TeSys GV motor circuit breaker, 3 poles (3P), 150A/690V, for protection of 3-phase motors 55-75kW@400V. It provides thermal magnetic protection and additional protections, breaking capacity Icu 70kA, start-stop control by rotary handle, connection for bars or cables with lugs (direct connection of cables with additional connectors). Thermal protection adjustable by dials with a setting current Ir in range 70-150A and a selectable tripping class 5, 10 or 20, magnetic protection at 15 In. Additional protections with fixed pick-up include short time delay protection Isd at 13 Ir, phase unbalance and loss protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine).
Main
| Characteristic | Value(s) |
|---|---|
| Range of product | TeSys GV5 |
| Range | TeSys |
| Device short name | GV5P |
| product name | TeSys GV5 TeSys Giga |
| Product or component type | Motor circuit breaker |
| Device application | Motor protection |
| Trip unit technology | Electronic |
Complementary
| Characteristic | Value(s) |
|---|---|
| Poles description | 3P |
| Utilisation category | Category A conforming to IEC 60947-2 |
| Motor power kW | 55â¦75 kW at 400/415 V AC 50/60 Hz 75â¦90 kW at 500 V AC 50/60 Hz 90â¦110 kW at 660/690 V AC 50/60 Hz |
| Breaking capacity | 70 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| control type | Direct rotary handle |
| [In] rated current | 150 A at 65 °C |
| Magnetic tripping current | 2250 A |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ith] conventional free air thermal current | 150 A conforming to IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Power dissipation per pole | 9.2 W |
| Mechanical durability | 40000 cycles |
| Electrical durability | 20000 cycles for AC-3 at 400/415 V In |
| Maximum operating rate | 25 cyc/h |
| Rated duty | Continuous |
| Connection pitch | 35 mm without spreaders |
| Connections - terminals | Bars Lugs |
| Tightening torque | 15 N.m M8 screw type |
| Mechanical robustness | Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Height | 161 mm |
| Width | 105 mm |
| Depth | 155 mm |
| Product weight | 2.4 kg |
| Colour | Anthracite (RAL 7016) |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |



TeSys GV motor circuit breaker, 3 poles (3P), 50A/690V, for protection of 3-phase motors 11-22kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 25kA@400V, start-stop control by rotary handle, connection for bars or cables with lugs. Thermal protection adjustable by dials with a setting current Ir in range 20-50A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | TeSys GV4 |
| Range | TeSys Deca |
| Device short name | GV4P |
| product name | TeSys GV4 |
| Product or Component Type | Motor circuit breaker |
| Device Application | Motor protection |
| Trip unit technology | Thermal-magnetic Electronic |
Complementary
| Characteristic | Value(s) |
|---|---|
| Poles description | 3P |
| Utilisation category | Category A IEC 60947-2 AC-3 IEC 60947-4-1 |
| Operating position | Any position |
| Motor power kW | 11 kW 400...415 V AC 50/60 Hz 15 kW 500 V AC 50/60 Hz 18.5 kW 660...690 V AC 50/60 Hz 15 kW 400...415 V AC 50/60 Hz 18.5 kW 400...415 V AC 50/60 Hz 22 kW 400...415 V AC 50/60 Hz 18.5 kW 500 V AC 50/60 Hz 22 kW 500 V AC 50/60 Hz 30 kW 500 V AC 50/60 Hz 22 kW 660...690 V AC 50/60 Hz 30 kW 660...690 V AC 50/60 Hz 37 kW 660...690 V AC 50/60 Hz 45 kW 660...690 V AC 50/60 Hz |
| Breaking capacity | 50 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 25 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 35 kA 208Y/120 V AC 50/60 Hz UL 60947 35 kA 240 V AC 50/60 Hz UL 60947 18 kA 480Y/277 V AC 50/60 Hz UL 60947 14 kA 600Y/347 V AC 50/60 Hz UL 60947 |
| Control Type | Rotary handle |
| Line Rated Current | 50 A |
| Magnetic tripping current | 850 A |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz IEC 60947-2 |
| [Ith] conventional free air thermal current | 115 A IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 8 kV IEC 60947-2 |
| Power dissipation per pole | 4.6 W |
| Mechanical durability | 40000 cycles |
| Electrical durability | 20000 cycles AC-3 440 V In/2 10000 cycles AC-3 440 V In |
| Maximum operating rate | 25 cyc/h |
| Rated duty | Continuous IEC 60947-4-1 |
| Connection pitch | 1.06 in (27 mm) without spreaders 1.4 in (35 mm) with spreaders |
| Connections - terminals | Lugs-ring terminals |
| Tightening torque | 79.7 lbf.in (9 N.m) 0.02â¦0.1 in² (16â¦95 mm²) 44.3 lbf.in (5 N.m) 0.002â¦0.02 in² (1.5â¦10 mm²) |
| Mechanical robustness | Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27 |
| Phase failure sensitivity | Yes IEC 60947-4-1 |
| Height | 6.1 in (155 mm) |
| Width | 3.2 in (81 mm) |
| Depth | 6.5 in (165 mm) |
| Product Weight | 3.5 lb(US) (1.6 kg) |
| color | Gray RAL 7016) |
| Suitability for isolation | Yes IEC 60947-1 |

