Ask for quote
| Characteristic | Value(s) |
|---|---|
| Motor power kW | 18.5 kW at 220...230 V AC 50 Hz (AC-3) 30 kW at 380...400 V AC 50 Hz (AC-3) 37 kW at 415 V AC 50 Hz (AC-3) 37 kW at 440 V AC 50 Hz (AC-3) 37 kW at 500 V AC 50 Hz (AC-3) 37 kW at 660...690 V AC 50 Hz (AC-3) 18.5 kW at 220...230 V AC 50 Hz (AC-3e) 30 kW at 380...400 V AC 50 Hz (AC-3e) 37 kW at 415 V AC 50 Hz (AC-3e) 37 kW at 440 V AC 50 Hz (AC-3e) 37 kW at 500 V AC 50 Hz (AC-3e) 37 kW at 660...690 V AC 50 Hz (AC-3e) |
| Motor power hp | 5 hp at 115 V AC 60 Hz for 1 phase motors 10 hp at 230/240 V AC 60 Hz for 1 phase motors 20 hp at 200/208 V AC 60 Hz for 3 phases motors 20 hp at 230/240 V AC 60 Hz for 3 phases motors 40 hp at 460/480 V AC 60 Hz for 3 phases motors 50 hp at 575/600 V AC 60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 80 A (at 60 °C) for power circuit 10 A (at 60 °C) for signalling circuit |
| Irms rated making capacity | 1000 A at 440 V for power circuit conforming to IEC 60947 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1000 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 110 A 40 °C - 10 min for power circuit 260 A 40 °C - 1 min for power circuit 640 A 40 °C - 10 s for power circuit 900 A 40 °C - 1 s for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 125 A gG at <= 690 V coordination type 1 for power circuit 125 A gG at <= 690 V coordination type 2 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1 |
| Average impedance | 1.5 mOhm - Ith 80 A 50 Hz for power circuit |
| Power dissipation per pole | 9.6 W AC-1 6.3 W AC-3 6.3 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1 Signalling circuit: 690 V conforming to IEC 60947-1 |
| Overvoltage category | III |
| pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 6 Mcycles |
| Electrical durability | 1.8 Mcycles 57 A AC-3 at Ue <= 440 V 0.5 Mcycles 80 A AC-1 at Ue <= 440 V 1.8 Mcycles 57 A AC-3e at Ue <= 440 V |
| Control circuit type | AC/DC at 50/60 Hz AC/DC electronic |
| Coil technology | Built-in bidirectional peak limiting |
| Control circuit voltage limits | <= 0.1 Uc (-40â¦70 °C):drop-out AC/DC 0.85...1.1 Uc (-40â¦60 °C):operational AC/DC 1...1.1 Uc (60â¦70 °C):operational AC/DC |
| Inrush power in VA | 18 VA 50/60 Hz (at 20 °C) |
| Inrush power in W | 14 W (at 20 °C) |
| Hold-in power consumption in VA | 1.8 VA 50/60 Hz (at 20 °C) |
| Hold-in power consumption in W | 1.2 W at 20 °C |
| Heat dissipation | 1.2 W at 50/60 Hz |
| Operating time | 55...65 ms closing 20...80 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Connections - terminals | Power circuit: lugs-ring terminals - external diameter: 16.5 mm Control circuit: lugs-ring terminals - external diameter: 8 mm |
| Tightening torque | Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver flat à 6 mm M3.5 Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5 Power circuit: 6 N.m - on lugs-ring terminals hexagonal screw head 10 mm M6 Power circuit: 6 N.m - on lugs-ring terminals - with screwdriver pozidriv No 2 M4 Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver pozidriv No 2 M3.5 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
| Mounting support | Rail Plate |
All PLC Direct products come with a 1-year warranty. The warranty is issued by PLC Direct. Warranty coverage commences at the date of purchase. The warranty is for mechanical defects or failures not caused by human factors including but not limited to (a) incorrect installation, (b) operating the unit in sub-optimal conditions or in scenarios not recommended by the manufacturer, (c) poor unit maintenance, etc. The warranty does not cover programming or software related issues.
If the product is eligible for PLC Direct’s warranty coverage and the customer encounters an issue with the product, we will request the item is shipped to us for diagnosis and examination. Regardless of the cause of product issues, the customer will bear responsibility for the cost of shipping the unit to PLC Direct for evaluation. Where the unit was damaged by human factors, we will offer a repair or replace quote; in cases where damage was caused by human factors, the customer is responsible for the cost of shipping the repaired/replaced unit from PLC Direct to the customer. Where the unit was not damaged by human factors but is covered by PLC Direct’s warranty, we will repair or replace the unit at our cost (or, in rare cases, refund you your purchase); in such cases, PLC Direct will bear the cost of shipping the repaired or replaced product back to the customer. It is up to PLC Direct’s discretion whether to repair, replace, or refund the customer in such cases. Diagnoses can take time to complete based on technician availability and the complexity of diagnosis.
In no event shall PLC Direct be liable for any damages except actual damages up to, but not exceeding, the amount paid to us for the product, including we shall not be liable for any consequential or indirect damages or lost profits whether or not advised of same.
PLC Direct offers free shipping worldwide. Product ship from a various warehouses worldwide based on the customer's and the product's location. The estimated delivery date on the product page is PLC Direct's best estimated assuming a US-based shipping destination.
Regardless of where the product is shipping from, PLC Direct covers all duties for US-based shipping destinations. For non-US-based shipping destinations, customers are responsible for duties as appropriate.
PLC Direct's focus is on balancing price with lead time. Some but not all products can be expedited. If you have questions about delivery ETAs, please contact our team.

Ask for quote
Trusted By
Need More?
Contact Us
we're here to support your business.

"Fast service for obsolete parts"
Increasingly PLC/ HMI control platforms are becoming obsolete and parts are no longer supported, however PLC Direct had the HMI we needed and fast shipping for our system to get back online!
Buyer at GE Health

"Helping us move projects forward"
With supply chain issues increasingly affecting our business, PLC Direct has been there for us to supply the PLC products we need, when we need it. If they don't have it readily available, they find it and provide it quickly and reliably. This has helped us move forward with several projects that would have otherwise taken us many, many months to complete.
Buyer at E-Merge Systems – A Rockwell Integrator