This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.2S accuracy per IEC 62053-22 standard and 128 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to the 63rd Harmonic. Include 1.1 MegaBytes of memory for up to 14 selectable parameters with configurable interval and duration. This meter also feature the direct monitoring of neutral current. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 480 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 20 to 690 VAC at 45 to 65 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 45 to 65 Hz. Communication protocol are Modbus RTU and ASCII 2 wires with RS485 port support plus Modbus TCP/IP, Ethernet/IP and BACnet/IP based on 10/100 Mbit/s, daisy chain Ethernet with RJ45 port support. The embedded communication capabilities allow the support of the DNP 3.0 protocol, the access to an onboard web server and a Serial to Ethernet gateway. The meter also has four digital inputs with WAGES support and two digital outputs. There are 52 configurable alarms and it supports eight tariff schedules. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 3.03 inches (77 millimetres), height 3.78 inches (96 millimetres) and product weight 15.9 onces (450 g).
Main
| Characteristic | Value(s) |
|---|---|
| Range | PowerLogic |
| product name | PowerLogic PM5000 |
| Device short name | PM5560 |
| Product or Component Type | Power meter |
Complementary
| Characteristic | Value(s) |
|---|---|
| Power quality analysis | up to the 63rd harmonic |
| Metering type | Measured neutral current Calculated ground current |
| Device Application | Gateway WAGES metering Power monitoring Multi-tariff |
| Type of measurement | Current Voltage Frequency Power factor Energy Active and reactive power |
| supply voltage | 100...300 V DC 90...528 V AC 45...65 Hz |
| Network Frequency | 60 Hz 50 Hz |
| Line Rated Current | 1 A 5 A |
| type of network | 3P + N 3P 1P + N |
| Maximum power consumption in VA | 16 VA 480 V |
| Ride-through time | 35 ms 120 V AC typical 129 ms 230 V AC typical 50 ms 125 V DC typical |
| Display Type | Backlit LCD |
| Display Resolution | 128 x 128 pixels |
| Sampling rate | 128 samples/cycle |
| Measurement current | 50â¦10000 mA |
| Analogue input type | Voltage (impedance 5 MOhm) Current (impedance <= 0.3 mOhm) |
| Measurement voltage | 20â¦400 V AC 45...65 Hz between phase and neutral 20â¦828 V AC 45...65 Hz between phases |
| Frequency measurement range | 45â¦65 Hz |
| Number of inputs | 4 digital |
| Measurement accuracy | Apparent power +/- 0.5 % Frequency +/- 0.05 % Active energy +/- 0.2 % Reactive energy +/- 1 % Active power +/- 0.2 % Voltage +/- 0.1 % Power factor +/- 0.005 Current +/- 0.15 % Reactive power +/- 1 % |
| Accuracy class | Class 0.2S active energy IEC 62053-22 |
| Number of Outputs | 2 digital |
| Information displayed | Tariff 8) |
| Communication port protocol | Modbus RTU and ASCII 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires 2500 V JBUS Modbus TCP/IP 10/100 Mbit/s 2500 V Ethernet Modbus TCP/IP daisy chain BACnet IP DNP3 over ethernet |
| Communication port support | RS485 ETHERNET |
| Communication gateway | Ethernet/serial |
| Data recording | Event logs Maintenance logs Min/max of instantaneous values Data logs Alarm logs Time stamping |
| Memory capacity | 1.1 MB |
| Web services | Alarm notification by e-mail Diagnostic via predefined web pages Web server Real time viewing of data |
| Ethernet service | SNTP client SNMP-Traps |
| Connections - terminals | Voltage circuit screw terminal block4 Control circuit screw terminal block2 Current transformer screw terminal block6 RS485 link screw terminal block4 Digital input screw terminal block8 Digital output screw terminal block4 Ethernet network RJ45 connector2 |
| Mounting Mode | Flush-mounted |
| Mounting support | Framework |
| Standards | EN 50470-3 IEC 61557-12:2015 IEC 62053-22:2020 IEC 62053-24 IEC 60529 EN 50470-1 UL 61010-1 ANSI C12.20 IEC 62053-23:2020 IEC 62052-11:2020 IEC 62052-31:2015 |
| Product certifications | CE conforming to IEC 61010-1 CULus conforming to UL 61010-1 BTL |
| Width | 3.8 in (96 mm) |
| Depth | 2.8 in (72 mm) |
| Height | 3.8 in (96 mm) |
| Product Weight | 15.9 oz (450 g) |
All PLC Direct products come with a 1-year warranty. The warranty is issued by PLC Direct. Warranty coverage commences at the date of purchase. The warranty is for mechanical defects or failures not caused by human factors including but not limited to (a) incorrect installation, (b) operating the unit in sub-optimal conditions or in scenarios not recommended by the manufacturer, (c) poor unit maintenance, etc. The warranty does not cover programming or software related issues.
If the product is eligible for PLC Direct’s warranty coverage and the customer encounters an issue with the product, we will request the item is shipped to us for diagnosis and examination. Regardless of the cause of product issues, the customer will bear responsibility for the cost of shipping the unit to PLC Direct for evaluation. Where the unit was damaged by human factors, we will offer a repair or replace quote; in cases where damage was caused by human factors, the customer is responsible for the cost of shipping the repaired/replaced unit from PLC Direct to the customer. Where the unit was not damaged by human factors but is covered by PLC Direct’s warranty, we will repair or replace the unit at our cost (or, in rare cases, refund you your purchase); in such cases, PLC Direct will bear the cost of shipping the repaired or replaced product back to the customer. It is up to PLC Direct’s discretion whether to repair, replace, or refund the customer in such cases. Diagnoses can take time to complete based on technician availability and the complexity of diagnosis.
In no event shall PLC Direct be liable for any damages except actual damages up to, but not exceeding, the amount paid to us for the product, including we shall not be liable for any consequential or indirect damages or lost profits whether or not advised of same.
PLC Direct offers free shipping worldwide. Product ship from a various warehouses worldwide based on the customer's and the product's location. The estimated delivery date on the product page is PLC Direct's best estimated assuming a US-based shipping destination.
Regardless of where the product is shipping from, PLC Direct covers all duties for US-based shipping destinations. For non-US-based shipping destinations, customers are responsible for duties as appropriate.
PLC Direct's focus is on balancing price with lead time. Some but not all products can be expedited. If you have questions about delivery ETAs, please contact our team.


"Fast service for obsolete parts"
Increasingly PLC/ HMI control platforms are becoming obsolete and parts are no longer supported, however PLC Direct had the HMI we needed and fast shipping for our system to get back online!
Buyer at GE Health

"Helping us move projects forward"
With supply chain issues increasingly affecting our business, PLC Direct has been there for us to supply the PLC products we need, when we need it. If they don't have it readily available, they find it and provide it quickly and reliably. This has helped us move forward with several projects that would have otherwise taken us many, many months to complete.
Buyer at E-Merge Systems – A Rockwell Integrator