Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Premium Automation platform |
| Product or Component Type | Power supply module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Primary voltage | 100...240 V AC 85...264 V |
| Network Frequency | 50/60 Hz |
| Network frequency limits | 47â¦63 Hz |
| Input current | 300 mA 240 V 500 mA 100 V |
| Inrush current | 37 A 100 V 75 A 240 V |
| I²t on activation | 0.63 A².s 100 V 2.6 A².s 240 V |
| It on activation | 0.034 A.s 100 V 0.067 A.s 240 V |
| Protection type | Internal fuse 4 A 5 x 20 mm time-delayed primary circuit Overload protection secondary circuit Overvoltage protection secondary circuit Short-circuit protection secondary circuit |
| Total useful secondary power | 26 W |
| Secondary power | 15 W 24 V DC 25 W 5 V DC |
| Current at secondary voltage | 0.5 A 24 V DC sensor power supply 0.6 A 24 V DC relay power supply 5 A 5 V DC |
| Insulation resistance | >= 100 MOhm primary/ground >= 100 MOhm primary/secondary |
| Marking | CE |
| Local signalling | 1 LED (green) for presence of sensor voltage (24V) 1 LED (green) for presence of voltages (OK) 1 LED (red) for battery fault (BAT) |
| Module format | Standard |
| Product Weight | 1.12 lb(US) (0.51 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Premium Automation platform |
| Product or Component Type | Power supply module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Primary voltage | 24 V DC 19.2...30 V |
| Input current | <= 2700 mA 24 V |
| Inrush current | 150 A 24 V |
| I²t on activation | 20 A².s |
| It on activation | 0.5 A.s |
| Protection type | Overload protection secondary circuit Overvoltage protection secondary circuit Short-circuit protection secondary circuit |
| Total useful secondary power | 50 W |
| Secondary power | 19 W 24 V DC 35 W 5 V DC |
| Current at secondary voltage | 0.6 A 24 V DC relay power supply 7 A 5 V DC |
| Marking | CE |
| Local signalling | 1 LED (green) for presence of voltages (OK) 1 LED (red) for battery fault (BAT) |
| Module format | Double |
| Product Weight | 1.72 lb(US) (0.78 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Premium Automation platform |
| Product or Component Type | Power supply module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Primary voltage | 100...120 V AC 85...140 V 200...240 V AC 190...264 V |
| Network Frequency | 50/60 Hz |
| Network frequency limits | 47â¦63 Hz |
| Input current | 1700 mA 100 V 500 mA 240 V |
| Inrush current | 38 A 100 V 38 A 240 V |
| I²t on activation | 2 A².s 240 V 4 A².s 100 V |
| It on activation | 0.11 A.s 100 V 0.11 A.s 240 V |
| Protection type | Internal fuse 4 A 5 x 20 mm time-delayed primary circuit Overload protection secondary circuit Overvoltage protection secondary circuit Short-circuit protection secondary circuit |
| Total useful secondary power | 50 W |
| Secondary power | 19 W 24 V DC 35 W 5 V DC |
| Current at secondary voltage | 0.8 A 24 V DC relay power supply 0.8 A 24 V DC sensor power supply 7 A 5 V DC |
| Insulation resistance | >= 100 MOhm primary/ground >= 100 MOhm primary/secondary |
| Marking | CE |
| Local signalling | 1 LED (green) for presence of sensor voltage (24V) 1 LED (green) for presence of voltages (OK) 1 LED (red) for battery fault (BAT) |
| Module format | Double |
| Product Weight | 1.37 lb(US) (0.62 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Premium Automation platform |
| Product or Component Type | Power supply module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Primary voltage | 100...240 V AC 85...264 V |
| Network Frequency | 50/60 Hz |
| Network frequency limits | 47â¦63 Hz |
| Input current | 300 mA 240 V 500 mA 100 V |
| Inrush current | 37 A 100 V 75 A 240 V |