TeSys GV motor circuit breaker, 3 poles (3P), 3.5A/690V, for protection of 3-phase motors 0.55-1.5kW@400V. Multifunction circuit breaker, it provides thermal magnetic protection and advanced motor protection, breaking capacity Icu 50kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 1.4-3.5A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Advanced protections are adjustable with a smartphone using wireless NFC and include short time delay protection Isd with a setting range 5-13 Ir, phase unbalance and loss protection, ground fault protection, locked rotor (jam), long start. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). It can be equiped externally with 1 or 2 auxiliary SDx modules in order to have alarming and fault differentiation. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX).
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | TeSys GV4 |
| Range | TeSys Deca |
| Device short name | GV4PEM |
| product name | TeSys GV4 |
| Product or Component Type | Motor circuit breaker |
| Device Application | Motor protection |
| Trip unit technology | Thermal-magnetic Electronic |
Complementary
| Characteristic | Value(s) |
|---|---|
| Poles description | 3P |
| Utilisation category | Category A IEC 60947-2 AC-3 IEC 60947-4-1 |
| Operating position | Any position |
| Motor power kW | 0.55 kW 400...415 V AC 50/60 Hz 0.75 kW 400...415 V AC 50/60 Hz 0.75 kW 500 V AC 50/60 Hz 1.1 kW 500 V AC 50/60 Hz 1.1 kW 660...690 V AC 50/60 Hz 1.5 kW 660...690 V AC 50/60 Hz 1.5 kW 500 V AC 50/60 Hz 2.2 kW 660...690 V AC 50/60 Hz 1.1 kW 400...415 V AC 50/60 Hz 1.5 kW 400...415 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 65 kA 208Y/120 V AC 50/60 Hz UL 60947 65 kA 240 V AC 50/60 Hz UL 60947 35 kA 480Y/277 V AC 50/60 Hz UL 60947 8 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA 600Y/347 V AC 50/60 Hz UL 60947 |
| Control Type | Toggle |
| Line Rated Current | 3.5 A |
| Magnetic tripping current | 59 A |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz IEC 60947-2 |
| [Ith] conventional free air thermal current | 115 A IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 8 kV IEC 60947-2 |
| Power dissipation per pole | 4.6 W |
| Mechanical durability | 40000 cycles |
| Electrical durability | 40000 cycles AC-3 440 V In/2 40000 cycles AC-3 440 V In |
| Maximum operating rate | 25 cyc/h |
| Rated duty | Continuous IEC 60947-4-1 |
| Connections - terminals | EverLink BTR screw connectors top) 1 0.002â¦0.1 in² (1.5â¦70 mm²) - solid EverLink BTR screw connectors top) 1 0.002â¦0.08 in² (1.5â¦50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004â¦0.1 in² (2.5â¦95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004â¦0.1 in² (2.5â¦70 mm²) - flexible |
| Tightening torque | 79.7 lbf.in (9 N.m) 0.02â¦0.1 in² (16â¦95 mm²) 44.3 lbf.in (5 N.m) 0.002â¦0.02 in² (1.5â¦10 mm²) |
| Mechanical robustness | Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27 |
| Phase failure sensitivity | Yes IEC 60947-4-1 |
| Height | 6.1 in (155 mm) |
| Width | 3.2 in (81 mm) |
| Depth | 4.6 in (116 mm) |
| Product Weight | 3.20 lb(US) (1.45 kg) |
| color | Gray RAL 7016) |
| Suitability for isolation | Yes IEC 60947-1 |

