This ABL6 transformer supplies alternating current to control circuits while isolating them from mains power. It has a rated input voltage of 230V to 400V AC, a rated output voltage of 230V AC and a rated power of 100VA. It offers an economic way to supply each consuming load individually, or by groups of loads, in applications such as mining, refining. It is ideal for systems accepting low voltage AC power, such as motor protection relays, contactors.
Main
| Characteristic | Value(s) |
|---|---|
| Range of product | Modicon Transformer Optimized |
| Product or component type | Safety and isolation transformer |
| Rated power in VA | 100 VA |
| Input voltage | 230 V AC single phase, terminal(s): N-L1 400 V AC phase to phase, terminal(s): L1-L2 |
| Output voltage | 230 V AC |
| Secondary winding | Single |
| Protective cover | Without |
| Ambient air temperature for operation | -20â¦50 °C |
Complementary
| Characteristic | Value(s) |
|---|---|
| Input voltage limits | 207...253 V 360...440 V |
| Network frequency limits | 47â¦63 Hz |
| Input voltage tolerance | +/- 15 V |
| Efficiency | 86 % |
| Power dissipation in W | 16.3 W |
| Output sustained overvoltage | 9 % (no load, hot state) |
| Maximum voltage drop at rated load | 0.6 % |
| No load losses | 7.1 W |
| Short-circuit voltage | 0,0832 |
| Output protection type | Against overload, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection Against overvoltage, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection Against short-circuits, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection |
| Connections - terminals | For input connection: screw type terminals, connection capacity: 5 x 4 mm² AWG 11 For input ground connection: screw type terminals, connection capacity: 1 x 4 mm² AWG 11 For output connection: screw type terminals, connection capacity: 2 x 4 mm² AWG 11 |
| Marking | CE |
| Fixing mode | By 4 screws diameter: 4.8 mm on vertical panel, operating position: horizontal By 4 screws diameter: 4.8 mm on vertical panel, operating position: vertical By clips (with mounting plate) on 35 mm symmetrical DIN rail By 4 screws diameter: 4.8 mm on horizontal panel with derating to 90 % |
| Operating altitude | 3000 m |
| Electrical insulation class | Class B |
| Width | 84.0 mm |
| Height | 86.0 mm |
| Depth | 94.0 mm |
| Product weight | 1.99 kg |


This Phaseo ABL1 regulated switch mode power supply (SMPS) supplies direct current voltage. It has a rated input of 100V to 240V AC, a rated output current of 8.3A at 12V DC and a rated power of 100W. It is ideal for supplying DC voltage necessary for automation equipment designed for applications in industrial, commercial and residential applications such as conveying, packaging, control, food & beverage, mining, oil & gas and water. Automatic reset allows short-term faults to be cleared and systems to restart without the need to disturb on-duty maintenance engineers. It has LED diagnostics indicator available in the front for troubleshooting instantly. Its width is 200mm, its height is 98mm, its depth is 38mm. It weighs 0.640kg. It is certified with TUV 60950-1, UL 508, CCSAus, EAC, CSA 22-2 No 60950-1 and RCM. It is a power supply for commercial use, panel mount; It is compatible with reversible mounting bracket type ABL1A01 and ABL1A02 clip-on mounting plate. It installs on panel with reversible mounting bracket or mounting plate fixing by screw. ABL1 power supplies bring energy to your automated systems. ABL1 power supplies are designed for simple and repetitive machines, dedicated power supplies are particularly quality/price competitive due to their simplicity and compactness. The main applications to use Phaseo ABL1 power supply are lifts, display panels, escalators, carwash, foodstuff ovens, etc.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Phaseo Dedicated |
| Product or Component Type | Power supply |
| Power supply type | Regulated switch mode |
| Kw Rating | 100 W |
| Main Input Voltage | 100...240 V AC single phase 120...370 V DC |
| Output voltage | 12 V DC |
| Power supply output current | 8.3 A |
| Operating position | Any position |
| Vibration resistance | 2 gn (f= 9â¦150 Hz) conforming to EN/IEC 61131-2 3.5 mm (f= 5â¦9 Hz) conforming to EN/IEC 61131-2 |
