Specifications

Model

NR-PM01

Performance Specifications

Measurement specifications

Phase wire system

1-phase 2-wire, 1-phase 3-wire, 3-phase 3-wire, 3-phase 4-wire (switchable)

No. of measurement circuits

1

Primary side rated current (In)

With dedicated NR-CT250 CT: 250 A
With dedicated NR-CT600 CT: 600 A
With dedicated NR-CT050 CT: 50 A
With dedicated NR-CT100 CT: 100 A
or general-purpose CT (secondary side rated input current 1 A)*1

Overcurrent withstand capability

1.2 times the primary side rated current (can be continuous), 10 times the primary side rated current (1 sec or less)

Rated input voltage (direct input)

1-phase 2-wire

With dedicated NR-CT250/CT600 CT: 100–277 V AC (L-N)
With dedicated NR-CT050/CT100 CT: 100–240 V AC (L-N)

1-phase 3-wire

100–240 V AC (L-N), 200–480 V AC (L-L)

3-phase 3-wire

With dedicated NR-CT250/CT600 CT: 173–480 V AC (L-L)
With dedicated NR-CT050/CT100 CT: 173–240 V AC (L-L)

3-phase 4-wire

With dedicated NR-CT250/CT600 CT: 100–277 V AC (L-N), 173–480 V AC (L-L)
With dedicated NR-CT050/CT100 CT: 100–240 V AC (L-N), 173–415 V AC (L-L)

Maximum allowable earth voltage

With dedicated NR-CT250/CT600 CT: 480 V AC
With dedicated NR-CT050/CT100 CT: 240 V AC

Input voltage fluctuation range

−15% to +15% of rated input voltage

Rated input frequency

50/60 Hz

Measurement range

Voltage

Measurable range: Within rated input voltage
Display resolution: 0.1 V

Current

Measurable range: Within primary side rated current
Display resolution: 0.001 A

Active energy/Reactive energy/Apparent energy (Instantaneous)

Measurable range: -8942.400 to +8942.400 [kW/kvar/kVA]
Display resolution: 0.001 [kW/kvar/kVA]

Active energy/Reactive energy/Apparent energy (Integrated)

Measurable range: 0.000 to 999999.999 [kWh/kvarh/kVah]
Display resolution: 0.001 [kWh/kvarh/kVAh]

Power factor (PF)

Measurable range: -1.00–1.00
Display resolution: 0.01

Frequency

Measurable range: 0.0 to 90.0 Hz
Display resolution: 0.1 Hz

Measurement accuracy

Voltage

±0.5% of rdg (within rated input voltage)*2

Current

With dedicated NR-CT250/CT600 CT: ± 0.5% of rdg (5% ≤ In ≤ 120%) and ± 1.0% of rdg (1% ≤ In ≤ 5%)
With dedicated NR-CT050/CT100 CT: ±0.5% of F.S.
*2

Active energy (power factor of 1)

±1.0% of rdg (1% ≤ In ≤ 120%)*2

Reactive energy (reactive power factor of 1)

±2.0% of rdg (5% ≤ In ≤ 120%)*2

Apparent energy

With dedicated NR-CT250/CT600 CT: ±1.0% of rdg (1% ≤ In ≤ 120%)*3
With dedicated NR-CT050/CT100 CT: ±1.0% of rdg (5% ≤ In ≤ 120%)*3
*2

Effects of ambient temperature

±0.03% of rdg/°C*4*2

Power factor (PF)

±0.01*2

Frequency

±0.1 [Hz]*2

General specifications

Power voltage

—(Powered by NR-PMC10)

Operating ambient temperature

0 to 55°C 32°F to 131°F (no freezing)

Operating ambient humidity

Max. 85% RH (no condensation)

Withstand voltage

2500 V AC/minute
• Between all terminals and case
• Between voltage measurement terminal and expansion port
• Between CT input terminal and expansion port
* With dedicated CT

Insulation resistance

20 MΩ or more at 500 V DC
• Between all terminals and case
• Between voltage measurement terminal, all CT input terminals and expansion port

Vibration

Frequency: 10 to 500 Hz; Power spectral density: 0.033 G2/Hz for X, Y and Z directions

Material

Polycarbonate

Current consumption

36 mA or less

Weight

Approx. 110 g 3.88 oz

*1 Primary side rated current: 1 to 2000 A, Secondary side rated input current: 1 A, Nominal cross-sectional area: 0.2 mm2 to 1.5 mm2 0.0003 in2 to 0.0023 in2. However, if a general-purpose CT is used, it does not meet the requirements of EU Directives or CSA certification.
*2 Values when at room temperature and rated frequency. Does not include CT precision. Only the measurement resolution may be shifted at times.
*3 This value to be used as a guideline when multiple Power Monitors are used to measure the total apparent energy.
*4 Excluding temperature fluctuations due to measured current fluctuations.

