LTMEV40FM Schneider

TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. TeSys T has a number of components that increase the flexibility of the system. This expansion module adds functionalities to the TeSys T controller. It adds voltage mesurement between phases up to 690 V nominal and 4 additional inputs. Module has 4 discrete logic inputs. 120 to 240 VAC is used to power the module. Module has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.

Main

Characteristic Value(s)
Range TeSys
product name TeSys T
Device short name LTME
Product or Component Type Extension module
Device Application Equipment monitoring and control
Range compatibility TeSys TeSys T LTMR motor controller
Supply Via the controller

Complementary

Characteristic Value(s)
[Ui] rated insulation voltage 690 V EN/IEC 60947-1
690 V CSA C22.2 No 14
690 V UL 508
[Uimp] rated impulse withstand voltage 4 kV supply, inputs and outputs EN/IEC 60947-4-1
6 kV current or voltage measurement circuit EN/IEC 60947-4-1
Logic input number 4
Input current 3.1 mA 100 V
7.5 mA 240 V
Current state 0 guaranteed Logic input 0...40 V 2...15 mA 25 ms
Current state 1 guaranteed Logic input 79...264 V <= 15 mA 25 ms
maximum output switching frequency 2 Hz
Maximum operating rate 1800 cyc/h
Contacts type and composition Without
Metering type Imbalance voltage
Active power P, P1, P2, P3
Calculated active and reactive energy (+/- W.h, +/- VAR.h)
Voltage U21, U32, U13, V1, V2, V3
Reactive power Q, Q1, Q2, Q3
Frequency
Power factor
Measurement accuracy 1 % voltage 100...830 V)
3 % power factor
5 % active and reactive power
Overvoltage category III
Connection pitch 0.20 in (5.08 mm)
Connections - terminals Control circuit connector 1 0.0004…0.004 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible with cable end
Control circuit connector 1 0.0003…0.004 in² (0.2…2.5 mm²) AWG 24...AWG 14)flexible without cable end
Control circuit connector 1 0.0004…0.004 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible without cable end
Control circuit connector 1 0.0003…0.004 in² (0.2…2.5 mm²) AWG 24...AWG 14)solid without cable end
Control circuit connector 2 0.0003…0.002 in² (0.2…1 mm²) AWG 24...AWG 14)flexible with cable end
Control circuit connector 2 0.0003…0.002 in² (0.2…1.5 mm²) AWG 24...AWG 14)flexible without cable end
Control circuit connector 2 0.0008…0.002 in² (0.5…1.5 mm²) AWG 24...AWG 14)flexible without cable end
Control circuit connector 2 0.0003…0.002 in² (0.2…1 mm²) AWG 24...AWG 14)solid without cable end
Tightening torque Control circuit: 4.4…5.3 lbf.in (0.5…0.6 N.m) flat screwdriver 0.1 in (3 mm)
pollution degree 3
Electromagnetic compatibility Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4
Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4
Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6
Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Voltage inputs: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5
Voltage inputs: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Width 1.8 in (45 mm)
Height 2.4 in (61 mm)
Depth 4.8 in (120.7 mm)
Product Weight 0.46 lb(US) (0.21 kg)
Compatibility code LTME
Est. delivery between and    
Estimated delivery dates are estimates only. Int'l customers allow a few more days. For more precise delivery estimates, please contact us at support@plc-direct.com. Contact us in advance for expedited shipping options.
Sale price5,471.00 kr
1-year warranty
FREE WORDWIDE SHIPPING
Condition:
0.00 kr
5,471.00 kr
5,042.00 kr
Ach Direct Debit American Express Apple Pay Diners Club Discover Google Pay Mastercard PayPal Shop Pay Visa

TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. TeSys T has a number of components that increase the flexibility of the system. This expansion module adds functionalities to the TeSys T controller. It adds voltage mesurement between phases up to 690 V nominal and 4 additional inputs. Module has 4 discrete logic inputs. 120 to 240 VAC is used to power the module. Module has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.

