Altivar Soft Starter ATS480 is intended to start and stop asynchronous motors supplied from 208V to 690V. It meets the requirements of the most demanding applications in normal and heavy duty. With an operational rated current of 170A in normal duty, it supplies motor from 45kW to 160kW according to mains voltage. Designed for digitization, connected, optimized to meet cybersecurity standard, it simplifies project execution and maximizes the availability of applications. Its torque control (TCS) masters acceleration and deceleration. It efficiently stops high inertia application thanks to the dynamic braking and DC injection. It could be connected in-line or inside the delta to reduce its operational current. The embedded test routine simplifies the commissioning inside the delta. Its dimensions are 200mm (width) x 272mm (depth) x 340mm (height) and it weighs 12,4kg. Altivar Soft Starter ATS480 is designed to address process, infrastructures and industrial machines. It conforms to IEC/EN60947-4-1. It is certified CE, cULus, UKCA, CCC, RCM, EAC, and Marine certified DNV, ABS, BV and CCS. Display terminals, remote mounting kit, communication modules are common with Altivar Drives. Line chokes, DNV kits are common with ATS48. ATS480 is compatible with ATS48, it has same footprint, fixing, torque control algorithm, I/O, menus… The integration of Altivar Soft Starter ATS480 in EcoStruxure drastically simplifies architecture selection, detailed design and execution in automation and electrical systems.

Main

Characteristic Value(s)
Range of Product Altivar Soft Starter ATS480
Product or Component Type Soft starter
Product destination Asynchronous motors
Product Specific Application Process and infrastructures
Device short name ATS480
Phase 3 phase
Utilisation category AC-3A
AC-53A
Ue power supply voltage 208...690 V - 15...10 %
power supply frequency 50...60 Hz - 20...20 %
[Ie] rated operational current Normal duty 170.0 A 104 °F (40 °C))
rated current in heavy duty 140.0 A at 104 °F (40 °C) heavy duty
Torque control True
IP Degree of Protection IP00
Motor power kW 45.0 kW 230 V in the motor supply line normal duty
37.0 kW 230 V in the motor supply line heavy duty
90.0 kW 400 V in the motor supply line normal duty
75.0 kW 400 V in the motor supply line heavy duty
90.0 kW 440 V in the motor supply line normal duty
75.0 kW 440 V in the motor supply line heavy duty
110.0 kW 500 V in the motor supply line normal duty
90.0 kW 500 V in the motor supply line heavy duty
110.0 kW 525 V in the motor supply line normal duty
90.0 kW 525 V in the motor supply line heavy duty
132.0 kW 660 V in the motor supply line normal duty
110.0 kW 660 V in the motor supply line heavy duty
160.0 kW 690 V in the motor supply line normal duty
110.0 kW 690 V in the motor supply line heavy duty
90.0 kW 230 V to the motor delta terminals normal duty
75.0 kW 230 V to the motor delta terminals heavy duty
132.0 kW 400 V to the motor delta terminals normal duty
110.0 kW 400 V to the motor delta terminals heavy duty
Maximum Horse Power Rating 50.0 hp 208 V normal duty
40.0 hp 208 V heavy duty
60.0 hp 230 V normal duty
50.0 hp 230 V heavy duty
125.0 hp 460 V normal duty
100.0 hp 460 V heavy duty
150.0 hp 575 V normal duty
125.0 hp 575 V heavy duty
Option card Communication module Profibus DP V1
Communication module Modbus TCP/EtherNet/IP
Communication module CANopen daisy chain
Communication module CANopen Sub-D
Communication module CANopen open style
Communication module PROFINET