Price on request
Ask for quote
   

Notify Me When Available

Specifications

Model

NR-PM01

Performance Specifications

Measurement specifications

Phase wire system

1-phase 2-wire, 1-phase 3-wire, 3-phase 3-wire, 3-phase 4-wire (switchable)

No. of measurement circuits

1

Primary side rated current (In)

With dedicated NR-CT250 CT: 250 A
With dedicated NR-CT600 CT: 600 A
With dedicated NR-CT050 CT: 50 A
With dedicated NR-CT100 CT: 100 A
or general-purpose CT (secondary side rated input current 1 A)*1

Overcurrent withstand capability

1.2 times the primary side rated current (can be continuous), 10 times the primary side rated current (1 sec or less)

Rated input voltage (direct input)

1-phase 2-wire

With dedicated NR-CT250/CT600 CT: 100–277 V AC (L-N)
With dedicated NR-CT050/CT100 CT: 100–240 V AC (L-N)

1-phase 3-wire

100–240 V AC (L-N), 200–480 V AC (L-L)

3-phase 3-wire

With dedicated NR-CT250/CT600 CT: 173–480 V AC (L-L)
With dedicated NR-CT050/CT100 CT: 173–240 V AC (L-L)

3-phase 4-wire

With dedicated NR-CT250/CT600 CT: 100–277 V AC (L-N), 173–480 V AC (L-L)
With dedicated NR-CT050/CT100 CT: 100–240 V AC (L-N), 173–415 V AC (L-L)

Maximum allowable earth voltage

With dedicated NR-CT250/CT600 CT: 480 V AC
With dedicated NR-CT050/CT100 CT: 240 V AC

Input voltage fluctuation range

−15% to +15% of rated input voltage

Rated input frequency

50/60 Hz

Measurement range

Voltage

Measurable range: Within rated input voltage
Display resolution: 0.1 V

Current

Measurable range: Within primary side rated current
Display resolution: 0.001 A

Active energy/Reactive energy/Apparent energy (Instantaneous)

Measurable range: -8942.400 to +8942.400 [kW/kvar/kVA]
Display resolution: 0.001 [kW/kvar/kVA]

Active energy/Reactive energy/Apparent energy (Integrated)

Measurable range: 0.000 to 999999.999 [kWh/kvarh/kVah]
Display resolution: 0.001 [kWh/kvarh/kVAh]

Power factor (PF)

Measurable range: -1.00–1.00
Display resolution: 0.01

Frequency

Measurable range: 0.0 to 90.0 Hz
Display resolution: 0.1 Hz

Measurement accuracy

Voltage

±0.5% of rdg (within rated input voltage)*2

Current

With dedicated NR-CT250/CT600 CT: ± 0.5% of rdg (5% ≤ In ≤ 120%) and ± 1.0% of rdg (1% ≤ In ≤ 5%)
With dedicated NR-CT050/CT100 CT: ±0.5% of F.S.
*2

Active energy (power factor of 1)

±1.0% of rdg (1% ≤ In ≤ 120%)*2

Reactive energy (reactive power factor of 1)

±2.0% of rdg (5% ≤ In ≤ 120%)*2

Apparent energy

With dedicated NR-CT250/CT600 CT: ±1.0% of rdg (1% ≤ In ≤ 120%)*3
With dedicated NR-CT050/CT100 CT: ±1.0% of rdg (5% ≤ In ≤ 120%)*3
*2

Effects of ambient temperature

±0.03% of rdg/°C*4*2

Power factor (PF)

±0.01*2

Frequency

±0.1 [Hz]*2

General specifications

Power voltage

—(Powered by NR-PMC10)

Operating ambient temperature

0 to 55°C 32°F to 131°F (no freezing)

