LC1D150FD Schneider

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 150A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 40HP at 200 to 208VAC, 50HP at 240VAC, 100HP at 480VAC and 125HP at 600VAC three phase. When used with a 480VAC up to 250A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 300A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.

Main

Characteristic Value(s)
Range TeSys
Range of Product TeSys Deca
Product or Component Type Contactor
Device short name LC1D
Contactor application Motor control
Resistive load
Utilisation category AC-3
AC-1
AC-4
AC-3e
Poles description 3P
[Ue] rated operational voltage Power circuit <= 1000 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current 200 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
150 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
150 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage 110 V DC

Complementary

Characteristic Value(s)
Motor power kW 40 kW at 220...230 V AC 50/60 Hz (AC-3)
75 kW at 380...400 V AC 50/60 Hz (AC-3)
80 kW at 415...440 V AC 50/60 Hz (AC-3)
90 kW at 500 V AC 50/60 Hz (AC-3)
100 kW at 660...690 V AC 50/60 Hz (AC-3)
75 kW at 1000 V AC 50/60 Hz (AC-3)
22 kW at 400 V AC 50/60 Hz (AC-4)
40 kW at 220...230 V AC 50/60 Hz (AC-3e)
75 kW at 380...400 V AC 50/60 Hz (AC-3e)
80 kW at 415...440 V AC 50/60 Hz (AC-3e)
90 kW at 500 V AC 50/60 Hz (AC-3e)
100 kW at 660...690 V AC 50/60 Hz (AC-3e)
75 kW at 1000 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating 40 hp at 200/208 V AC 50/60 Hz for 3 phase motors
50 hp at 230/240 V AC 50/60 Hz for 3 phase motors
100 hp at 460/480 V AC 50/60 Hz for 3 phase motors
125 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover With
[Ith] conventional free air thermal current 200 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1660 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 1400 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 250 A 104 °F (40 °C) - 10 min for power circuit
580 A 104 °F (40 °C) - 1 min for power circuit
1200 A 104 °F (40 °C) - 10 s for power circuit
1400 A 104 °F (40 °C) - 1 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
315 A gG at <= 690 V coordination type 1 for power circuit
250 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 0.6 mOhm - Ith 200 A 50 Hz for power circuit
Power dissipation per pole 24 W AC-1
13.5 W AC-3
13.5 W AC-3e
[Ui] rated insulation voltage Power circuit 600 V CSA
Power circuit 600 V UL
Power circuit 1000 V IEC 60947-4-1
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Overvoltage category III
pollution degree 3
[Uimp] rated impulse withstand voltage 8 kV IEC 60947
Safety reliability level B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1
B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 8 Mcycles
Electrical durability 0.85 Mcycles 150 A AC-3 <= 440 V
1 Mcycles 200 A AC-1 <= 440 V
0.85 Mcycles 150 A AC-3e <= 440 V
Control circuit type DC standard
Coil technology With integral suppression device
Control circuit voltage limits 0.75...1.2 Uc (-40…131 °F (-40…55 °C)):operational DC
0.15...0.4 Uc (-40…158 °F (-40…70 °C)):drop-out DC
1...1.2 Uc (131…158 °F (55…70 °C)):operational DC
Inrush power in W 270…365 W 68 °F (20 °C))
Hold-in power consumption in W 2.4…5.1 W 68 °F (20 °C)
Operating time 20...35 ms closing
40...75 ms opening
Time constant 25 ms
Maximum operating rate 1200 cyc/h at 60 °C
Connections - terminals Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: solid without cable end
Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: flexible without cable end
Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: flexible without cable end
Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: flexible with cable end
Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: flexible with cable end
Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: solid without cable end
Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: solid without cable end
Tightening torque Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2
Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm)
Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support Rail
Plate
Price on request
Ask for quote
   

Notify Me When Available

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 150A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 40HP at 200 to 208VAC, 50HP at 240VAC, 100HP at 480VAC and 125HP at 600VAC three phase. When used with a 480VAC up to 250A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 300A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.