Complementary

Characteristic Value(s)
Device connection In the motor supply line
To the motor delta terminals
[Us] control circuit voltage 110...230 V AC 50/60 Hz - 15...10 %
Apparent power 0.09 kVA
Integrated motor overload protection True
motor thermal protection class Class 10E
Protection type Phase failure line
Integrated thermal protection motor
Thermal protection starter
Current overload motor
Underload motor
Excessive starting time, locked rotor motor
Motor phase loss motor
Line supply phase loss line
Line supply phase loss motor
Thermal protection motor
current limiting %In (5 x Ie maximum) 150…700 %
[In] Rated current pwr loss specifctn 170.0 A
Power loss static current independent 25.0 W
Power loss per device current dependent 459.0 W
Standards IEC 60947-4-2
UL 60947-4-2
IEC 60664-1
Product Certifications CE
cULus
CCC
UKCA
RCM
EAC
DNV
ABS
BV
CCS
Marking CE
CCC
UKCA
EAC
RCM
CULus
[Uc] control circuit voltage 24 V DC
Discrete input number 4
Discrete input type STOP) logic inputs, 3500 Ohm
RUN) logic inputs, 3500 Ohm
DI3) programmable as logic input, 3500 Ohm
DI4) programmable as logic input, 3500 Ohm
Input compatibility STOP discrete input level 1 PLC IEC 61131-2
RUN discrete input level 1 PLC IEC 61131-2
DI3 discrete input level 1 PLC IEC 61131-2
DI4 discrete input level 1 PLC IEC 61131-2
Discrete input logic Programmable digital input < 5 V
Relay output number 3
Relay output type Relay outputs R1A 1 NO
Relay outputs R1B 1 NO
Relay outputs RIC NO/NC programmable
Minimum switching current 100 mA 12 V DC relay outputs
Maximum switching current Relay outputs 2 A 250 V AC
Relay outputs 2 A 30 V DC
Relay outputs
Discrete output number 2
Discrete output type DQ1) programmable digital output <= 30 V
DQ2) programmable digital output <= 30 V
Output compatibility Open collector level 1 PLC IEC 65A-68
Analogue input number 1
Analogue input type AI1/PTC PTC/Pt 100 temperature probe
PTC2 PTC/Pt 100 temperature probe
PTC3 PTC/Pt 100 temperature probe
Analogue output number 1
Analogue output type Current output AQ1 0...20 mA or 0...10 V 500 Ohm
Communication Port Protocol Modbus serial
Connector Type 1 RJ45
Communication data link Serial
Physical interface 2-wire RS 485
Transmission Rate 1200...256000 bit/s
Transmission frame RTU
Data format 8 bits, configurable odd, even or no parity
Type of polarization No impedance Modbus serial
Number of addresses 0…227 Modbus serial
Method of access Slave Modbus serial
Function Available External bypass control
Pre-heating
Smoke extraction
Multi-motor cascade
Second motor set
User management
Ports and services hardening
Security event logging
Cybersecure firmware update
Single direction
Display screen available True
Operating position Vertical +/- 10 degree
Height 13.4 in (340.0 mm)
Width 7.9 in (200.0 mm)
Depth 10.7 in (272.0 mm)
Product Weight 27.3 lb(US) (12.4 kg)

Sale price$1,777.17
1-year warranty
FREE WORDWIDE SHIPPING
Est. delivery between and  
Estimated delivery dates are estimates only. Int'l customers allow a few more days. For more precise delivery estimates, please contact us at support@plc-direct.com. Contact us in advance for expedited shipping options.
Condition:
$1,777.17
$0.00
$0.00

Ach Direct Debit American Express Apple Pay Diners Club Discover Google Pay Mastercard PayPal Shop Pay Visa
Description
Warranty
Shipping and Return

Altivar Soft Starter ATS480 is intended to start and stop asynchronous motors supplied from 208V to 690V. It meets the requirements of the most demanding applications in normal and heavy duty. With an operational rated current of 170A in normal duty, it supplies motor from 45kW to 160kW according to mains voltage. Designed for digitization, connected, optimized to meet cybersecurity standard, it simplifies project execution and maximizes the availability of applications. Its torque control (TCS) masters acceleration and deceleration. It efficiently stops high inertia application thanks to the dynamic braking and DC injection. It could be connected in-line or inside the delta to reduce its operational current. The embedded test routine simplifies the commissioning inside the delta. Its dimensions are 200mm (width) x 272mm (depth) x 340mm (height) and it weighs 12,4kg. Altivar Soft Starter ATS480 is designed to address process, infrastructures and industrial machines. It conforms to IEC/EN60947-4-1. It is certified CE, cULus, UKCA, CCC, RCM, EAC, and Marine certified DNV, ABS, BV and CCS. Display terminals, remote mounting kit, communication modules are common with Altivar Drives. Line chokes, DNV kits are common with ATS48. ATS480 is compatible with ATS48, it has same footprint, fixing, torque control algorithm, I/O, menus… The integration of Altivar Soft Starter ATS480 in EcoStruxure drastically simplifies architecture selection, detailed design and execution in automation and electrical systems.