Main

Characteristic Value(s)
Range TeSys
product name TeSys T
Device short name LTME
Product or Component Type Extension module
Device Application Equipment monitoring and control
Range compatibility TeSys TeSys T LTMR motor controller
Supply Via the controller

Complementary

Characteristic Value(s)
[Ui] rated insulation voltage 690 V EN/IEC 60947-1
690 V CSA C22.2 No 14
690 V UL 508
[Uimp] rated impulse withstand voltage 4 kV supply, inputs and outputs EN/IEC 60947-4-1
6 kV current or voltage measurement circuit EN/IEC 60947-4-1
Logic input number 4
Input current 3.1 mA 100 V
7.5 mA 240 V
Current state 0 guaranteed Logic input 0...40 V 2...15 mA 25 ms
Current state 1 guaranteed Logic input 79...264 V <= 15 mA 25 ms
maximum output switching frequency 2 Hz
Maximum operating rate 1800 cyc/h
Contacts type and composition Without
Metering type Imbalance voltage
Active power P, P1, P2, P3
Calculated active and reactive energy (+/- W.h, +/- VAR.h)
Voltage U21, U32, U13, V1, V2, V3
Reactive power Q, Q1, Q2, Q3
Frequency
Power factor
Measurement accuracy 1 % voltage 100...830 V)
3 % power factor
5 % active and reactive power
Overvoltage category III
Connection pitch 0.20 in (5.08 mm)
Connections - terminals Control circuit connector 1 0.0004…0.004 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible with cable end
Control circuit connector 1 0.0003…0.004 in² (0.2…2.5 mm²) AWG 24...AWG 14)flexible without cable end
Control circuit connector 1 0.0004…0.004 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible without cable end
Control circuit connector 1 0.0003…0.004 in² (0.2…2.5 mm²) AWG 24...AWG 14)solid without cable end
Control circuit connector 2 0.0003…0.002 in² (0.2…1 mm²) AWG 24...AWG 14)flexible with cable end
Control circuit connector 2 0.0003…0.002 in² (0.2…1.5 mm²) AWG 24...AWG 14)flexible without cable end
Control circuit connector 2 0.0008…0.002 in² (0.5…1.5 mm²) AWG 24...AWG 14)flexible without cable end
Control circuit connector 2 0.0003…0.002 in² (0.2…1 mm²) AWG 24...AWG 14)solid without cable end
Tightening torque Control circuit: 4.4…5.3 lbf.in (0.5…0.6 N.m) flat screwdriver 0.1 in (3 mm)
pollution degree 3
Electromagnetic compatibility Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4
Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4
Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6
Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Voltage inputs: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5
Voltage inputs: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Width 1.8 in (45 mm)
Height 2.4 in (61 mm)
Depth 4.8 in (120.7 mm)
Product Weight 0.46 lb(US) (0.21 kg)
Compatibility code LTME
Characteristic Value(s)
[Ui] rated insulation voltage 690 V EN/IEC 60947-1
690 V CSA C22.2 No 14
690 V UL 508
[Uimp] rated impulse withstand voltage 4 kV supply, inputs and outputs EN/IEC 60947-4-1
6 kV current or voltage measurement circuit EN/IEC 60947-4-1
Logic input number 4
Input current 3.1 mA 100 V
7.5 mA 240 V
Current state 0 guaranteed Logic input 0...40 V 2...15 mA 25 ms
Current state 1 guaranteed Logic input 79...264 V <= 15 mA 25 ms
maximum output switching frequency 2 Hz
Maximum operating rate 1800 cyc/h
Contacts type and composition Without
Metering type Imbalance voltage
Active power P, P1, P2, P3
Calculated active and reactive energy (+/- W.h, +/- VAR.h)
Voltage U21, U32, U13, V1, V2, V3
Reactive power Q, Q1, Q2, Q3
Frequency
Power factor
Measurement accuracy 1 % voltage 100...830 V)
3 % power factor
5 % active and reactive power
Overvoltage category III
Connection pitch 0.20 in (5.08 mm)
Connections - terminals Control circuit connector 1 0.0004…0.004 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible with cable end
Control circuit connector 1 0.0003…0.004 in² (0.2…2.5 mm²) AWG 24...AWG 14)flexible without cable end
Control circuit connector 1 0.0004…0.004 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible without cable end
Control circuit connector 1 0.0003…0.004 in² (0.2…2.5 mm²) AWG 24...AWG 14)solid without cable end
Control circuit connector 2 0.0003…0.002 in² (0.2…1 mm²) AWG 24...AWG 14)flexible with cable end
Control circuit connector 2 0.0003…0.002 in² (0.2…1.5 mm²) AWG 24...AWG 14)flexible without cable end
Control circuit connector 2 0.0008…0.002 in² (0.5…1.5 mm²) AWG 24...AWG 14)flexible without cable end
Control circuit connector 2 0.0003…0.002 in² (0.2…1 mm²) AWG 24...AWG 14)solid without cable end
Tightening torque Control circuit: 4.4…5.3 lbf.in (0.5…0.6 N.m) flat screwdriver 0.1 in (3 mm)
pollution degree 3
Electromagnetic compatibility Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4
Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4
Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6
Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Voltage inputs: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5
Voltage inputs: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Width 1.8 in (45 mm)
Height 2.4 in (61 mm)
Depth 4.8 in (120.7 mm)
Product Weight 0.46 lb(US) (0.21 kg)
Compatibility code LTME