TeSys GV motor circuit breaker, 3 poles (3P), 25A/690V, for 3-phase motor applications 11kW@400V. It provides a thermal-magnetic protection with a thermal setting range 20-25A, magnetic tripping at 13xIn, high breaking capacity Icu 15kA@400V. Connection by lugs. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX),
Main
| Characteristic | Value(s) |
|---|---|
| Range | TeSys Deca |
| product name | TeSys GV2 |
| Product or component type | Motor circuit breaker |
| Device short name | GV2ME |
| Device application | Motor protection |
| Trip unit technology | Thermal-magnetic |
Complementary
| Characteristic | Value(s) |
|---|---|
| Poles description | 3P |
| Network type | AC |
| Utilisation category | Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Motor power kW | 11 kW at 400/415 V AC 50/60 Hz 15 kW at 500 V AC 50/60 Hz |
| Breaking capacity | 50 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 40 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| control type | Push-button |
| [In] rated current | 25 A |
| Thermal protection adjustment range | 20â¦25 A conforming to IEC 60947-2 |
| Magnetic tripping current | 388.3 A |
| [Ith] conventional free air thermal current | 25 A conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Power dissipation per pole | 2.5 W |
| Mechanical durability | 100000 cycles |
| Electrical durability | 100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In |
| Rated duty | Uninterrupted conforming to IEC 60947-4-1 |
| Connections - terminals | Power circuit: lugs-ring terminals 2 cable(s) 1â¦6 mm²solid Power circuit: lugs-ring terminals 2 cable(s) 1.5â¦6 mm²flexible without cable end Power circuit: lugs-ring terminals 2 cable(s) 1â¦4 mm²flexible with cable end |
| Tightening torque | 1.7 N.m - on screw clamp terminal |
| Fixing mode | 35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate) |
| Mounting position | Horizontal Vertical |
| Width | 45 mm |
| Height | 89 mm |
| Depth | 78.5 mm |
| Product weight | 0.26 kg |
| Colour | Dark grey |
| Connection pitch | 13.5 mm without spreader |