Main

Characteristic Value(s)
Range of Product Altivar Soft Starter ATS480
Product or Component Type Soft starter
Product destination Asynchronous motors
Product Specific Application Process and infrastructures
Device short name ATS480
Phase 3 phase
Utilisation category AC-3A
AC-53A
Ue power supply voltage 208...690 V - 15...10 %
power supply frequency 50...60 Hz - 20...20 %
[Ie] rated operational current Normal duty 170.0 A 104 °F (40 °C))
rated current in heavy duty 140.0 A at 104 °F (40 °C) heavy duty
Torque control True
IP Degree of Protection IP00
Motor power kW 45.0 kW 230 V in the motor supply line normal duty
37.0 kW 230 V in the motor supply line heavy duty
90.0 kW 400 V in the motor supply line normal duty
75.0 kW 400 V in the motor supply line heavy duty
90.0 kW 440 V in the motor supply line normal duty
75.0 kW 440 V in the motor supply line heavy duty
110.0 kW 500 V in the motor supply line normal duty
90.0 kW 500 V in the motor supply line heavy duty
110.0 kW 525 V in the motor supply line normal duty
90.0 kW 525 V in the motor supply line heavy duty
132.0 kW 660 V in the motor supply line normal duty
110.0 kW 660 V in the motor supply line heavy duty
160.0 kW 690 V in the motor supply line normal duty
110.0 kW 690 V in the motor supply line heavy duty
90.0 kW 230 V to the motor delta terminals normal duty
75.0 kW 230 V to the motor delta terminals heavy duty
132.0 kW 400 V to the motor delta terminals normal duty
110.0 kW 400 V to the motor delta terminals heavy duty
Maximum Horse Power Rating 50.0 hp 208 V normal duty
40.0 hp 208 V heavy duty
60.0 hp 230 V normal duty
50.0 hp 230 V heavy duty
125.0 hp 460 V normal duty
100.0 hp 460 V heavy duty
150.0 hp 575 V normal duty
125.0 hp 575 V heavy duty
Option card Communication module Profibus DP V1
Communication module Modbus TCP/EtherNet/IP
Communication module CANopen daisy chain
Communication module CANopen Sub-D
Communication module CANopen open style
Communication module PROFINET

Complementary

Characteristic Value(s)
Device connection In the motor supply line
To the motor delta terminals
[Us] control circuit voltage 110...230 V AC 50/60 Hz - 15...10 %
Apparent power 0.09 kVA
Integrated motor overload protection True
motor thermal protection class Class 10E
Protection type Phase failure line
Integrated thermal protection motor
Thermal protection starter
Current overload motor
Underload motor
Excessive starting time, locked rotor motor
Motor phase loss motor
Line supply phase loss line
Line supply phase loss motor
Thermal protection motor
current limiting %In (5 x Ie maximum) 150…700 %
[In] Rated current pwr loss specifctn 170.0 A
Power loss static current independent 25.0 W
Power loss per device current dependent 459.0 W
Standards IEC 60947-4-2
UL 60947-4-2
IEC 60664-1
Product Certifications CE
cULus
CCC
UKCA
RCM
EAC
DNV
ABS
BV
CCS
Marking CE
CCC
UKCA
EAC
RCM
CULus
[Uc] control circuit voltage 24 V DC
Discrete input number 4
Discrete input type STOP) logic inputs, 3500 Ohm
RUN) logic inputs, 3500 Ohm
DI3) programmable as logic input, 3500 Ohm
DI4) programmable as logic input, 3500 Ohm
Input compatibility STOP discrete input level 1 PLC IEC 61131-2
RUN discrete input level 1 PLC IEC 61131-2
DI3 discrete input level 1 PLC IEC 61131-2
DI4 discrete input level 1 PLC IEC 61131-2
Discrete input logic Programmable digital input < 5 V
Relay output number 3
Relay output type Relay outputs R1A 1 NO
Relay outputs R1B 1 NO
Relay outputs RIC NO/NC programmable
Minimum switching current 100 mA 12 V DC relay outputs
Maximum switching current Relay outputs 2 A 250 V AC
Relay outputs 2 A 30 V DC
Relay outputs
Discrete output number 2
Discrete output type DQ1) programmable digital output <= 30 V
DQ2) programmable digital output <= 30 V
Output compatibility Open collector level 1 PLC IEC 65A-68
Analogue input number 1
Analogue input type AI1/PTC PTC/Pt 100 temperature probe
PTC2 PTC/Pt 100 temperature probe
PTC3 PTC/Pt 100 temperature probe
Analogue output number 1
Analogue output type Current output AQ1 0...20 mA or 0...10 V 500 Ohm
Communication Port Protocol Modbus serial
Connector Type 1 RJ45
Communication data link Serial
Physical interface 2-wire RS 485
Transmission Rate 1200...256000 bit/s
Transmission frame RTU
Data format 8 bits, configurable odd, even or no parity
Type of polarization No impedance Modbus serial
Number of addresses 0…227 Modbus serial
Method of access Slave Modbus serial
Function Available External bypass control
Pre-heating
Smoke extraction
Multi-motor cascade
Second motor set
User management
Ports and services hardening
Security event logging
Cybersecure firmware update
Single direction
Display screen available True
Operating position Vertical +/- 10 degree
Height 13.4 in (340.0 mm)
Width 7.9 in (200.0 mm)
Depth 10.7 in (272.0 mm)
Product Weight 27.3 lb(US) (12.4 kg)

