contacts (NC mirror contacts), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Main

Characteristic Value(s)
Range TeSys
TeSys Deca
product name TeSys D
TeSys Deca
Product or component type Reversing contactor
Device short name LC2D
Contactor application Resistive load
Motor control
Utilisation category AC-3
AC-1
AC-3e
Device presentation Preassembled with reversing power busbar
Poles description 3P
power pole contact composition 3 NO
[Ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz
Power circuit: <= 300 V DC
[Ie] rated operational current 50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
38 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
38 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
Motor power kW 9 kW at 220...230 V AC 50...60 Hz
18.5 kW at 380...400 V AC 50...60 Hz
18.5 kW at 415 V AC 50...60 Hz
18.5 kW at 440 V AC 50...60 Hz
18.5 kW at 500 V AC 50...60 Hz
18.5 kW at 660...690 V AC 50...60 Hz
motor power HP (UL / CSA) 5 hp at 240 V AC 60 Hz for 1 phase motors
Control circuit type AC at 50/60 Hz
[Uc] control circuit voltage 48 V AC 50/60 Hz
Auxiliary contact composition 1 NO + 1 NC
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Overvoltage category III
[Ith] conventional free air thermal current 10 A (at 60 °C) for signalling circuit
50 A (at 60 °C) for power circuit
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
550 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 550 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 60 A 40 °C - 10 min for power circuit
430 A 40 °C - 1 s for power circuit
150 A 40 °C - 1 min for power circuit
310 A 40 °C - 10 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
63 A gG at <= 690 V coordination type 1 for power circuit
63 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2 mOhm - Ith 50 A 50 Hz for power circuit
[Ui] rated insulation voltage Power circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Electrical durability 1.4 Mcycles 50 A AC-1 at Ue <= 440 V
1.4 Mcycles 38 A AC-3 at Ue <= 440 V
1.4 Mcycles 38 A AC-3e at Ue <= 440 V
Power dissipation per pole 5 W AC-1
3 W AC-3
3 W AC-3e
Front cover With
Interlocking type Mechanical
Mounting support Rail
Plate
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
IEC 60335-1
Product certifications UL
CSA
RINA
GOST
CCC
DNV
LROS (Lloyds register of shipping)
GL
BV
UKCA
CB
Connections - terminals Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid
Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm²flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…10 mm²flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm²flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm²solid
Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²solid
Tightening torque Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Operating time 12...22 ms closing
4...19 ms opening
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability 15 Mcycles
Maximum operating rate 3600 cyc/h 60 °C

Complementary

Characteristic Value(s)
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Inrush power in VA 70 VA 60 Hz cos phi 0.75 (at 20 °C)
70 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA 7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
7 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation 2…3 W at 50/60 Hz
Auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Insulation resistance > 10 MOhm for signalling circuit
Schneider New Stock Image
Schneider LCID12BL Schneider
Sale price $102.92
Only 10 units left
PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.
LC1K0601Q7 Schneider Electric
Schneider LC1K0601Q7 Schneider Electric
Sale price$0.00
Sold Out

TeSys K contactor - 3P - AC-3 <= 440 V 6 A - 1 NC aux. - 380...400 V AC coil

Schneider New Stock Image
Schneider LC1F225BD Schneider
Sale price$0.00
Sold Out
PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.
Schneider Stock Image
Schneider LC2D18G7V Schneider
Sale price $525.00
Only 5 units left

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

LC1D126BL Schneider Electric
Schneider LC1D126BL Schneider Electric
Sale price$0.00
Sold Out

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A - 24 V DC coil

Schneider New Stock Image
Schneider LC1D12BD20 Schneider
Sale price $119.58
In stock, 11 units
PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.
LC1DT20U7 Schneider Electric
Schneider LC1DT20U7 Schneider Electric
Sale price$0.00
Sold Out

TeSys Deca contactor, 4 poles (4NO), for non-inductive load applications up to 20A/440V AC-1. They can be used to create motor starters for almost any type of application. It provides a 240V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Power contacts have a 20A resistive load rating. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.

Main

Characteristic Value(s)
Range TeSys
TeSys Deca
Range of Product TeSys Deca
Product or Component Type Contactor
Device short name LC1D
Contactor application Resistive load
Utilisation category AC-1
Poles description 4P
[Ue] rated operational voltage Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current 20 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage 240 V AC 50/60 Hz

Complementary

Characteristic Value(s)
Compatibility code LC1D
Pole contact composition 4 NO
Protective cover With
[Ith] conventional free air thermal current 10 A (at 140 °F (60 °C)) for signalling circuit
20 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
250 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 250 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 30 A 104 °F (40 °C) - 10 min for power circuit
61 A 104 °F (40 °C) - 1 min for power circuit
105 A 104 °F (40 °C) - 10 s for power circuit
210 A 104 °F (40 °C) - 1 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
25 A gG at <= 690 V coordination type 1 for power circuit
20 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2.5 mOhm - Ith 20 A 50 Hz for power circuit
Power dissipation per pole 1.56 W AC-1
[Ui] rated insulation voltage Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Power circuit 690 V IEC 60947-4-1
Overvoltage category III
pollution degree 3
[Uimp] rated impulse withstand voltage 6 kV IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 15 Mcycles
Control circuit type AC 50/60 Hz
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3...0.6 Uc (-40…158 °F (-40…70 °C)):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC 50 Hz
0.85...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC 60 Hz
1...1.1 Uc (140…158 °F (60…70 °C)):operational AC 50/60 Hz
Inrush power in VA 70 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))
70 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA 7.5 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
7 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation 2…3 W at 50/60 Hz
Operating time 4...19 ms opening
12...22 ms closing
Maximum operating rate 3600 cyc/h at 60 °C
Connections - terminals Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Tightening torque Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support Plate
Rail

Recently viewed