TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. TeSys T has a number of components that increase the flexibility of the system. This expansion module adds functionalities to the TeSys T controller. It adds voltage mesurement between phases up to 690 V nominal and 4 additional inputs. Module has 4 discrete logic inputs. 120 to 240 VAC is used to power the module. Module has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
Main
| Characteristic | Value(s) |
|---|---|
| Range | TeSys |
| product name | TeSys T |
| Device short name | LTME |
| Product or Component Type | Extension module |
| Device Application | Equipment monitoring and control |
| Range compatibility | TeSys TeSys T LTMR motor controller |
| Supply | Via the controller |
Complementary
| Characteristic | Value(s) |
|---|---|
| [Ui] rated insulation voltage | 690 V EN/IEC 60947-1 690 V CSA C22.2 No 14 690 V UL 508 |
| [Uimp] rated impulse withstand voltage | 4 kV supply, inputs and outputs EN/IEC 60947-4-1 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 |
| Logic input number | 4 |
| Input current | 3.1 mA 100 V 7.5 mA 240 V |
| Current state 0 guaranteed | Logic input 0...40 V 2...15 mA 25 ms |
| Current state 1 guaranteed | Logic input 79...264 V <= 15 mA 25 ms |
| maximum output switching frequency | 2 Hz |
| Maximum operating rate | 1800 cyc/h |
| Contacts type and composition | Without |
| Metering type | Imbalance voltage Active power P, P1, P2, P3 Calculated active and reactive energy (+/- W.h, +/- VAR.h) Voltage U21, U32, U13, V1, V2, V3 Reactive power Q, Q1, Q2, Q3 Frequency Power factor |
| Measurement accuracy | 1 % voltage 100...830 V) 3 % power factor 5 % active and reactive power |
| Overvoltage category | III |
| Connection pitch | 0.20 in (5.08 mm) |
| Connections - terminals | Control circuit connector 1 0.0004â¦0.004 in² (0.25â¦2.5 mm²) AWG 24...AWG 14)flexible with cable end Control circuit connector 1 0.0003â¦0.004 in² (0.2â¦2.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 1 0.0004â¦0.004 in² (0.25â¦2.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 1 0.0003â¦0.004 in² (0.2â¦2.5 mm²) AWG 24...AWG 14)solid without cable end Control circuit connector 2 0.0003â¦0.002 in² (0.2â¦1 mm²) AWG 24...AWG 14)flexible with cable end Control circuit connector 2 0.0003â¦0.002 in² (0.2â¦1.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 2 0.0008â¦0.002 in² (0.5â¦1.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 2 0.0003â¦0.002 in² (0.2â¦1 mm²) AWG 24...AWG 14)solid without cable end |
| Tightening torque | Control circuit: 4.4â¦5.3 lbf.in (0.5â¦0.6 N.m) flat screwdriver 0.1 in (3 mm) |
| pollution degree | 3 |
| Electromagnetic compatibility | Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5 Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 Voltage inputs: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 Voltage inputs: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 |
| Width | 1.8 in (45 mm) |
| Height | 2.4 in (61 mm) |
| Depth | 4.8 in (120.7 mm) |
| Product Weight | 0.46 lb(US) (0.21 kg) |
| Compatibility code | LTME |

This Micrologic 2.3 is a 3 poles 3d electronic trip unit used on Compact NSX 400/630 circuit breakers. This 400A rating electronic trip unit is an optimum choice for all standard and specific applications. It embeds an adjustable long time protection against overloads. It provides also an adjustable short-time protection and a fixed instantaneous protection against short-circuits. Micrologic 2.3 indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.
Main
| Characteristic | Value(s) |
|---|---|
| Range | ComPact |
| Range of Product | ComPact NSX400...630 |
| Product or Component Type | Trip unit |
| Trip unit name | MicroLogic 2.3 |
| Trip unit technology | Electronic |
| Range Compatibility | ComPact NSX400 ComPact NSX630 |
| Device Application | Distribution |
| Number of poles | 3P |
| Protected poles description | 3t |
| Trip unit protection functions | LSoI |
| Protection type | L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection |
| Trip unit rated current | 400 A 104 °F (40 °C) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network Frequency | 50/60 Hz |
Complementary
| Characteristic | Value(s) |
|---|---|
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 160...400 A |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 11 s 7.2 x Ir 16 s 6 x Ir 400 s 1.5 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| [tsd] Short-time protection delay adjustment range | 0.02 s |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 4800 A |
| Earth-leakage protection | Without |
| Zone selective interlocking ZSI | Without |
| Local signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |

This Harmony RM22-UA relay allows monitoring of voltage control in single phase networks. This modular multi function single phase voltage control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market slim form-factors with 22.5mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a diagnostic button, sealable cover, simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Harmony Control Relays |
| Relay Type | Voltage control relay |
| Product or Component Type | Voltage control relay |
| Phase | 1 phase |
| Supply circuit type | DC |
| Relay name | RM22UA |
| Relay monitored parameters | Undervoltage and overvoltage in window mode Overvoltage or undervoltage detection |
| time delay | Adjustable 0.1...30 s, +/- 10 % of the full scale value Tt- time delay upon fault |
| Switching capacity in VA | 2000 VA |
| Measurement range | 15...500 V AC/DC |
| Contacts type and composition | 2 C/O |
Complementary
| Characteristic | Value(s) |
|---|---|
| Reset time | 1500 ms at maximum voltage |
| Maximum switching voltage | 250 V AC |
| Minimum switching current | 10 mA 5 V DC |
| Maximum switching current | 8 A AC |
| Supply voltage limits | 20.4â¦264 V AC/DC |
| Power consumption in VA | 3.5 VA AC |
| Maximum power consumption in W | 1.5 W DC |
| Immunity to microbreaks | 10 ms |
| Resistance across terminals | 150 kOhm E2-M terminals 300 kOhm E1-M terminals 500 kOhm E3-M terminals |
| Output contacts | 2 C/O |
| nominal output current | 8 A |
| Hysteresis | 3 % fixed full scale for window mode 5â¦50 % adjustable threshold setting |
| delay at power up | 600 ms |
| Maximum measuring cycle | 100 ms measurement cycle as true rms value |
| Repeat accuracy | +/- 0.5 % input and measurement circuit +/- 2 % time delay |
| Measurement error | < 1 % over the whole range with voltage variation 0.05 %/°C with temperature variation |
| Response time | <= 500 ms |
| Insulation resistance | > 100 MOhm 500 V DC |
| Overvoltage category | III conforming to IEC 60664-1 |
| Insulation | Between supply and measurement |
| Connections - terminals | Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end Screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end |
| Tightening torque | 5.3â¦8.9 lbf.in (0.6â¦1 N.m) IEC 60947-1 |
| Housing material | Self-extinguishing plastic |
| Mounting support | 35 mm DIN rail conforming to IEC 60715 |
| Electrical durability | 100000 cycles |
| Mechanical durability | 10000000 cycles |
| Utilisation category | AC-15 IEC 60947-5-1 DC-13 IEC 60947-5-1 AC-1 IEC 60947-4-1 DC-1 IEC 60947-4-1 |
| [Un] rated nominal voltage | 24...240 V AC/DC 50/60 Hz, non self-powered |
| Safety reliability data | MTTFd = 308.2 years B10d = 290000 |
| Contacts material | Cadmium free |
| Control Type | With test button |
| Width | 0.9 in (22.5 mm) |
| Product Weight | 0.24 lb(US) (0.11 kg) |

circuit breaker Compact NSXm F (36 kA at 415 VAC), 3P, 80 A rating TMD trip unit, compression lugs and busbar connectors

Main
| Characteristic | Value(s) |
|---|---|
| Range of product | Modicon TSX Micro automation platform |
| Product or component type | Analog output module |
| Number of channels | 4 |
| Analogue output type | +/- 10 V 0...10 V |
Complementary
| Characteristic | Value(s) |
|---|---|
| Analog/digital conversion | 11 bits 0...10 V 11 bits + sign +/- 10 V |
| Response time | 400 µs |
| Output load | >= 2 Ohm |
| Protection type | Short-circuit |
| Temperature drift | 0.096 %/10 °C |
| Current consumption | 90 mA |
| Isolation voltage | 1000 V AC |
| Product weight | 0.2 kg |