Operating ambient humidity

Max. 85% RH (no condensation)

Withstand voltage

2500 V AC/minute
• Between all terminals and case
• Between voltage measurement terminal and expansion port
• Between CT input terminal and expansion port
* With dedicated CT

Insulation resistance

20 MΩ or more at 500 V DC
• Between all terminals and case
• Between voltage measurement terminal, all CT input terminals and expansion port

Vibration

Frequency: 10 to 500 Hz; Power spectral density: 0.033 G2/Hz for X, Y and Z directions

Material

Polycarbonate

Current consumption

36 mA or less

Weight

Approx. 110 g 3.88 oz

*1 Primary side rated current: 1 to 2000 A, Secondary side rated input current: 1 A, Nominal cross-sectional area: 0.2 mm2 to 1.5 mm2 0.0003 in2 to 0.0023 in2. However, if a general-purpose CT is used, it does not meet the requirements of EU Directives or CSA certification.
*2 Values when at room temperature and rated frequency. Does not include CT precision. Only the measurement resolution may be shifted at times.
*3 This value to be used as a guideline when multiple Power Monitors are used to measure the total apparent energy.
*4 Excluding temperature fluctuations due to measured current fluctuations.

Model

NR-PM01

Performance Specifications

Measurement specifications

Phase wire system

1-phase 2-wire, 1-phase 3-wire, 3-phase 3-wire, 3-phase 4-wire (switchable)

No. of measurement circuits

1

Primary side rated current (In)

With dedicated NR-CT250 CT: 250 A
With dedicated NR-CT600 CT: 600 A
With dedicated NR-CT050 CT: 50 A
With dedicated NR-CT100 CT: 100 A
or general-purpose CT (secondary side rated input current 1 A)*1

Overcurrent withstand capability

1.2 times the primary side rated current (can be continuous), 10 times the primary side rated current (1 sec or less)

Rated input voltage (direct input)

1-phase 2-wire

With dedicated NR-CT250/CT600 CT: 100–277 V AC (L-N)
With dedicated NR-CT050/CT100 CT: 100–240 V AC (L-N)

1-phase 3-wire

100–240 V AC (L-N), 200–480 V AC (L-L)

3-phase 3-wire

With dedicated NR-CT250/CT600 CT: 173–480 V AC (L-L)
With dedicated NR-CT050/CT100 CT: 173–240 V AC (L-L)

3-phase 4-wire

With dedicated NR-CT250/CT600 CT: 100–277 V AC (L-N), 173–480 V AC (L-L)
With dedicated NR-CT050/CT100 CT: 100–240 V AC (L-N), 173–415 V AC (L-L)

Maximum allowable earth voltage

With dedicated NR-CT250/CT600 CT: 480 V AC
With dedicated NR-CT050/CT100 CT: 240 V AC

Input voltage fluctuation range

−15% to +15% of rated input voltage

Rated input frequency

50/60 Hz

Measurement range

Voltage

Measurable range: Within rated input voltage
Display resolution: 0.1 V

Current

Measurable range: Within primary side rated current
Display resolution: 0.001 A

Active energy/Reactive energy/Apparent energy (Instantaneous)

Measurable range: -8942.400 to +8942.400 [kW/kvar/kVA]
Display resolution: 0.001 [kW/kvar/kVA]

Active energy/Reactive energy/Apparent energy (Integrated)

Measurable range: 0.000 to 999999.999 [kWh/kvarh/kVah]
Display resolution: 0.001 [kWh/kvarh/kVAh]

Power factor (PF)

Measurable range: -1.00–1.00
Display resolution: 0.01

Frequency

Measurable range: 0.0 to 90.0 Hz
Display resolution: 0.1 Hz

Measurement accuracy

Voltage

±0.5% of rdg (within rated input voltage)*2

Current

With dedicated NR-CT250/CT600 CT: ± 0.5% of rdg (5% ≤ In ≤ 120%) and ± 1.0% of rdg (1% ≤ In ≤ 5%)
With dedicated NR-CT050/CT100 CT: ±0.5% of F.S.
*2

Active energy (power factor of 1)

±1.0% of rdg (1% ≤ In ≤ 120%)*2

Reactive energy (reactive power factor of 1)