All PLC Direct products come with a 1-year warranty. The warranty is issued by PLC Direct. Warranty coverage commences at the date of purchase. The warranty is for mechanical defects or failures not caused by human factors including but not limited to (a) incorrect installation, (b) operating the unit in sub-optimal conditions or in scenarios not recommended by the manufacturer, (c) poor unit maintenance, etc. The warranty does not cover programming or software related issues.

If the product is eligible for PLC Direct’s warranty coverage and the customer encounters an issue with the product, we will request the item is shipped to us for diagnosis and examination. Regardless of the cause of product issues, the customer will bear responsibility for the cost of shipping the unit to PLC Direct for evaluation. Where the unit was damaged by human factors, we will offer a repair or replace quote; in cases where damage was caused by human factors, the customer is responsible for the cost of shipping the repaired/replaced unit from PLC Direct to the customer. Where the unit was not damaged by human factors but is covered by PLC Direct’s warranty, we will repair or replace the unit at our cost (or, in rare cases, refund you your purchase); in such cases, PLC Direct will bear the cost of shipping the repaired or replaced product back to the customer. It is up to PLC Direct’s discretion whether to repair, replace, or refund the customer in such cases. Diagnoses can take time to complete based on technician availability and the complexity of diagnosis.

In no event shall PLC Direct be liable for any damages except actual damages up to, but not exceeding, the amount paid to us for the product, including we shall not be liable for any consequential or indirect damages or lost profits whether or not advised of same.

PLC Direct offers free shipping worldwide. Product ship from a various warehouses worldwide based on the customer's and the product's location. The estimated delivery date on the product page is PLC Direct's best estimated assuming a US-based shipping destination.

Regardless of where the product is shipping from, PLC Direct covers all duties for US-based shipping destinations. For non-US-based shipping destinations, customers are responsible for duties as appropriate.

PLC Direct's focus is on balancing price with lead time. Some but not all products can be expedited. If you have questions about delivery ETAs, please contact our team.

Description
Warranty
Shipping and Return

Altivar Soft Starter ATS480 is intended to start and stop asynchronous motors supplied from 208V to 690V. It meets the requirements of the most demanding applications in normal and heavy duty. With an operational rated current of 170A in normal duty, it supplies motor from 45kW to 160kW according to mains voltage. Designed for digitization, connected, optimized to meet cybersecurity standard, it simplifies project execution and maximizes the availability of applications. Its torque control (TCS) masters acceleration and deceleration. It efficiently stops high inertia application thanks to the dynamic braking and DC injection. It could be connected in-line or inside the delta to reduce its operational current. The embedded test routine simplifies the commissioning inside the delta. Its dimensions are 200mm (width) x 272mm (depth) x 340mm (height) and it weighs 12,4kg. Altivar Soft Starter ATS480 is designed to address process, infrastructures and industrial machines. It conforms to IEC/EN60947-4-1. It is certified CE, cULus, UKCA, CCC, RCM, EAC, and Marine certified DNV, ABS, BV and CCS. Display terminals, remote mounting kit, communication modules are common with Altivar Drives. Line chokes, DNV kits are common with ATS48. ATS480 is compatible with ATS48, it has same footprint, fixing, torque control algorithm, I/O, menus… The integration of Altivar Soft Starter ATS480 in EcoStruxure drastically simplifies architecture selection, detailed design and execution in automation and electrical systems.