TeSys GV motor circuit breaker, 3 poles (3P), 50A/690V, for protection of 3-phase motors 11-22kW@400V. Multifunction circuit breaker, it provides thermal magnetic protection and advanced motor protection, breaking capacity Icu 25kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 20-50A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Advanced protections are adjustable with a smartphone using wireless NFC and include short time delay protection Isd with a setting range 5-13 Ir, phase unbalance and loss protection, ground fault protection, locked rotor (jam), long start. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). It can be equiped externally with 1 or 2 auxiliary SDx modules in order to have alarming and fault differentiation. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | TeSys GV4 |
| Range | TeSys Deca |
| Device short name | GV4PEM |
| product name | TeSys GV4 |
| Product or Component Type | Motor circuit breaker |
| Device Application | Motor protection |
| Trip unit technology | Thermal-magnetic Electronic |
Complementary
| Characteristic | Value(s) |
|---|---|
| Poles description | 3P |
| Utilisation category | Category A IEC 60947-2 AC-3 IEC 60947-4-1 |
| Operating position | Any position |
| Motor power kW | 11 kW 400...415 V AC 50/60 Hz 15 kW 500 V AC 50/60 Hz 18.5 kW 660...690 V AC 50/60 Hz 15 kW 400...415 V AC 50/60 Hz 18.5 kW 400...415 V AC 50/60 Hz 22 kW 400...415 V AC 50/60 Hz 18.5 kW 500 V AC 50/60 Hz 22 kW 500 V AC 50/60 Hz 30 kW 500 V AC 50/60 Hz 22 kW 660...690 V AC 50/60 Hz 30 kW 660...690 V AC 50/60 Hz 37 kW 660...690 V AC 50/60 Hz 45 kW 660...690 V AC 50/60 Hz |
| Breaking capacity | 50 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 25 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 35 kA 208Y/120 V AC 50/60 Hz UL 60947 35 kA 240 V AC 50/60 Hz UL 60947 18 kA 480Y/277 V AC 50/60 Hz UL 60947 14 kA 600Y/347 V AC 50/60 Hz UL 60947 |
| Control Type | Toggle |
| Line Rated Current | 50 A |
| Magnetic tripping current | 850 A |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz IEC 60947-2 |
| [Ith] conventional free air thermal current | 115 A IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 8 kV IEC 60947-2 |
| Power dissipation per pole | 4.6 W |
| Mechanical durability | 40000 cycles |
| Electrical durability | 20000 cycles AC-3 440 V In/2 10000 cycles AC-3 440 V In |
| Maximum operating rate | 25 cyc/h |
| Rated duty | Continuous IEC 60947-4-1 |
| Connections - terminals | EverLink BTR screw connectors top) 1 0.002â¦0.1 in² (1.5â¦70 mm²) - solid EverLink BTR screw connectors top) 1 0.002â¦0.08 in² (1.5â¦50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004â¦0.1 in² (2.5â¦95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004â¦0.1 in² (2.5â¦70 mm²) - flexible |
| Tightening torque | 79.7 lbf.in (9 N.m) 0.02â¦0.1 in² (16â¦95 mm²) 44.3 lbf.in (5 N.m) 0.002â¦0.02 in² (1.5â¦10 mm²) |
| Mechanical robustness | Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27 |
| Phase failure sensitivity | Yes IEC 60947-4-1 |
| Height | 6.1 in (155 mm) |
| Width | 3.2 in (81 mm) |
| Depth | 4.6 in (116 mm) |
| Product Weight | 3.20 lb(US) (1.45 kg) |
| color | Gray RAL 7016) |
| Suitability for isolation | Yes IEC 60947-1 |

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.


TeSys Deca motor thermal magnetic circuit breaker GV2ME, push button (control), thermal outlet range: 2.5-4 A, screw clamp terminals

TeSys GV electrical trip, MX shunt release, 220-240V AC 60Hz, for motor circuit breakers GV2, GV3. It trips the circuit breaker when the control voltage is applied in limits 0.7-1.1 Uc with an impulse duration greater than 20ms or a maintained signal. To be mounted on right-hand side of the circuit breaker, connection by screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC).
Main
| Characteristic | Value(s) |
|---|---|
| Range | TeSys TeSys Deca |
| Product or Component Type | Shunt trip release |
| Device short name | GVAS |
Complementary
| Characteristic | Value(s) |
|---|---|
| Range compatibility | TeSys GV2ME TeSys GV2LE TeSys GV2L TeSys GV2P TeSys GV3L TeSys GV3P TeSys Deca |
| [Uc] control circuit voltage | 220...240 V AC 60 Hz |
| Control circuit voltage limits | 0.7...1.1 Un |
| [Ui] rated insulation voltage | 690 V AC IEC 60947-1 600 V AC UL 60947-4-1 600 V AC CSA C22.2 No 60947-4-1 |
| Threshold tripping voltage | 0.75...0.2 Un |
| Inrush power in VA | 14 VA AC |
| Inrush power in W | 10.5 W |
| Hold-in Power Consumption in VA | 5 VA AC |
| Hold-in power consumption in W | 1.6 W |
| Operating time | 10...15 ms IEC 60947-1 |
| On-load factor | 100 % |
| Connections - terminals | screw clamp terminals 1 0.002â¦0.004 in² (1â¦2.5 mm²)solid screw clamp terminals 2 0.002â¦0.004 in² (1â¦2.5 mm²)solid screw clamp terminals 1 0.001â¦0.004 in² (0.75â¦2.5 mm²)flexible without cable end screw clamp terminals 2 0.001â¦0.004 in² (0.75â¦2.5 mm²)flexible without cable end screw clamp terminals 1 0.001â¦0.002 in² (0.75â¦1.5 mm²)flexible with cable end screw clamp terminals 2 0.001â¦0.002 in² (0.75â¦1.5 mm²)flexible with cable end |
| Tightening torque | < 1.4 N.m screw clamp terminals |
| Mechanical durability | 10000 cycles with GV3P and GV3L 30000 cycles with GV2ME and GV2P |
| Quantity per Set | Set of 10 |
| Height | 3.5 in (89 mm) |
| Width | 0.7 in (18 mm) |
| Depth | 2.6 in (66 mm) |
| Product Weight | 0.231 lb(US) (0.105 kg) |
| color | Dark grey |

