| Characteristic | Value(s) |
|---|---|
| Discrete input number | 8 |
| Discrete input type | DI7, DI8 programmable as pulse input: 0â¦30 kHz, 24 V DC (<= 30 V) |
| Discrete input logic | 16 preset speeds |
| Discrete output number | 0 |
| Discrete output type | Relay outputs R1A, R1B, R1C 250 V AC 3000 mA Relay outputs R1A, R1B, R1C 30 V DC 3000 mA Relay outputs R2A, R2C 250 V AC 5000 mA Relay outputs R2A, R2C 30 V DC 5000 mA Relay outputs R3A, R3C 250 V AC 5000 mA Relay outputs R3A, R3C 30 V DC 5000 mA |
| Analogue input number | 3 |
| Analogue input type | AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits AI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits |
| Analogue output number | 2 |
| Analogue output type | Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits Software-configurable current DQ-, DQ+: 30 V DC Software-configurable current DQ-, DQ+: 100 mA |
| Relay output number | 3 |
| Relay output type | Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles |
| Maximum switching current | Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC |
| Minimum switching current | Relay output R1, R2, R3: 5 mA at 24 V DC |
| Network number of phases | 3 phases |
| Physical interface | Ethernet 2-wire RS 485 |
| Method of access | Slave Modbus TCP |
| Transmission rate | 10, 100 Mbits 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps |
| Transmission frame | RTU |
| Output voltage | <= power supply voltage |
| Permissible temporary current boost | 1.5 x In during 60 s (heavy duty) 1.1 x In during 60 s (normal duty) |
| Data format | 8 bits, configurable odd, even or no parity |
| Type of polarization | No impedance |
| Frequency resolution | Analog input: 0.012/50 Hz Display unit: 0.1 Hz |
| Electrical connection | Motor: screw terminal 70...120 mm²/AWG 1/0...250 kcmil Line side: screw terminal 70...95 mm²/AWG 1...250 kcmil Control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16 |
| Connector type | RJ45 (on the remote graphic terminal) for Modbus serial RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP |
| Exchange mode | Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP |
| Number of addresses | 1â¦247 for Modbus serial |
| Supply | Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection Internal supply for digital inputs and STO: 24 V DC (21â¦27 V), <200 mA, protection type: overload and short-circuit protection External supply for digital inputs: 24 V DC (19â¦30 V), <1.25 mA, protection type: overload and short-circuit protection |
| Local signalling | 3 LEDs (dual colour) for embedded communication status 4 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage 3 LEDs for local diagnostic |
| Input compatibility | DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68 STOA, STOB: discrete input level 1 PLC conforming to IEC 61131-2 DI1...DI6: discrete input level 1 PLC conforming to IEC 61131-2 |
| Discrete input logic | Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1) Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1) |
| Sampling duration | 5 ms +/- 1 ms (DI5, DI6) - discrete input 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input 10 ms +/- 1 ms (AO1) - analog output 2 ms +/- 0.5 ms (DI1...DI4) - discrete input |
| Accuracy | +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input |
| Linearity error | AO1, AO2: +/- 0.2 % for analog output AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input |
| Refresh time | Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
| Isolation | Between power and control terminals |
| Discrete and process manufacturing | Building - HVAC compressor centrifugal |
| Power range | 55â¦100 kW at 380â¦440 V 3 phases |
| Enclosure mounting | Wall mounted |
| 4 quadrant operation possible | False |
| Asynchronous motor control profile | Constant torque standard Optimized torque mode Optimized torque mode |
| Synchronous motor control profile | Synchronous reluctance motor Permanent magnet motor |
| Maximum output frequency | 500 kHz |
| Acceleration and deceleration ramps | Linear adjustable separately from 0.01...9999 s |
| Motor slip compensation | Not available in permanent magnet motor law Adjustable Can be suppressed Adjustable |
| Switching frequency | 2...8 kHz adjustable 2.5...8 kHz with derating factor |
| Nominal switching frequency | 2.5 kHz |
| Braking to standstill | By DC injection |
| Brake chopper integrated | False |
| Maximum input current | 131.3 A |