Main

Characteristic Value(s)
Range of Product Altivar Soft Starter ATS480
Product or Component Type Soft starter
Product destination Asynchronous motors
Product Specific Application Process and infrastructures
Device short name ATS480
Phase 3 phase
Utilisation category AC-3A
AC-53A
Ue power supply voltage 208...690 V - 15...10 %
power supply frequency 50...60 Hz - 20...20 %
[Ie] rated operational current Normal duty 170.0 A 104 °F (40 °C))
rated current in heavy duty 140.0 A at 104 °F (40 °C) heavy duty
Torque control True
IP Degree of Protection IP00
Motor power kW 45.0 kW 230 V in the motor supply line normal duty
37.0 kW 230 V in the motor supply line heavy duty
90.0 kW 400 V in the motor supply line normal duty
75.0 kW 400 V in the motor supply line heavy duty
90.0 kW 440 V in the motor supply line normal duty
75.0 kW 440 V in the motor supply line heavy duty
110.0 kW 500 V in the motor supply line normal duty
90.0 kW 500 V in the motor supply line heavy duty
110.0 kW 525 V in the motor supply line normal duty
90.0 kW 525 V in the motor supply line heavy duty
132.0 kW 660 V in the motor supply line normal duty
110.0 kW 660 V in the motor supply line heavy duty
160.0 kW 690 V in the motor supply line normal duty
110.0 kW 690 V in the motor supply line heavy duty
90.0 kW 230 V to the motor delta terminals normal duty
75.0 kW 230 V to the motor delta terminals heavy duty
132.0 kW 400 V to the motor delta terminals normal duty
110.0 kW 400 V to the motor delta terminals heavy duty
Maximum Horse Power Rating 50.0 hp 208 V normal duty
40.0 hp 208 V heavy duty
60.0 hp 230 V normal duty
50.0 hp 230 V heavy duty
125.0 hp 460 V normal duty
100.0 hp 460 V heavy duty
150.0 hp 575 V normal duty
125.0 hp 575 V heavy duty
Option card Communication module Profibus DP V1
Communication module Modbus TCP/EtherNet/IP
Communication module CANopen daisy chain
Communication module CANopen Sub-D
Communication module CANopen open style
Communication module PROFINET

