FD-EPA0 Keyence

Specifications

Model

FD-EPA0

Type

Zero line type*1

Number of control outputs

*2

Number of analog outputs

Number of external inputs

*2

Power supply cable

No cable

Response time (90% response)

Flow rate

50 ms/100 ms/250 ms/1 s/5 s (selectable, initial value: 250 ms) *3

Pressure

2.5 ms/10 ms/50 ms/100 ms/250 ms/1 s/5 s (selectable, initial value: 2.5 ms) *3

I/O

Control outputs 1, 2, and 3

Instantaneous flow/Accumulated flow/Pressure/Alarm output/Predictive maintenance output/Seating Confirmation (output 1 only)/Pulse output NPN/PNP setting switchable, 100 mA or less total for three outputs, residual voltage: 2.5 V or less

Analog output

Instantaneous flow/Pressure 4-20 mA/0-20 mA (switchable), load resistance: 260 Ω or less

External inputs 1 and 2

Zero flow/Origin adjust./Atmospheric pressure correction/Pressure zero shift/Reset total/App. learning/App. reset Short-circuit current: 1.5 mA or less

Network compatibility

NU Series compatibility

Number of connectible units

Eight units per one NU1 main unit; four units per one FS-MC8N/P main unit*1

Protection circuit

Protection against incorrect head cable wiring

Power supply

Power voltage

24 VDC ± 10% (including ripple), Class2/LPS

Power consumption

1400 mW excluding load current *4

Environmental resistance

Ambient temperature

−10°C to +55°C 14 to 131°F (no freezing)*4

Relative humidity

35%RH to 85%RH (no condensation)

Vibration resistance

10 to 500 Hz, power spectral concentration: 0.816 G2/Hz, XYZ axes

Shock resistance

100 m/s2, 16 ms pulse, XYZ axes, 1000 times for each axis

Material

Main unit: polycarbonate, FG terminal: copper/iron

Weight

Approx. 26 g 0.92 oz

*1 To use the zero line type, connect it to the FS-MC8N/P, NU Series.
*2 This counts as 2 outputs/2 inputs when connecting multiple units to the FS-MC8N/P, NU Series.
*3 5 ms is added to the analog output response time and the response is set to 63%.
*4 The ambient temperature to use varies depending on the number of adjacent cable type/M12 connector type units or depending on the number of expansion zero line type units added to the system. For 1 or 2 units, the temperature is 55°C 131°F. For 3 to 5 units, the temperature is 50°C 122°F. For 6 to 8 units, the temperature is 45°C 113°F. The prescribed values for the ambient temperature assume that the amplifier unit has been mounted on a DIN rail installed on a metal surface. Exercise special care when installing the product in an airtight space.

Est. delivery between and    
Estimated delivery dates are estimates only. Int'l customers allow a few more days. For more precise delivery estimates, please contact us at support@plc-direct.com. Contact us in advance for expedited shipping options.
Sale price5,946.00 kr
1-year warranty
FREE WORDWIDE SHIPPING
Condition:
0.00 kr
5,946.00 kr
3,495.00 kr
Ach Direct Debit American Express Apple Pay Diners Club Discover Google Pay Mastercard PayPal Shop Pay Visa

Specifications

Model

FD-EPA0

Type

Zero line type*1

Number of control outputs

*2

Number of analog outputs

Number of external inputs

*2

Power supply cable

No cable

Response time (90% response)

Flow rate

50 ms/100 ms/250 ms/1 s/5 s (selectable, initial value: 250 ms) *3

Pressure

2.5 ms/10 ms/50 ms/100 ms/250 ms/1 s/5 s (selectable, initial value: 2.5 ms) *3

I/O

Control outputs 1, 2, and 3

Instantaneous flow/Accumulated flow/Pressure/Alarm output/Predictive maintenance output/Seating Confirmation (output 1 only)/Pulse output NPN/PNP setting switchable, 100 mA or less total for three outputs, residual voltage: 2.5 V or less

Analog output

Instantaneous flow/Pressure 4-20 mA/0-20 mA (switchable), load resistance: 260 Ω or less

External inputs 1 and 2

Zero flow/Origin adjust./Atmospheric pressure correction/Pressure zero shift/Reset total/App. learning/App. reset Short-circuit current: 1.5 mA or less

Network compatibility

NU Series compatibility

Number of connectible units

Eight units per one NU1 main unit; four units per one FS-MC8N/P main unit*1

Protection circuit

Protection against incorrect head cable wiring

Power supply

Power voltage

24 VDC ± 10% (including ripple), Class2/LPS

Power consumption

1400 mW excluding load current *4

Environmental resistance

Ambient temperature

−10°C to +55°C 14 to 131°F (no freezing)*4

Relative humidity

35%RH to 85%RH (no condensation)

Vibration resistance

10 to 500 Hz, power spectral concentration: 0.816 G2/Hz, XYZ axes

Shock resistance

100 m/s2, 16 ms pulse, XYZ axes, 1000 times for each axis

Material

Main unit: polycarbonate, FG terminal: copper/iron

Weight

Approx. 26 g 0.92 oz

*1 To use the zero line type, connect it to the FS-MC8N/P, NU Series.
*2 This counts as 2 outputs/2 inputs when connecting multiple units to the FS-MC8N/P, NU Series.
*3 5 ms is added to the analog output response time and the response is set to 63%.
*4 The ambient temperature to use varies depending on the number of adjacent cable type/M12 connector type units or depending on the number of expansion zero line type units added to the system. For 1 or 2 units, the temperature is 55°C 131°F. For 3 to 5 units, the temperature is 50°C 122°F. For 6 to 8 units, the temperature is 45°C 113°F. The prescribed values for the ambient temperature assume that the amplifier unit has been mounted on a DIN rail installed on a metal surface. Exercise special care when installing the product in an airtight space.