All PLC Direct products come with a 1-year warranty. The warranty is issued by PLC Direct. Warranty coverage commences at the date of purchase. The warranty is for mechanical defects or failures not caused by human factors including but not limited to (a) incorrect installation, (b) operating the unit in sub-optimal conditions or in scenarios not recommended by the manufacturer, (c) poor unit maintenance, etc. The warranty does not cover programming or software related issues.

If the product is eligible for PLC Direct’s warranty coverage and the customer encounters an issue with the product, we will request the item is shipped to us for diagnosis and examination. Regardless of the cause of product issues, the customer will bear responsibility for the cost of shipping the unit to PLC Direct for evaluation. Where the unit was damaged by human factors, we will offer a repair or replace quote; in cases where damage was caused by human factors, the customer is responsible for the cost of shipping the repaired/replaced unit from PLC Direct to the customer. Where the unit was not damaged by human factors but is covered by PLC Direct’s warranty, we will repair or replace the unit at our cost (or, in rare cases, refund you your purchase); in such cases, PLC Direct will bear the cost of shipping the repaired or replaced product back to the customer. It is up to PLC Direct’s discretion whether to repair, replace, or refund the customer in such cases. Diagnoses can take time to complete based on technician availability and the complexity of diagnosis.

In no event shall PLC Direct be liable for any damages except actual damages up to, but not exceeding, the amount paid to us for the product, including we shall not be liable for any consequential or indirect damages or lost profits whether or not advised of same.

PLC Direct offers free shipping worldwide. Product ship from a various warehouses worldwide based on the customer's and the product's location. The estimated delivery date on the product page is PLC Direct's best estimated assuming a US-based shipping destination.

Regardless of where the product is shipping from, PLC Direct covers all duties for US-based shipping destinations. For non-US-based shipping destinations, customers are responsible for duties as appropriate.

PLC Direct's focus is on balancing price with lead time. Some but not all products can be expedited. If you have questions about delivery ETAs, please contact our team.

Trusted By

"Fast service for obsolete parts"

Increasingly PLC/ HMI control platforms are becoming obsolete and parts are no longer supported, however PLC Direct had the HMI we needed and fast shipping for our system to get back online!

Buyer at GE Health

"Helping us move projects forward"

With supply chain issues increasingly affecting our business, PLC Direct has been there for us to supply the PLC products we need, when we need it. If they don't have it readily available, they find it and provide it quickly and reliably. This has helped us move forward with several projects that would have otherwise taken us many, many months to complete.

Buyer at E-Merge Systems – A Rockwell Integrator