Complementary

Characteristic Value(s)
Device connection In the motor supply line
To the motor delta terminals
[Us] control circuit voltage 110...230 V AC 50/60 Hz - 15...10 %
Apparent power 0.09 kVA
Integrated motor overload protection True
motor thermal protection class Class 10E
Protection type Phase failure line
Integrated thermal protection motor
Thermal protection starter
Current overload motor
Underload motor
Excessive starting time, locked rotor motor
Motor phase loss motor
Line supply phase loss line
Line supply phase loss motor
Thermal protection motor
current limiting %In (5 x Ie maximum) 150…700 %
[In] Rated current pwr loss specifctn 170.0 A
Power loss static current independent 25.0 W
Power loss per device current dependent 459.0 W
Standards IEC 60947-4-2
UL 60947-4-2
IEC 60664-1
Product Certifications CE
cULus
CCC
UKCA
RCM
EAC
DNV
ABS
BV
CCS
Marking CE
CCC
UKCA
EAC
RCM
CULus
[Uc] control circuit voltage 24 V DC
Discrete input number 4
Discrete input type STOP) logic inputs, 3500 Ohm
RUN) logic inputs, 3500 Ohm
DI3) programmable as logic input, 3500 Ohm
DI4) programmable as logic input, 3500 Ohm
Input compatibility STOP discrete input level 1 PLC IEC 61131-2
RUN discrete input level 1 PLC IEC 61131-2
DI3 discrete input level 1 PLC IEC 61131-2
DI4 discrete input level 1 PLC IEC 61131-2
Discrete input logic Programmable digital input < 5 V
Relay output number 3
Relay output type Relay outputs R1A 1 NO
Relay outputs R1B 1 NO
Relay outputs RIC NO/NC programmable
Minimum switching current 100 mA 12 V DC relay outputs
Maximum switching current Relay outputs 2 A 250 V AC
Relay outputs 2 A 30 V DC
Relay outputs
Discrete output number 2
Discrete output type DQ1) programmable digital output <= 30 V
DQ2) programmable digital output <= 30 V
Output compatibility Open collector level 1 PLC IEC 65A-68
Analogue input number 1
Analogue input type AI1/PTC PTC/Pt 100 temperature probe
PTC2 PTC/Pt 100 temperature probe
PTC3 PTC/Pt 100 temperature probe
Analogue output number 1
Analogue output type Current output AQ1 0...20 mA or 0...10 V 500 Ohm
Communication Port Protocol Modbus serial
Connector Type 1 RJ45
Communication data link Serial
Physical interface 2-wire RS 485
Transmission Rate 1200...256000 bit/s
Transmission frame RTU
Data format 8 bits, configurable odd, even or no parity
Type of polarization No impedance Modbus serial
Number of addresses 0…227 Modbus serial
Method of access Slave Modbus serial
Function Available External bypass control
Pre-heating
Smoke extraction
Multi-motor cascade
Second motor set
User management
Ports and services hardening
Security event logging
Cybersecure firmware update
Single direction
Display screen available True
Operating position Vertical +/- 10 degree
Height 13.4 in (340.0 mm)
Width 7.9 in (200.0 mm)
Depth 10.7 in (272.0 mm)
Product Weight 27.3 lb(US) (12.4 kg)

All PLC Direct products come with a 1-year warranty. The warranty is issued by PLC Direct. Warranty coverage commences at the date of purchase. The warranty is for mechanical defects or failures not caused by human factors including but not limited to (a) incorrect installation, (b) operating the unit in sub-optimal conditions or in scenarios not recommended by the manufacturer, (c) poor unit maintenance, etc. The warranty does not cover programming or software related issues.

If the product is eligible for PLC Direct’s warranty coverage and the customer encounters an issue with the product, we will request the item is shipped to us for diagnosis and examination. Regardless of the cause of product issues, the customer will bear responsibility for the cost of shipping the unit to PLC Direct for evaluation. Where the unit was damaged by human factors, we will offer a repair or replace quote; in cases where damage was caused by human factors, the customer is responsible for the cost of shipping the repaired/replaced unit from PLC Direct to the customer. Where the unit was not damaged by human factors but is covered by PLC Direct’s warranty, we will repair or replace the unit at our cost (or, in rare cases, refund you your purchase); in such cases, PLC Direct will bear the cost of shipping the repaired or replaced product back to the customer. It is up to PLC Direct’s discretion whether to repair, replace, or refund the customer in such cases. Diagnoses can take time to complete based on technician availability and the complexity of diagnosis.

In no event shall PLC Direct be liable for any damages except actual damages up to, but not exceeding, the amount paid to us for the product, including we shall not be liable for any consequential or indirect damages or lost profits whether or not advised of same.

PLC Direct offers free shipping worldwide. Product ship from a various warehouses worldwide based on the customer's and the product's location. The estimated delivery date on the product page is PLC Direct's best estimated assuming a US-based shipping destination.

Regardless of where the product is shipping from, PLC Direct covers all duties for US-based shipping destinations. For non-US-based shipping destinations, customers are responsible for duties as appropriate.

PLC Direct's focus is on balancing price with lead time. Some but not all products can be expedited. If you have questions about delivery ETAs, please contact our team.

Trusted By

"Fast service for obsolete parts"

Increasingly PLC/ HMI control platforms are becoming obsolete and parts are no longer supported, however PLC Direct had the HMI we needed and fast shipping for our system to get back online!

Buyer at GE Health

"Helping us move projects forward"

With supply chain issues increasingly affecting our business, PLC Direct has been there for us to supply the PLC products we need, when we need it. If they don't have it readily available, they find it and provide it quickly and reliably. This has helped us move forward with several projects that would have otherwise taken us many, many months to complete.

Buyer at E-Merge Systems – A Rockwell Integrator

You may also like

Recently viewed