| Name of test | Conducted interference conforming to EN 61000-4-8 level 4 Electrostatic discharges conforming to EN/IEC 61000-4-2 level 3 Induced electromagnetic field conforming to EN/IEC 61000-4-6 level 3 Radiated electromagnetic field conforming to EN/IEC 61000-4-3 level 3 Rapid transient conforming to IEC 61000-4-4 level 3 Conducted/radiated emissions conforming to EN 55022 Class B Conducted/radiated emissions conforming to EN/IEC 55011 Emission conforming to EN/IEC 61000-6-3 Primary outage conforming to IEC 61000-4-11 Surge conforming to EN/IEC 61000-4-5 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Input voltage limits | 85...264 V |
| Network Frequency | 47...63 Hz |
| Inrush current | 50 A at 115 V AC 100 A at 230 V AC |
| Cos phi | 0.7â¦0.95 |
| Efficiency | 80 % |
| Power dissipation in W | 25 W |
| Current consumption | 0.7 A at 240 V 1.7 A at 100 V |
| Input protection type | Integrated fuse (not interchangeable) |
| Output voltage limits | 10.8...13.2 V |
| Line and load regulation | +/- 3 % |
| Holding time | >= 10 ms at 100 V >= 40 ms at 240 V |
| Output protection type | Against overload, protection technology: 1.1...1.5 x In Against overvoltage, protection technology: tripping if U > 1.25 x Un Against short-circuits, protection technology: automatic reset Thermal |
| Connections - terminals | For ground connection: screw type terminals, connection capacity: 1 x 4 mm² AWG 12 For input connection: screw type terminals, connection capacity: 2 x 4 mm² AWG 12 For output connection: screw type terminals, connection capacity: 4 x 4 mm² AWG 12 |
| Marking | CE |
| Mounting Support | Reversible mounting bracket Panel |
| Operating altitude | 6561.68 ft (2000 m) |
| Output coupling | Series Parallel |
| Overvoltage category | II |
| Meantime between failure [MTBF] | 100000 h at 104 °F (40 °C) |
| Status LED | 1 LED (Green) output voltage |
| Product Weight | 1.41 lb(US) (0.64 kg) |

This ABL6 transformer supplies alternating current to control circuits while isolating them from mains power. It has a rated input voltage of 230V to 400V AC, a rated output voltage of 12V AC and a rated power of 100VA. It offers an economic way to supply each consuming load individually, or by groups of loads, in applications such as mining, refining. It is ideal for systems accepting low voltage AC power, such as motor protection relays, contactors.
Main
| Characteristic | Value(s) |
|---|---|
| Range of product | Modicon Transformer Optimized |
| Product or component type | Safety and isolation transformer |
| Rated power in VA | 100 VA |
| Input voltage | 230 V AC single phase, terminal(s): N-L1 400 V AC phase to phase, terminal(s): L1-L2 |
| Output voltage | 12 V AC |
| Secondary winding | Single |
| Protective cover | Without |
| Ambient air temperature for operation | -20â¦50 °C |
Complementary
| Characteristic | Value(s) |
|---|---|
| Input voltage limits | 360...440 V 207...253 V |
| Network frequency limits | 47â¦63 Hz |
| Input voltage tolerance | +/- 15 V |
| Efficiency | 86 % |
| Power dissipation in W | 16.3 W |
| Output sustained overvoltage | 9 % (no load, hot state) |
| Maximum voltage drop at rated load | 0.3 % |
| No load losses | 7.1 W |
| Short-circuit voltage | 8 % |
| Output protection type | Against overload, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection Against overvoltage, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection Against short-circuits, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection |
| Connections - terminals | For input connection: screw type terminals, connection capacity: 5 x 4 mm² AWG 11 For input ground connection: screw type terminals, connection capacity: 1 x 4 mm² AWG 11 For output connection: screw type terminals, connection capacity: 2 x 4 mm² AWG 11 |
| Marking | CE |
| Fixing mode | By 4 screws diameter: 4.8 mm on vertical panel, operating position: horizontal By 4 screws diameter: 4.8 mm on vertical panel, operating position: vertical By clips (with mounting plate) on 35 mm symmetrical DIN rail By 4 screws diameter: 4.8 mm on horizontal panel with derating to 90 % |
| Operating altitude | 3000 m |
| Electrical insulation class | Class B |
| Width | 84.0 mm |
| Height | 86.0 mm |
| Depth | 94.0 mm |
| Product weight | 2.09 kg |

This ABL6 transformer supplies alternating current to control circuits while isolating them from mains power. It has a rated input voltage of 230V to 400V AC, a rated output voltage of 24V AC and a rated power of 100VA. It offers an economic way to supply each consuming load individually, or by groups of loads, in applications such as mining, refining. It is ideal for systems accepting low voltage AC power, such as motor protection relays, contactors.