Main
| Characteristic | Value(s) |
|---|---|
| Range | TeSys |
| Device short name | GV2AP |
| Product or component type | Rotary handle kit |
| Accessory / separate part category | Control accessory |
| Handle colour | Black |
| Handle front plate colour | Black |
Complementary
| Characteristic | Value(s) |
|---|---|
| Product compatibility | GV2L GV2P |
| Rotary handle mounting style | Extended |
| Locking options description | 1 to 3 padlocks |
| Back/door distance | 150â¦290 mm |
| Product weight | 0.104 kg |

TeSys GV auxiliary contact block, for motor circuit breakers GV2 and GV3. 1C/O contact for short circuit signaling. Rated for operation up to 2A/240V AC and 1A/60V DC. To be installed on left-hand side of the circuit breaker (1 block mounting maximum), connection by screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC).
Main
| Characteristic | Value(s) |
|---|---|
| Range | TeSys TeSys Deca |
| Device short name | GVAM |
| Product or Component Type | Auxiliary contact block |
| Product Compatibility | GV2L GV2ME GV2RT GV3L GV2P GV3P GV2LE |
| Mounting Location | Left side |
| Auxiliary contacts operation | Short-circuit signal 1 C/O |
| Pole contact composition | 1 C/O |
Complementary
| Characteristic | Value(s) |
|---|---|
| [Ui] rated insulation voltage | 690 V IEC 60947-1 300 V UL 508 300 V CSA C22.2 No 14 |
| [Ue] rated operational voltage | 24...240 V AC 24...60 V DC |
| [Ith] conventional free air thermal current | 2.5 A for fault signalling |
| Mechanical durability | 100000 cycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Protection type | GB2CB... circuit breaker GG fuse 10 A |
| Rated operational power in VA | 36 VA 24 V AC-14 1000 cycles 1.5 A 48 VA 48 V AC-14 1000 cycles 1 A 72 VA 110â¦127 V AC-14 1000 cycles 0.5 A 72 VA 230â¦240 V AC-14 1000 cycles 0.3 A |
| Rated operational power in W | 120 W 240 V DC-13 100000 cycles 140 W 110 V DC-13 100000 cycles 140 W 24 V DC-13 100000 cycles 180 W 60 V DC-13 100000 cycles 240 W 48 V DC-13 100000 cycles 15 W 48 V DC-13 1000 cycles 24 W 24 V DC-13 1000 cycles 9 W 60 V DC-13 1000 cycles |
| Tightening torque | 12.4 lbf.in (1.4 N.m) screw clamp terminals |
| Height | 3.5 in (89 mm) |
| Width | 0.4 in (9.3 mm) |
| Depth | 2.6 in (66 mm) |
| Product Weight | 0.121 lb(US) (0.055 kg) |
| color | Dark grey |