TeSys Deca instantaneous auxiliary contact block, for LC.D contactors and CAD control relays with AC coils only. It provides 1NO+1NC contacts (NC mirror certified) rated up to 10A 690V AC, connection by screw clamp terminals. Clip-on side mounting, it procures high reliability and durability. TeSys Deca contactors have been designed for perfect integration into control systems. Multi standards certified (IEC, UL, CSA, CCC, EAC). TeSys Deca contactors offer quick simple setup, while maintaining a compact size. Contactors have both horsepower and Kw motor rating for international acceptance. An extennsive line of accessories makes it easy to meet the requirements of most applications. These contactors have UL, CSA, GOST, RINA, BV, CCC, DNV, GL, LROS certifications.
Main
| Characteristic | Value(s) |
|---|---|
| Range | TeSys |
| product name | TeSys Deca |
| Product or Component Type | Auxiliary contact block |
| Range compatibility | TeSys Deca LC1D09â¦95 AC coil TeSys Deca LC1D115/150 TeSys Deca LC1D40Aâ¦80A AC Coil TeSys Deca CAD AC coil TeSys F LC1F |
| Mounting Location | Side |
| Pole contact composition | 1 NO + 1 NC |
| Contacts operation | Instantaneous |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ie] rated operational current | 6 A at 120 V AC-15 1.04 A at 690 V AC-15 0.55 A at 125 V DC-13 0.1 A at 600 V DC-13 |
| [Ui] rated insulation voltage | 690 V IEC 60947-5-1 600 V UL 600 V CSA |
| [Ith] conventional free air thermal current | 10 A (at 140 °F (60 °C)) |
| Standards | EN/IEC 60947-5-1 UL 60947-5-1 CSA C22.2 No 60947-5-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ |
| Product Certifications | CB Scheme UL CSA CCC EAC UKCA |
Complementary
| Characteristic | Value(s) |
|---|---|
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1 250 A DC conforming to IEC 60947-5-1 |
| Permissible short-time rating | 100 A 1 s 120 A 500 ms 140 A 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 30 Mcycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | screw clamp terminals 1 0.002â¦0.006 in² (1â¦4 mm²)flexible with cable end screw clamp terminals 1 0.002â¦0.006 in² (1â¦4 mm²)flexible without cable end screw clamp terminals 2 0.002â¦0.004 in² (1â¦2.5 mm²)flexible with cable end screw clamp terminals 2 0.002â¦0.006 in² (1â¦4 mm²)flexible without cable end screw clamp terminals 1 0.002â¦0.006 in² (1â¦4 mm²)rigid without cable end screw clamp terminals 2 0.002â¦0.006 in² (1â¦4 mm²)rigid without cable end |
| Tightening torque | 15.05 lbf.in (1.7 N.m) flat à 6 mm 15.05 lbf.in (1.7 N.m) Philips No 2 15.05 lbf.in (1.7 N.m) pozidriv No 2 |
| Height | 3.0 in (76 mm) |
| Width | 0.5 in (12.5 mm) |
| Depth | 3.0 in (76 mm) |

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.


| Product | |
| Article Number (Market Facing Number) | 6BK16301BA000AA0 | 6BK16301BA000AA0 |
| Product Description | SIMATIC MICRO-DRIVE PDC1000, drive controller for servo drives in the extra low voltage range, 24 up to 48 V CS power supply of the operating mechanism, motor output max. 1000 W |
| Product family | Not available |
| Product Lifecycle (PLM) | PM300:Active Product |
| Additional Product Information | |
| EAN | 4034106439439 |
| UPC | 195125068551 |
| Commodity Code | 85044095 |
| LKZ_FDB/ CatalogID | ST80.1 |
| Product Group | 4B71 |
| Group Code | R220 |
| Country of origin | Germany |
| SCIP number | f98fbdbe-1d96-4777-b4d4-e3d854c80f23 |
| Delivery information | |
| Net Weight (lb) | 1.433 lb |
| Package size unit of measure | Inch |
| Packaging Quantity | 1 |