Main

Characteristic Value(s)
Range TeSys
Range of Product TeSys Deca
Product or Component Type Contactor
Device short name LC1D
Contactor application Motor control
Resistive load
Utilisation category AC-3
AC-1
AC-4
AC-3e
Poles description 3P
[Ue] rated operational voltage Power circuit <= 1000 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current 200 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
150 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
150 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage 110 V DC

Complementary

Characteristic Value(s)
Motor power kW 40 kW at 220...230 V AC 50/60 Hz (AC-3)
75 kW at 380...400 V AC 50/60 Hz (AC-3)
80 kW at 415...440 V AC 50/60 Hz (AC-3)
90 kW at 500 V AC 50/60 Hz (AC-3)
100 kW at 660...690 V AC 50/60 Hz (AC-3)
75 kW at 1000 V AC 50/60 Hz (AC-3)
22 kW at 400 V AC 50/60 Hz (AC-4)
40 kW at 220...230 V AC 50/60 Hz (AC-3e)
75 kW at 380...400 V AC 50/60 Hz (AC-3e)
80 kW at 415...440 V AC 50/60 Hz (AC-3e)
90 kW at 500 V AC 50/60 Hz (AC-3e)
100 kW at 660...690 V AC 50/60 Hz (AC-3e)
75 kW at 1000 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating 40 hp at 200/208 V AC 50/60 Hz for 3 phase motors
50 hp at 230/240 V AC 50/60 Hz for 3 phase motors
100 hp at 460/480 V AC 50/60 Hz for 3 phase motors
125 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover With
[Ith] conventional free air thermal current 200 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1660 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 1400 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 250 A 104 °F (40 °C) - 10 min for power circuit
580 A 104 °F (40 °C) - 1 min for power circuit
1200 A 104 °F (40 °C) - 10 s for power circuit
1400 A 104 °F (40 °C) - 1 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
315 A gG at <= 690 V coordination type 1 for power circuit
250 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 0.6 mOhm - Ith 200 A 50 Hz for power circuit
Power dissipation per pole 24 W AC-1
13.5 W AC-3
13.5 W AC-3e
[Ui] rated insulation voltage Power circuit 600 V CSA
Power circuit 600 V UL
Power circuit 1000 V IEC 60947-4-1
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Overvoltage category III
pollution degree 3
[Uimp] rated impulse withstand voltage 8 kV IEC 60947
Safety reliability level B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1
B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 8 Mcycles
Electrical durability 0.85 Mcycles 150 A AC-3 <= 440 V
1 Mcycles 200 A AC-1 <= 440 V
0.85 Mcycles 150 A AC-3e <= 440 V
Control circuit type DC standard
Coil technology With integral suppression device
Control circuit voltage limits 0.75...1.2 Uc (-40…131 °F (-40…55 °C)):operational DC
0.15...0.4 Uc (-40…158 °F (-40…70 °C)):drop-out DC
1...1.2 Uc (131…158 °F (55…70 °C)):operational DC
Inrush power in W 270…365 W 68 °F (20 °C))
Hold-in power consumption in W 2.4…5.1 W 68 °F (20 °C)
Operating time 20...35 ms closing
40...75 ms opening
Time constant 25 ms
Maximum operating rate 1200 cyc/h at 60 °C
Connections - terminals Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: solid without cable end
Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: flexible without cable end
Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: flexible without cable end
Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: flexible with cable end
Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: flexible with cable end
Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: solid without cable end
Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: solid without cable end
Tightening torque Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2
Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm)
Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support Rail
Plate
Characteristic Value(s)
Motor power kW 40 kW at 220...230 V AC 50/60 Hz (AC-3)
75 kW at 380...400 V AC 50/60 Hz (AC-3)
80 kW at 415...440 V AC 50/60 Hz (AC-3)
90 kW at 500 V AC 50/60 Hz (AC-3)
100 kW at 660...690 V AC 50/60 Hz (AC-3)
75 kW at 1000 V AC 50/60 Hz (AC-3)
22 kW at 400 V AC 50/60 Hz (AC-4)
40 kW at 220...230 V AC 50/60 Hz (AC-3e)
75 kW at 380...400 V AC 50/60 Hz (AC-3e)
80 kW at 415...440 V AC 50/60 Hz (AC-3e)
90 kW at 500 V AC 50/60 Hz (AC-3e)
100 kW at 660...690 V AC 50/60 Hz (AC-3e)
75 kW at 1000 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating 40 hp at 200/208 V AC 50/60 Hz for 3 phase motors
50 hp at 230/240 V AC 50/60 Hz for 3 phase motors
100 hp at 460/480 V AC 50/60 Hz for 3 phase motors
125 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover With
[Ith] conventional free air thermal current 200 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1660 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 1400 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 250 A 104 °F (40 °C) - 10 min for power circuit
580 A 104 °F (40 °C) - 1 min for power circuit
1200 A 104 °F (40 °C) - 10 s for power circuit
1400 A 104 °F (40 °C) - 1 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
315 A gG at <= 690 V coordination type 1 for power circuit
250 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 0.6 mOhm - Ith 200 A 50 Hz for power circuit
Power dissipation per pole 24 W AC-1
13.5 W AC-3
13.5 W AC-3e
[Ui] rated insulation voltage Power circuit 600 V CSA
Power circuit 600 V UL
Power circuit 1000 V IEC 60947-4-1
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Overvoltage category III
pollution degree 3
[Uimp] rated impulse withstand voltage 8 kV IEC 60947
Safety reliability level B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1
B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 8 Mcycles
Electrical durability 0.85 Mcycles 150 A AC-3 <= 440 V
1 Mcycles 200 A AC-1 <= 440 V
0.85 Mcycles 150 A AC-3e <= 440 V
Control circuit type DC standard
Coil technology With integral suppression device
Control circuit voltage limits 0.75...1.2 Uc (-40…131 °F (-40…55 °C)):operational DC
0.15...0.4 Uc (-40…158 °F (-40…70 °C)):drop-out DC
1...1.2 Uc (131…158 °F (55…70 °C)):operational DC
Inrush power in W 270…365 W 68 °F (20 °C))
Hold-in power consumption in W 2.4…5.1 W 68 °F (20 °C)
Operating time 20...35 ms closing
40...75 ms opening
Time constant 25 ms
Maximum operating rate 1200 cyc/h at 60 °C
Connections - terminals Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: solid without cable end
Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: flexible without cable end
Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: flexible without cable end
Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: flexible with cable end
Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: flexible with cable end
Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: solid without cable end
Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: solid without cable end
Tightening torque Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2
Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm)
Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support Rail
Plate