| I²t on activation | 0.63 A².s 100 V 2.6 A².s 240 V |
| It on activation | 0.034 A.s 100 V 0.067 A.s 240 V |
| Protection type | Internal fuse 4 A 5 x 20 mm time-delayed primary circuit Overload protection secondary circuit Overvoltage protection secondary circuit Short-circuit protection secondary circuit |
| Total useful secondary power | 26 W |
| Secondary power | 15 W 24 V DC 25 W 5 V DC |
| Current at secondary voltage | 0.5 A 24 V DC sensor power supply 0.6 A 24 V DC relay power supply 5 A 5 V DC |
| Insulation resistance | >= 100 MOhm primary/ground >= 100 MOhm primary/secondary |
| Marking | CE |
| Local signalling | 1 LED (green) for presence of sensor voltage (24V) 1 LED (green) for presence of voltages (OK) 1 LED (red) for battery fault (BAT) |
| Module format | Standard |
| Product Weight | 1.12 lb(US) (0.51 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Premium Automation platform |
| Product or Component Type | Power supply module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Primary voltage | 100...120 V AC 85...140 V 200...240 V AC 190...264 V |
| Network Frequency | 50/60 Hz |
| Network frequency limits | 47â¦63 Hz |
| Input current | 1700 mA 100 V 500 mA 240 V |
| Inrush current | 38 A 100 V 38 A 240 V |
| I²t on activation | 2 A².s 240 V 4 A².s 100 V |
| It on activation | 0.11 A.s 100 V 0.11 A.s 240 V |
| Protection type | Internal fuse 4 A 5 x 20 mm time-delayed primary circuit Overload protection secondary circuit Overvoltage protection secondary circuit Short-circuit protection secondary circuit |
| Total useful secondary power | 50 W |
| Secondary power | 19 W 24 V DC 35 W 5 V DC |
| Current at secondary voltage | 0.8 A 24 V DC relay power supply 0.8 A 24 V DC sensor power supply 7 A 5 V DC |
| Insulation resistance | >= 100 MOhm primary/ground >= 100 MOhm primary/secondary |
| Marking | CE |
| Local signalling | 1 LED (green) for presence of sensor voltage (24V) 1 LED (green) for presence of voltages (OK) 1 LED (red) for battery fault (BAT) |
| Module format | Double |
| Product Weight | 1.37 lb(US) (0.62 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Premium Automation platform |
| Product or Component Type | Power supply module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Primary voltage | 100...120 V AC 85...140 V 200...240 V AC 170...264 V |
| Network Frequency | 50/60 Hz |
| Network frequency limits | 47â¦63 Hz |
| Input current | 1700 mA 100 V 500 mA 240 V |
| Inrush current | 30 A 100 V 60 A 240 V |
| I²t on activation | 15 A².s 100 V 8 A².s 240 V |
| It on activation | 0.15 A.s 100 V 0.15 A.s 240 V |
| Protection type | Internal fuse 4 A 5 x 20 mm time-delayed primary circuit Overload protection secondary circuit Overvoltage protection secondary circuit Short-circuit protection secondary circuit |
| Total useful secondary power | 100 W 131 °F (55 °C) with fan module 77 W 140 °F (60 °C) 85 W 131 °F (55 °C) |
| Secondary power | 75 W 5 V DC |
| Current at secondary voltage | 1.6 A 24 V DC sensor power supply 15 A 5 V DC |
| Insulation resistance | >= 100 MOhm primary/ground >= 100 MOhm primary/secondary |
| Marking | CE |
| Local signalling | 1 LED (green) for presence of sensor voltage (24V) 1 LED (green) for presence of voltages (OK) 1 LED (red) for battery fault (BAT) |
| Module format | Double |
| Product Weight | 1.63 lb(US) (0.74 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Premium Automation platform |
| Product or Component Type | Power supply module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Primary voltage | 24...48 V DC 19.2...60 V |
| Input current | <= 1500 mA 48 V <= 3000 mA 24 V |
| Inrush current | 15 A 24 V 15 A 48 V |