Model

FD-EPA0

Type

Zero line type*1

Number of control outputs

*2

Number of analog outputs

Number of external inputs

*2

Power supply cable

No cable

Response time (90% response)

Flow rate

50 ms/100 ms/250 ms/1 s/5 s (selectable, initial value: 250 ms) *3

Pressure

2.5 ms/10 ms/50 ms/100 ms/250 ms/1 s/5 s (selectable, initial value: 2.5 ms) *3

I/O

Control outputs 1, 2, and 3

Instantaneous flow/Accumulated flow/Pressure/Alarm output/Predictive maintenance output/Seating Confirmation (output 1 only)/Pulse output NPN/PNP setting switchable, 100 mA or less total for three outputs, residual voltage: 2.5 V or less

Analog output

Instantaneous flow/Pressure 4-20 mA/0-20 mA (switchable), load resistance: 260 Ω or less

External inputs 1 and 2

Zero flow/Origin adjust./Atmospheric pressure correction/Pressure zero shift/Reset total/App. learning/App. reset Short-circuit current: 1.5 mA or less

Network compatibility

NU Series compatibility

Number of connectible units

Eight units per one NU1 main unit; four units per one FS-MC8N/P main unit*1

Protection circuit

Protection against incorrect head cable wiring

Power supply

Power voltage

24 VDC ± 10% (including ripple), Class2/LPS

Power consumption

1400 mW excluding load current *4

Environmental resistance

Ambient temperature

−10°C to +55°C 14 to 131°F (no freezing)*4

Relative humidity

35%RH to 85%RH (no condensation)

Vibration resistance

10 to 500 Hz, power spectral concentration: 0.816 G2/Hz, XYZ axes

Shock resistance

100 m/s2, 16 ms pulse, XYZ axes, 1000 times for each axis

Material

Main unit: polycarbonate, FG terminal: copper/iron

Weight

Approx. 26 g 0.92 oz

*1 To use the zero line type, connect it to the FS-MC8N/P, NU Series.
*2 This counts as 2 outputs/2 inputs when connecting multiple units to the FS-MC8N/P, NU Series.
*3 5 ms is added to the analog output response time and the response is set to 63%.
*4 The ambient temperature to use varies depending on the number of adjacent cable type/M12 connector type units or depending on the number of expansion zero line type units added to the system. For 1 or 2 units, the temperature is 55°C 131°F. For 3 to 5 units, the temperature is 50°C 122°F. For 6 to 8 units, the temperature is 45°C 113°F. The prescribed values for the ambient temperature assume that the amplifier unit has been mounted on a DIN rail installed on a metal surface. Exercise special care when installing the product in an airtight space.

All PLC Direct products come with a 1-year warranty. The warranty is issued by PLC Direct. Warranty coverage commences at the date of purchase. The warranty is for mechanical defects or failures not caused by human factors including but not limited to (a) incorrect installation, (b) operating the unit in sub-optimal conditions or in scenarios not recommended by the manufacturer, (c) poor unit maintenance, etc. The warranty does not cover programming or software related issues.

If the product is eligible for PLC Direct’s warranty coverage and the customer encounters an issue with the product, we will request the item is shipped to us for diagnosis and examination. Regardless of the cause of product issues, the customer will bear responsibility for the cost of shipping the unit to PLC Direct for evaluation. Where the unit was damaged by human factors, we will offer a repair or replace quote; in cases where damage was caused by human factors, the customer is responsible for the cost of shipping the repaired/replaced unit from PLC Direct to the customer. Where the unit was not damaged by human factors but is covered by PLC Direct’s warranty, we will repair or replace the unit at our cost (or, in rare cases, refund you your purchase); in such cases, PLC Direct will bear the cost of shipping the repaired or replaced product back to the customer. It is up to PLC Direct’s discretion whether to repair, replace, or refund the customer in such cases. Diagnoses can take time to complete based on technician availability and the complexity of diagnosis.

In no event shall PLC Direct be liable for any damages except actual damages up to, but not exceeding, the amount paid to us for the product, including we shall not be liable for any consequential or indirect damages or lost profits whether or not advised of same.

PLC Direct offers free shipping worldwide. Product ship from a various warehouses worldwide based on the customer's and the product's location. The estimated delivery date on the product page is PLC Direct's best estimated assuming a US-based shipping destination.

Regardless of where the product is shipping from, PLC Direct covers all duties for US-based shipping destinations. For non-US-based shipping destinations, customers are responsible for duties as appropriate.

PLC Direct's focus is on balancing price with lead time. Some but not all products can be expedited. If you have questions about delivery ETAs, please contact our team.

Trusted By

"Fast service for obsolete parts"

Increasingly PLC/ HMI control platforms are becoming obsolete and parts are no longer supported, however PLC Direct had the HMI we needed and fast shipping for our system to get back online!

Buyer at GE Health

"Helping us move projects forward"

With supply chain issues increasingly affecting our business, PLC Direct has been there for us to supply the PLC products we need, when we need it. If they don't have it readily available, they find it and provide it quickly and reliably. This has helped us move forward with several projects that would have otherwise taken us many, many months to complete.

Buyer at E-Merge Systems – A Rockwell Integrator