Main
| Characteristic | Value(s) |
|---|---|
| Range of product | Modicon Transformer Optimized |
| Product or component type | Safety and isolation transformer |
| Rated power in VA | 100 VA |
| Input voltage | 230 V AC single phase, terminal(s): N-L1 400 V AC phase to phase, terminal(s): L1-L2 |
| Output voltage | 24 V AC |
| Secondary winding | Single |
| Protective cover | Without |
| Ambient air temperature for operation | -20â¦50 °C |
Complementary
| Characteristic | Value(s) |
|---|---|
| Input voltage limits | 207...253 V 360...440 V |
| Network frequency limits | 47â¦63 Hz |
| Input voltage tolerance | +/- 15 V |
| Efficiency | 86 % |
| Power dissipation in W | 16.3 W |
| Output sustained overvoltage | 9 % (no load, hot state) |
| Maximum voltage drop at rated load | 0 % |
| No load losses | 7.1 W |
| Short-circuit voltage | 0,0786 |
| Output protection type | Against overload, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection Against overvoltage, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection Against short-circuits, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection |
| Connections - terminals | For input connection: screw type terminals, connection capacity: 5 x 4 mm² AWG 11 For input ground connection: screw type terminals, connection capacity: 1 x 4 mm² AWG 11 For output connection: screw type terminals, connection capacity: 2 x 4 mm² AWG 11 |
| Marking | CE |
| Fixing mode | By 4 screws diameter: 4.8 mm on vertical panel, operating position: horizontal By 4 screws diameter: 4.8 mm on vertical panel, operating position: vertical By clips (with mounting plate) on 35 mm symmetrical DIN rail By 4 screws diameter: 4.8 mm on horizontal panel with derating to 90 % |
| Operating altitude | 3000 m |
| Electrical insulation class | Class B |
| Width | 84.0 mm |
| Height | 87.0 mm |
| Depth | 95.0 mm |
| Product weight | 2.05 kg |

Main
| Characteristic | Value(s) |
|---|---|
| Range of product | Phaseo |
| Accessory / separate part type | Plate for mounting on rail |
| Accessory / separate part category | Mounting and fixing accessories |
| Quantity per set | Set of 5 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Accessory / separate part destination | Transformer: ABL6TS 25 VA |
| Product mounting | 35 mm symmetrical DIN rail |
| Height | 70 mm |
| Width | 68 mm |
| Product weight | 0.045 kg |

This ABL6 transformer supplies alternating current to control circuits while isolating them from mains power. It has a rated input voltage of 230V to 400V AC, a rated output voltage of 24V AC and a rated power of 63VA. It offers an economic way to supply each consuming load individually, or by groups of loads, in applications such as mining, refining. It is ideal for systems accepting low voltage AC power, such as motor protection relays, contactors.
Main
| Characteristic | Value(s) |
|---|---|
| Range of product | Modicon Transformer Optimized |
| Product or component type | Safety and isolation transformer |
| Rated power in VA | 63 VA |
| Input voltage | 230 V AC single phase, terminal(s): N-L1 400 V AC phase to phase, terminal(s): L1-L2 |
| Output voltage | 24 V AC |
| Secondary winding | Single |
| Protective cover | Without |
| Ambient air temperature for operation | -20â¦50 °C |
Complementary
| Characteristic | Value(s) |
|---|---|
| Input voltage limits | 360...440 V 207...253 V |
| Network frequency limits | 47â¦63 Hz |
| Input voltage tolerance | +/- 15 V |
| Efficiency | 84 % |
| Power dissipation in W | 12 W |
| Output sustained overvoltage | 9 % (no load, hot state) |
| Maximum voltage drop at rated load | 0.2 % |
| No load losses | 5.3 W |
| Short-circuit voltage | 0,0862 |
| Output protection type | Against overload, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection Against overvoltage, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection Against short-circuits, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection |
| Connections - terminals | For input connection: screw type terminals, connection capacity: 5 x 4 mm² AWG 11 For input ground connection: screw type terminals, connection capacity: 1 x 4 mm² AWG 11 For output connection: screw type terminals, connection capacity: 2 x 4 mm² AWG 11 |
| Marking | CE |
| Fixing mode | By 4 screws diameter: 4.8 mm on vertical panel, operating position: horizontal By 4 screws diameter: 4.8 mm on vertical panel, operating position: vertical By clips (with mounting plate) on 35 mm symmetrical DIN rail By 4 screws diameter: 4.8 mm on horizontal panel with derating to 90 % |
