This Phaseo ABL1 regulated switch mode power supply (SMPS) supplies direct current voltage. It has a rated input of 100V to 120V AC or 200 to 240V AC, a rated output current of 6.2A at 24V DC and a rated power of 150W. It is ideal for supplying DC voltage necessary for automation equipment designed for applications in industrial, commercial and residential applications such as conveying, packaging, control, food & beverage, mining, oil & gas and water. Automatic reset allows short-term faults to be cleared and systems to restart without the need to disturb on-duty maintenance engineers. It has LED diagnostics indicator available in the front for troubleshooting instantly. Its width is 200mm, its height is 98mm, its depth is 50mm. It weighs 0.970kg. It is certified with TUV 60950-1, UL 508, CCSAus, EAC, CSA 22-2 No 60950-1 and RCM. It is a power supply for commercial use, panel mount; It is compatible with reversible mounting bracket type ABL1A01 and ABL1A02 clip-on mounting plate. It installs on panel with reversible mounting bracket or mounting plate fixing by screw. ABL1 power supplies bring energy to your automated systems. ABL1 power supplies are designed for simple and repetitive machines, dedicated power supplies are particularly quality/price competitive due to their simplicity and compactness. The main applications to use Phaseo ABL1 power supply are lifts, display panels, escalators, carwash, foodstuff ovens, etc.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Phaseo Dedicated |
| Product or Component Type | Power supply |
| Power supply type | Regulated switch mode |
| Kw Rating | 150 W |
| Main Input Voltage | 100...120 V AC single phase 200...240 V AC single phase 180...370 V DC |
| Output voltage | 24 V DC |
| Power supply output current | 6.2 A |
| Operating position | Any position |
| Vibration resistance | 2 gn (f= 9â¦150 Hz) conforming to EN/IEC 61131-2 3.5 mm (f= 5â¦9 Hz) conforming to EN/IEC 61131-2 |
| Name of test | Conducted interference conforming to EN 61000-4-8 level 4 Electrostatic discharges conforming to EN/IEC 61000-4-2 level 3 Induced electromagnetic field conforming to EN/IEC 61000-4-6 level 3 Radiated electromagnetic field conforming to EN/IEC 61000-4-3 level 3 Rapid transient conforming to IEC 61000-4-4 level 3 Conducted/radiated emissions conforming to EN 55022 Class B Conducted/radiated emissions conforming to EN/IEC 55011 Emission conforming to EN/IEC 61000-6-3 Primary outage conforming to IEC 61000-4-11 Surge conforming to EN/IEC 61000-4-5 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Input voltage limits | 85...132 V 170...264 V |
| Network Frequency | 47...63 Hz |
| Inrush current | 50 A at 115 V AC 100 A at 230 V AC |
| Cos phi | 0.7â¦0.95 |
| Efficiency | 80 % |
| Power dissipation in W | 37.5 W |
| Current consumption | 5 A at 100 V 2.5 A at 240 V |
| Input protection type | Integrated fuse (not interchangeable) |
| Output voltage limits | 21.6...26.4 V |
| Line and load regulation | +/- 3 % |
| Holding time | >= 10 ms at 100 V >= 40 ms at 240 V |
| Output protection type | Against overload, protection technology: 1.1...1.5 x In Against overvoltage, protection technology: tripping if U > 1.25 x Un Against short-circuits, protection technology: automatic reset Thermal |
| Connections - terminals | For ground connection: screw type terminals, connection capacity: 1 x 4 mm² AWG 12 For input connection: screw type terminals, connection capacity: 2 x 4 mm² AWG 12 For output connection: screw type terminals, connection capacity: 4 x 4 mm² AWG 12 |
| Marking | CE |
| Mounting Support | Reversible mounting bracket Panel |
| Operating altitude | 6561.68 ft (2000 m) |
| Output coupling | Series Parallel |
| Overvoltage category | II |
| Meantime between failure [MTBF] | 100000 h at 104 °F (40 °C) |
| Status LED | 1 LED (Green) output voltage |
| Product Weight | 2.14 lb(US) (0.97 kg) |