Ask for quote
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Zelio Time |
| Product or Component Type | Industrial timing relay |
| Component name | RE7 |
| Time delay type | Di D W C A H |
| Time delay range | 0.05 s...300 h |
Complementary
| Characteristic | Value(s) |
|---|---|
| Discrete output type | Relay |
| Contacts material | 90/10 silver nickel contacts |
| Width pitch dimension | 0.9 in (22.5 mm) |
| [Us] rated supply voltage | 110...240 V AC 50/60 Hz 24 V AC/DC 50/60 Hz 42...48 V AC/DC 50/60 Hz |
| Voltage range | 0.85...1.1 Us |
| Connections - terminals | Screw terminals, 2 x 1.5 mm² flexible with cable end Screw terminals, 2 x 2.5 mm² flexible without cable end |
| Tightening torque | 5.3â¦9.7 lbf.in (0.6â¦1.1 N.m) |
| Setting accuracy of time delay | +/- 10 % of full scale |
| Repeat accuracy | +/- 0.2 % |
| Temperature Drift | < 0.07 %/°C |
| Voltage drift | < 0.2 %/V |
| Minimum pulse duration | 20 ms |
| Reset time | 50 ms |
| Maximum switching voltage | 250 V AC/DC |
| Mechanical durability | 20000000 cycles |
| [Ith] conventional free air thermal current | 8 A |
| Maximum [Ie] rated operational current | 2 A DC-13 24 V 158 °F (70 °C) IEC 60947-5-1/1991/VDE 0660 0.1 A DC-13 250 V 158 °F (70 °C) IEC 60947-5-1/1991/VDE 0660 0.2 A DC-13 115 V 158 °F (70 °C) IEC 60947-5-1/1991/VDE 0660 3 A AC-15 158 °F (70 °C) IEC 60947-5-1/1991/VDE 0660 |
| Minimum switching capacity | 10 mA 12 V |
| Input voltage | < 60 V X1Z2 < 60 V Y1Z2 |
| Maximum switching current | 1 mA X1Z2) 1 mA Y1Z2) |
| Input compatibility | 3/4 wires sensors PNP/NPN without internal load <164.04 ft (50 m) X1Z2 3/4 wires sensors PNP/NPN without internal load <164.04 ft (50 m) Y1Z2 |
| Potentiometer characteristic | Linear 47 kOhm +/- 20 %), 0.2 W 82.02 ft (25 m) Z1Z2 |
| Marking | CE |
| Overvoltage category | III conforming to IEC 60664-1 |
| [Ui] rated insulation voltage | 250 V between contact circuit and control inputs IEC 250 V between contact circuit and power supply IEC 300 V between contact circuit and control inputs CSA 300 V between contact circuit and power supply CSA |
| Supply disconnection value | > 0.1 Uc |
| Operating position | Any position without derating |
| Surge withstand | 2 kV IEC 61000-4-5 level 3 |
| Power consumption in VA | 0.7 VA 24 V 1.6 VA 48 V 1.8 VA 110 V 8.5 VA 240 V |
| Maximum power consumption in W | 0.5 W 24 V 1.2 W 48 V |
| Terminal description | (Y1)UNUSED (15-16-18)OC (Z1)UNUSED (Z2)UNUSED (B1-A2)CO ALT (X1)UNUSED |
| Height | 3.07 in (78 mm) |
| Width | 0.9 in (22.5 mm) |
| Depth | 3.1 in (80 mm) |
| Product Weight | 0.33 lb(US) (0.15 kg) |
All PLC Direct products come with a 1-year warranty. The warranty is issued by PLC Direct. Warranty coverage commences at the date of purchase. The warranty is for mechanical defects or failures not caused by human factors including but not limited to (a) incorrect installation, (b) operating the unit in sub-optimal conditions or in scenarios not recommended by the manufacturer, (c) poor unit maintenance, etc. The warranty does not cover programming or software related issues.
If the product is eligible for PLC Direct’s warranty coverage and the customer encounters an issue with the product, we will request the item is shipped to us for diagnosis and examination. Regardless of the cause of product issues, the customer will bear responsibility for the cost of shipping the unit to PLC Direct for evaluation. Where the unit was damaged by human factors, we will offer a repair or replace quote; in cases where damage was caused by human factors, the customer is responsible for the cost of shipping the repaired/replaced unit from PLC Direct to the customer. Where the unit was not damaged by human factors but is covered by PLC Direct’s warranty, we will repair or replace the unit at our cost (or, in rare cases, refund you your purchase); in such cases, PLC Direct will bear the cost of shipping the repaired or replaced product back to the customer. It is up to PLC Direct’s discretion whether to repair, replace, or refund the customer in such cases. Diagnoses can take time to complete based on technician availability and the complexity of diagnosis.
In no event shall PLC Direct be liable for any damages except actual damages up to, but not exceeding, the amount paid to us for the product, including we shall not be liable for any consequential or indirect damages or lost profits whether or not advised of same.
PLC Direct offers free shipping worldwide. Product ship from a various warehouses worldwide based on the customer's and the product's location. The estimated delivery date on the product page is PLC Direct's best estimated assuming a US-based shipping destination.
Regardless of where the product is shipping from, PLC Direct covers all duties for US-based shipping destinations. For non-US-based shipping destinations, customers are responsible for duties as appropriate.
PLC Direct's focus is on balancing price with lead time. Some but not all products can be expedited. If you have questions about delivery ETAs, please contact our team.

Ask for quote

"Fast service for obsolete parts"
Increasingly PLC/ HMI control platforms are becoming obsolete and parts are no longer supported, however PLC Direct had the HMI we needed and fast shipping for our system to get back online!
Buyer at GE Health

"Helping us move projects forward"
With supply chain issues increasingly affecting our business, PLC Direct has been there for us to supply the PLC products we need, when we need it. If they don't have it readily available, they find it and provide it quickly and reliably. This has helped us move forward with several projects that would have otherwise taken us many, many months to complete.
Buyer at E-Merge Systems – A Rockwell Integrator