| Operating altitude | 3000 m |
| Electrical insulation class | Class B |
| Width | 78.0 mm |
| Height | 79.0 mm |
| Depth | 91.0 mm |
| Product weight | 1.46 kg |

This Phaseo ABL1 regulated switch mode power supply (SMPS) supplies direct current voltage. It has a rated input of 100V to 120V AC or 200 to 240V AC, a rated output current of 6.2A at 24V DC and a rated power of 150W. It is ideal for supplying DC voltage necessary for automation equipment designed for applications in industrial, commercial and residential applications such as conveying, packaging, control, food & beverage, mining, oil & gas and water. Automatic reset allows short-term faults to be cleared and systems to restart without the need to disturb on-duty maintenance engineers. It has LED diagnostics indicator available in the front for troubleshooting instantly. Its width is 200mm, its height is 98mm, its depth is 50mm. It weighs 0.970kg. It is certified with TUV 60950-1, UL 508, CCSAus, EAC, CSA 22-2 No 60950-1 and RCM. It is a power supply for commercial use, panel mount; It is compatible with reversible mounting bracket type ABL1A01 and ABL1A02 clip-on mounting plate. It installs on panel with reversible mounting bracket or mounting plate fixing by screw. ABL1 power supplies bring energy to your automated systems. ABL1 power supplies are designed for simple and repetitive machines, dedicated power supplies are particularly quality/price competitive due to their simplicity and compactness. The main applications to use Phaseo ABL1 power supply are lifts, display panels, escalators, carwash, foodstuff ovens, etc.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Phaseo Dedicated |
| Product or Component Type | Power supply |
| Power supply type | Regulated switch mode |
| Kw Rating | 150 W |
| Main Input Voltage | 100...120 V AC single phase 200...240 V AC single phase 180...370 V DC |
| Output voltage | 24 V DC |
| Power supply output current | 6.2 A |
| Operating position | Any position |
| Vibration resistance | 2 gn (f= 9â¦150 Hz) conforming to EN/IEC 61131-2 3.5 mm (f= 5â¦9 Hz) conforming to EN/IEC 61131-2 |
| Name of test | Conducted interference conforming to EN 61000-4-8 level 4 Electrostatic discharges conforming to EN/IEC 61000-4-2 level 3 Induced electromagnetic field conforming to EN/IEC 61000-4-6 level 3 Radiated electromagnetic field conforming to EN/IEC 61000-4-3 level 3 Rapid transient conforming to IEC 61000-4-4 level 3 Conducted/radiated emissions conforming to EN 55022 Class B Conducted/radiated emissions conforming to EN/IEC 55011 Emission conforming to EN/IEC 61000-6-3 Primary outage conforming to IEC 61000-4-11 Surge conforming to EN/IEC 61000-4-5 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Input voltage limits | 85...132 V 170...264 V |
| Network Frequency | 47...63 Hz |
| Inrush current | 50 A at 115 V AC 100 A at 230 V AC |
| Cos phi | 0.7â¦0.95 |
| Efficiency | 80 % |
| Power dissipation in W | 37.5 W |
| Current consumption | 5 A at 100 V 2.5 A at 240 V |
| Input protection type | Integrated fuse (not interchangeable) |
| Output voltage limits | 21.6...26.4 V |
| Line and load regulation | +/- 3 % |
| Holding time | >= 10 ms at 100 V >= 40 ms at 240 V |
| Output protection type | Against overload, protection technology: 1.1...1.5 x In Against overvoltage, protection technology: tripping if U > 1.25 x Un Against short-circuits, protection technology: automatic reset Thermal |
| Connections - terminals | For ground connection: screw type terminals, connection capacity: 1 x 4 mm² AWG 12 For input connection: screw type terminals, connection capacity: 2 x 4 mm² AWG 12 For output connection: screw type terminals, connection capacity: 4 x 4 mm² AWG 12 |
| Marking | CE |
| Mounting Support | Reversible mounting bracket Panel |
| Operating altitude | 6561.68 ft (2000 m) |
| Output coupling | Series Parallel |
| Overvoltage category | II |
| Meantime between failure [MTBF] | 100000 h at 104 °F (40 °C) |
| Status LED | 1 LED (Green) output voltage |
| Product Weight | 2.14 lb(US) (0.97 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Premium Automation platform |
| Product or Component Type | Power supply module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Primary voltage | 100...240 V AC 85...264 V |
| Network Frequency | 50/60 Hz |
| Network frequency limits | 47â¦63 Hz |
| Input current | 300 mA 240 V 500 mA 100 V |