All PLC Direct products come with a 1-year warranty. The warranty is issued by PLC Direct. Warranty coverage commences at the date of purchase. The warranty is for mechanical defects or failures not caused by human factors including but not limited to (a) incorrect installation, (b) operating the unit in sub-optimal conditions or in scenarios not recommended by the manufacturer, (c) poor unit maintenance, etc. The warranty does not cover programming or software related issues.

If the product is eligible for PLC Direct’s warranty coverage and the customer encounters an issue with the product, we will request the item is shipped to us for diagnosis and examination. Regardless of the cause of product issues, the customer will bear responsibility for the cost of shipping the unit to PLC Direct for evaluation. Where the unit was damaged by human factors, we will offer a repair or replace quote; in cases where damage was caused by human factors, the customer is responsible for the cost of shipping the repaired/replaced unit from PLC Direct to the customer. Where the unit was not damaged by human factors but is covered by PLC Direct’s warranty, we will repair or replace the unit at our cost (or, in rare cases, refund you your purchase); in such cases, PLC Direct will bear the cost of shipping the repaired or replaced product back to the customer. It is up to PLC Direct’s discretion whether to repair, replace, or refund the customer in such cases. Diagnoses can take time to complete based on technician availability and the complexity of diagnosis.

In no event shall PLC Direct be liable for any damages except actual damages up to, but not exceeding, the amount paid to us for the product, including we shall not be liable for any consequential or indirect damages or lost profits whether or not advised of same.

PLC Direct offers free shipping worldwide. Product ship from a various warehouses worldwide based on the customer's and the product's location. The estimated delivery date on the product page is PLC Direct's best estimated assuming a US-based shipping destination.

Regardless of where the product is shipping from, PLC Direct covers all duties for US-based shipping destinations. For non-US-based shipping destinations, customers are responsible for duties as appropriate.

PLC Direct's focus is on balancing price with lead time. Some but not all products can be expedited. If you have questions about delivery ETAs, please contact our team.

Trusted By

"Fast service for obsolete parts"

Increasingly PLC/ HMI control platforms are becoming obsolete and parts are no longer supported, however PLC Direct had the HMI we needed and fast shipping for our system to get back online!

Buyer at GE Health

"Helping us move projects forward"

With supply chain issues increasingly affecting our business, PLC Direct has been there for us to supply the PLC products we need, when we need it. If they don't have it readily available, they find it and provide it quickly and reliably. This has helped us move forward with several projects that would have otherwise taken us many, many months to complete.

Buyer at E-Merge Systems – A Rockwell Integrator