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

| Product | |
| Article Number (Market Facing Number) | C73451A430D84 | C73451-A430-D84 |
| Product Description | Potentiometer assembly for SIPART PS2 |
| Product family | Ordering Data Overview |
| Product Lifecycle (PLM) | PM300:Active Product |
| Additional Product Information | |
| EAN | Not available |
| UPC | Not available |
| Commodity Code | 8543700000 |
| LKZ_FDB/ CatalogID | FI01 |
| Product Group | X0KJ |
| Group Code | R3P3 |
| Country of origin | Mexico |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 0.099 lb |
| Package size unit of measure | Not available |
| Packaging Quantity | 1 |

| Product | |
| Article Number (Market Facing Number) | 3RR22412FW30 | 3RR22412FW30 |
| Product Description | Monitoring relay, can be mounted to Contactor 3RT2, Size S00 standard, digitally adjustable Apparant/active current monitoring 1.6-16 A, 20-400 Hz, 3-phase Supply 24-240 V AC/DC 1 change-over contact, 1 semiconductor output for alarm and warning Monitoring for Current overshoot and undershoot Phase failure, Cable break Phase sequence Residual current Blocking current Warning and alarm thresholds with or without fault buffer ON delay 0-99 s Noise pulse suppression 0-30 s Pause after fault 0-300 min spring-type connection system |
| Product family | Current and active current monitoring |
| Product Lifecycle (PLM) | PM300:Active Product |
| Additional Product Information | |
| EAN | 4011209787360 |
| UPC | 662643908664 |
| Commodity Code | 85364900 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Product Group | 5343 |
| Group Code | R711 |
| Country of origin | Czech Republic |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 0.534 lb |
| Package size unit of measure | Inch |
| Packaging Quantity | 1 |

| Product | |
| Article Number (Market Facing Number) | 3TK28261CW30 | 3TK28261CW30 |
| Product Description | !!! Phased-out product !!! The successor product series is 3SK2 (see FAQ 109741483) SIRIUS safety relay with relay enabling circuits (EC) 24...240 V UC, 45 mm overall width screw terminal EC instantaneous: 4 NO EC delayed: 0 SC: 2 Switch with 8 functions Basic device Maximum achievable PL according to EN 13849-1: Maximum achievable SIL according to IEC 61508: 3 |
| Product family | Not available |
| Product Lifecycle (PLM) | PM490:Start of final year of support |
| Additional Product Information | |
| EAN | 4011209674219 |
| UPC | 754554946450 |
| Commodity Code | 85364900 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Product Group | 5837 |
| Group Code | R711 |
| Country of origin | Germany |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 0.904 lb |
| Package size unit of measure | Inch |
| Packaging Quantity | 1 |

| Product | |
| Article Number (Market Facing Number) | 48DC38AA4 | US2:48DC38AA4 |
| Product Description | * 30 AMP OVERLOAD |
| Product family | Not available |
| Product Lifecycle (PLM) | PM490:Start of final year of support |
| Additional Product Information | |
| EAN | Not available |
| UPC | 783087084049 |
| Commodity Code | 8536490080 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Product Group | 4645 |
| Group Code | R711 |
| Country of origin | Mexico |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 1.058 lb |
| Package size unit of measure | Inch |
| Packaging Quantity | 1 |

| Product | |
| Article Number (Market Facing Number) | 6DL11936GA000NN0 | 6DL11936GA000NN0 |
| Product Description | SIMATIC ET 200SP HA, carrier module 2-fold carrier for holding 2 I/O modules of the ET 200SP HA |
| Product family | Ordering Data Overview |
| Product Lifecycle (PLM) | PM300:Active Product |
| Additional Product Information | |
| EAN | 4047622424032 |
| UPC | Not available |
| Commodity Code | 85389099 |
| LKZ_FDB/ CatalogID | STPCS7 |
| Product Group | 4D85 |
| Group Code | R336 |
| Country of origin | Germany |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 0.661 lb |
| Package size unit of measure | Inch |
| Packaging Quantity | 1 |

| Product | |
| Article Number (Market Facing Number) | 6FM17064AA00 |
| Product Description | Analog module for WF 706 for operation of 3 axles, with 4 analog outputs |
| Product family | Not available |
| Product Lifecycle (PLM) | PM500:Discontinued Product or end of PLM & Support |
| Additional Product Information | |
| EAN | Not available |
| UPC | Not available |
| Commodity Code | 85389091 |
| LKZ_FDB/ CatalogID | AR90 |
| Product Group | 9320 |
| Group Code | R2S1 |
| Country of origin | Germany |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 0.057 lb |
| Package size unit of measure | Not available |
| Packaging Quantity | 1 |