| Inrush current | 37 A 100 V 75 A 240 V |
| I²t on activation | 0.63 A².s 100 V 2.6 A².s 240 V |
| It on activation | 0.034 A.s 100 V 0.067 A.s 240 V |
| Protection type | Internal fuse 4 A 5 x 20 mm time-delayed primary circuit Overload protection secondary circuit Overvoltage protection secondary circuit Short-circuit protection secondary circuit |
| Total useful secondary power | 26 W |
| Secondary power | 15 W 24 V DC 25 W 5 V DC |
| Current at secondary voltage | 0.5 A 24 V DC sensor power supply 0.6 A 24 V DC relay power supply 5 A 5 V DC |
| Insulation resistance | >= 100 MOhm primary/ground >= 100 MOhm primary/secondary |
| Marking | CE |
| Local signalling | 1 LED (green) for presence of sensor voltage (24V) 1 LED (green) for presence of voltages (OK) 1 LED (red) for battery fault (BAT) |
| Module format | Standard |
| Product Weight | 1.12 lb(US) (0.51 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Premium Automation platform |
| Product or Component Type | Power supply module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Primary voltage | 100...120 V AC 85...140 V 200...240 V AC 190...264 V |
| Network Frequency | 50/60 Hz |
| Network frequency limits | 47â¦63 Hz |
| Input current | 1700 mA 100 V 500 mA 240 V |
| Inrush current | 38 A 100 V 38 A 240 V |
| I²t on activation | 2 A².s 240 V 4 A².s 100 V |
| It on activation | 0.11 A.s 100 V 0.11 A.s 240 V |
| Protection type | Internal fuse 4 A 5 x 20 mm time-delayed primary circuit Overload protection secondary circuit Overvoltage protection secondary circuit Short-circuit protection secondary circuit |
| Total useful secondary power | 50 W |
| Secondary power | 19 W 24 V DC 35 W 5 V DC |
| Current at secondary voltage | 0.8 A 24 V DC relay power supply 0.8 A 24 V DC sensor power supply 7 A 5 V DC |
| Insulation resistance | >= 100 MOhm primary/ground >= 100 MOhm primary/secondary |
| Marking | CE |
| Local signalling | 1 LED (green) for presence of sensor voltage (24V) 1 LED (green) for presence of voltages (OK) 1 LED (red) for battery fault (BAT) |
| Module format | Double |
| Product Weight | 1.37 lb(US) (0.62 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Premium Automation platform |
| Product or Component Type | Power supply module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Primary voltage | 100...120 V AC 85...140 V 200...240 V AC 170...264 V |
| Network Frequency | 50/60 Hz |
| Network frequency limits | 47â¦63 Hz |
| Input current | 1700 mA 100 V 500 mA 240 V |
| Inrush current | 30 A 100 V 60 A 240 V |
| I²t on activation | 15 A².s 100 V 8 A².s 240 V |
| It on activation | 0.15 A.s 100 V 0.15 A.s 240 V |
| Protection type | Internal fuse 4 A 5 x 20 mm time-delayed primary circuit Overload protection secondary circuit Overvoltage protection secondary circuit Short-circuit protection secondary circuit |
| Total useful secondary power | 100 W 131 °F (55 °C) with fan module 77 W 140 °F (60 °C) 85 W 131 °F (55 °C) |
| Secondary power | 75 W 5 V DC |
| Current at secondary voltage | 1.6 A 24 V DC sensor power supply 15 A 5 V DC |
| Insulation resistance | >= 100 MOhm primary/ground >= 100 MOhm primary/secondary |
| Marking | CE |
| Local signalling | 1 LED (green) for presence of sensor voltage (24V) 1 LED (green) for presence of voltages (OK) 1 LED (red) for battery fault (BAT) |
| Module format | Double |
| Product Weight | 1.63 lb(US) (0.74 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Premium Automation platform |
| Product or Component Type | Power supply module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Primary voltage | 24...48 V DC 19.2...60 V |
| Input current | <= 1500 mA 48 V <= 3000 mA 24 V |
| Inrush current | 15 A 24 V 15 A 48 V |
| I²t on activation | 50 A².s 24 V 55 A².s 48 V |
| It on activation | 6 A.s 48 V 7 A.s 24 V |
| Protection type | Internal fuse 5 A 5 x 20 mm time-delayed primary circuit Overload protection secondary circuit Overvoltage protection secondary circuit Short-circuit protection secondary circuit |
| Total useful secondary power | 50 W |
| Secondary power | 19 W 24 V DC 35 W 5 V DC |
| Current at secondary voltage | 0.8 A 24 V DC relay power supply 7 A 5 V DC |
| Insulation resistance | >= 10 mOhm primary/ground >= 10 mOhm primary/secondary |
| Marking | CE |
| Local signalling | 1 LED (green) for presence of voltages (OK) 1 LED (red) for battery fault (BAT) |
| Module format | Double |
| Product Weight | 1.96 lb(US) (0.89 kg) |