| I²t on activation | 50 A².s 24 V 55 A².s 48 V |
| It on activation | 6 A.s 48 V 7 A.s 24 V |
| Protection type | Internal fuse 5 A 5 x 20 mm time-delayed primary circuit Overload protection secondary circuit Overvoltage protection secondary circuit Short-circuit protection secondary circuit |
| Total useful secondary power | 50 W |
| Secondary power | 19 W 24 V DC 35 W 5 V DC |
| Current at secondary voltage | 0.8 A 24 V DC relay power supply 7 A 5 V DC |
| Insulation resistance | >= 10 mOhm primary/ground >= 10 mOhm primary/secondary |
| Marking | CE |
| Local signalling | 1 LED (green) for presence of voltages (OK) 1 LED (red) for battery fault (BAT) |
| Module format | Double |
| Product Weight | 1.96 lb(US) (0.89 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Premium Automation platform |
| Product or Component Type | Power supply module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Primary voltage | 24 V DC 19.2...30 V |
| Input current | <= 1500 mA 24 V |
| Inrush current | 100 A 24 V |
| I²t on activation | 12.5 A².s |
| It on activation | 0.2 A.s |
| Protection type | Internal fuse 3.5 A 5 x 20 mm time-delayed primary circuit Overload protection secondary circuit Overvoltage protection secondary circuit Short-circuit protection secondary circuit |
| Total useful secondary power | 30 W |
| Secondary power | 15 W 24 V DC 15 W 5 V DC |
| Current at secondary voltage | 0.6 A 24 V DC relay power supply 3 A 5 V DC |
| Marking | CE |
| Local signalling | 1 LED (green) for presence of voltages (OK) 1 LED (red) for battery fault (BAT) |
| Module format | Standard |
| Product Weight | 1.19 lb(US) (0.54 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Premium Automation platform |
| Product or Component Type | Power supply module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Primary voltage | 24 V DC 19.2...30 V |
| Input current | <= 1500 mA 24 V |
| Inrush current | 100 A 24 V |
| I²t on activation | 12.5 A².s |
| It on activation | 0.2 A.s |
| Protection type | Internal fuse 3.5 A 5 x 20 mm time-delayed primary circuit Overload protection secondary circuit Overvoltage protection secondary circuit Short-circuit protection secondary circuit |
| Total useful secondary power | 30 W |
| Secondary power | 15 W 24 V DC 15 W 5 V DC |
| Current at secondary voltage | 0.6 A 24 V DC relay power supply 3 A 5 V DC |
| Marking | CE |
| Local signalling | 1 LED (green) for presence of voltages (OK) 1 LED (red) for battery fault (BAT) |
| Module format | Standard |
| Product Weight | 1.19 lb(US) (0.54 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Premium Automation platform |
| Product or Component Type | Power supply module |
Complementary
| Characteristic | Value(s) |
|---|---|
| Primary voltage | 24...48 V DC 19.2...60 V |
| Input current | <= 1500 mA 48 V <= 3000 mA 24 V |
| Inrush current | 15 A 24 V 15 A 48 V |
| I²t on activation | 50 A².s 24 V 55 A².s 48 V |
| It on activation | 6 A.s 48 V 7 A.s 24 V |
| Protection type | Internal fuse 5 A 5 x 20 mm time-delayed primary circuit Overload protection secondary circuit Overvoltage protection secondary circuit Short-circuit protection secondary circuit |
| Total useful secondary power | 50 W |
| Secondary power | 19 W 24 V DC 35 W 5 V DC |
| Current at secondary voltage | 0.8 A 24 V DC relay power supply 7 A 5 V DC |
| Insulation resistance | >= 10 mOhm primary/ground >= 10 mOhm primary/secondary |
| Marking | CE |
| Local signalling | 1 LED (green) for presence of voltages (OK) 1 LED (red) for battery fault (BAT) |
| Module format | Double |
| Product Weight | 1.96 lb(US) (0.89 kg) |
Main category name:Power Supply Sub category name:Modicon Premium Vendor:Schneider