| Maximum output voltage | 480.0 V |
| Apparent power | 59.7 kVA at 480 V (heavy duty) 93.7 kVA at 480 V (normal duty) |
| Maximum transient current | 132 A during 60 s (heavy duty) 159.5 A during 60 s (normal duty) |
| Network frequency | 50...60 Hz |
| Prospective line Isc | 50 kA |
| Base load current at high overload | 106.0 A |
| Base load current at low overload | 145.0 A |
| With safety function Safely Limited Speed (SLS) | False |
| With safety function Safe brake management (SBC/SBT) | False |
| With safety function Safe Operating Stop (SOS) | False |
| With safety function Safe Position (SP) | False |
| With safety function Safe programmable logic | False |
| With safety function Safe Speed Monitor (SSM) | False |
| With safety function Safe Stop 1 (SS1) | False |
| With sft fct Safe Stop 2 (SS2) | False |
| With safety function Safe torque off (STO) | True |
| With safety function Safely Limited Position (SLP) | False |
| With safety function Safe Direction (SDI) | False |
| Protection type | Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive Thermal protection: motor |
| Quantity per set | 1 |
| Width | 345 mm |
| Height | 1250 mm |
| Depth | 375 mm |
| Product weight | 87 kg |
All PLC Direct products come with a 1-year warranty. The warranty is issued by PLC Direct. Warranty coverage commences at the date of purchase. The warranty is for mechanical defects or failures not caused by human factors including but not limited to (a) incorrect installation, (b) operating the unit in sub-optimal conditions or in scenarios not recommended by the manufacturer, (c) poor unit maintenance, etc. The warranty does not cover programming or software related issues.
If the product is eligible for PLC Direct’s warranty coverage and the customer encounters an issue with the product, we will request the item is shipped to us for diagnosis and examination. Regardless of the cause of product issues, the customer will bear responsibility for the cost of shipping the unit to PLC Direct for evaluation. Where the unit was damaged by human factors, we will offer a repair or replace quote; in cases where damage was caused by human factors, the customer is responsible for the cost of shipping the repaired/replaced unit from PLC Direct to the customer. Where the unit was not damaged by human factors but is covered by PLC Direct’s warranty, we will repair or replace the unit at our cost (or, in rare cases, refund you your purchase); in such cases, PLC Direct will bear the cost of shipping the repaired or replaced product back to the customer. It is up to PLC Direct’s discretion whether to repair, replace, or refund the customer in such cases. Diagnoses can take time to complete based on technician availability and the complexity of diagnosis.
In no event shall PLC Direct be liable for any damages except actual damages up to, but not exceeding, the amount paid to us for the product, including we shall not be liable for any consequential or indirect damages or lost profits whether or not advised of same.
PLC Direct offers free shipping worldwide. Product ship from a various warehouses worldwide based on the customer's and the product's location. The estimated delivery date on the product page is PLC Direct's best estimated assuming a US-based shipping destination.
Regardless of where the product is shipping from, PLC Direct covers all duties for US-based shipping destinations. For non-US-based shipping destinations, customers are responsible for duties as appropriate.
PLC Direct's focus is on balancing price with lead time. Some but not all products can be expedited. If you have questions about delivery ETAs, please contact our team.

Trusted By
Need More?
Contact Us
we're here to support your business.

"Fast service for obsolete parts"
Increasingly PLC/ HMI control platforms are becoming obsolete and parts are no longer supported, however PLC Direct had the HMI we needed and fast shipping for our system to get back online!
Buyer at GE Health

"Helping us move projects forward"
With supply chain issues increasingly affecting our business, PLC Direct has been there for us to supply the PLC products we need, when we need it. If they don't have it readily available, they find it and provide it quickly and reliably. This has helped us move forward with several projects that would have otherwise taken us many, many months to complete.
Buyer at E-Merge Systems – A Rockwell Integrator