±2.0% of rdg (5% ≤ In ≤ 120%)*2

Apparent energy

With dedicated NR-CT250/CT600 CT: ±1.0% of rdg (1% ≤ In ≤ 120%)*3
With dedicated NR-CT050/CT100 CT: ±1.0% of rdg (5% ≤ In ≤ 120%)*3
*2

Effects of ambient temperature

±0.03% of rdg/°C*4*2

Power factor (PF)

±0.01*2

Frequency

±0.1 [Hz]*2

General specifications

Power voltage

—(Powered by NR-PMC10)

Operating ambient temperature

0 to 55°C 32°F to 131°F (no freezing)

Operating ambient humidity

Max. 85% RH (no condensation)

Withstand voltage

2500 V AC/minute
• Between all terminals and case
• Between voltage measurement terminal and expansion port
• Between CT input terminal and expansion port
* With dedicated CT

Insulation resistance

20 MΩ or more at 500 V DC
• Between all terminals and case
• Between voltage measurement terminal, all CT input terminals and expansion port

Vibration

Frequency: 10 to 500 Hz; Power spectral density: 0.033 G2/Hz for X, Y and Z directions

Material

Polycarbonate

Current consumption

36 mA or less

Weight

Approx. 110 g 3.88 oz

*1 Primary side rated current: 1 to 2000 A, Secondary side rated input current: 1 A, Nominal cross-sectional area: 0.2 mm2 to 1.5 mm2 0.0003 in2 to 0.0023 in2. However, if a general-purpose CT is used, it does not meet the requirements of EU Directives or CSA certification.
*2 Values when at room temperature and rated frequency. Does not include CT precision. Only the measurement resolution may be shifted at times.
*3 This value to be used as a guideline when multiple Power Monitors are used to measure the total apparent energy.
*4 Excluding temperature fluctuations due to measured current fluctuations.

All PLC Direct products come with a 1-year warranty. The warranty is issued by PLC Direct. Warranty coverage commences at the date of purchase. The warranty is for mechanical defects or failures not caused by human factors including but not limited to (a) incorrect installation, (b) operating the unit in sub-optimal conditions or in scenarios not recommended by the manufacturer, (c) poor unit maintenance, etc. The warranty does not cover programming or software related issues.

If the product is eligible for PLC Direct’s warranty coverage and the customer encounters an issue with the product, we will request the item is shipped to us for diagnosis and examination. Regardless of the cause of product issues, the customer will bear responsibility for the cost of shipping the unit to PLC Direct for evaluation. Where the unit was damaged by human factors, we will offer a repair or replace quote; in cases where damage was caused by human factors, the customer is responsible for the cost of shipping the repaired/replaced unit from PLC Direct to the customer. Where the unit was not damaged by human factors but is covered by PLC Direct’s warranty, we will repair or replace the unit at our cost (or, in rare cases, refund you your purchase); in such cases, PLC Direct will bear the cost of shipping the repaired or replaced product back to the customer. It is up to PLC Direct’s discretion whether to repair, replace, or refund the customer in such cases. Diagnoses can take time to complete based on technician availability and the complexity of diagnosis.

In no event shall PLC Direct be liable for any damages except actual damages up to, but not exceeding, the amount paid to us for the product, including we shall not be liable for any consequential or indirect damages or lost profits whether or not advised of same.

PLC Direct offers free shipping worldwide. Product ship from a various warehouses worldwide based on the customer's and the product's location. The estimated delivery date on the product page is PLC Direct's best estimated assuming a US-based shipping destination.

Regardless of where the product is shipping from, PLC Direct covers all duties for US-based shipping destinations. For non-US-based shipping destinations, customers are responsible for duties as appropriate.

PLC Direct's focus is on balancing price with lead time. Some but not all products can be expedited. If you have questions about delivery ETAs, please contact our team.

Trusted By

"Fast service for obsolete parts"

Increasingly PLC/ HMI control platforms are becoming obsolete and parts are no longer supported, however PLC Direct had the HMI we needed and fast shipping for our system to get back online!

Buyer at GE Health

"Helping us move projects forward"

With supply chain issues increasingly affecting our business, PLC Direct has been there for us to supply the PLC products we need, when we need it. If they don't have it readily available, they find it and provide it quickly and reliably. This has helped us move forward with several projects that would have otherwise taken us many, many months to complete.

Buyer at E-Merge Systems – A Rockwell Integrator