| Product | |
| Article Number (Market Facing Number) | 3TK28242BB40 | 3TK28242BB40 |
| Product Description | SIRIUS safety relay with relay enabling circuits (EC) 24 V DC, 22.5 mm Spring-type terminal EC instantaneous: 2 NO EC delayed: 0 NO SC: 0 NC AUTOSTART Basic device Maximum achieved SIL: 1, PL: c |
| Product family | Not available |
| Product Lifecycle (PLM) | PM490:Start of final year of support |
| Additional Product Information | |
| EAN | 4011209445291 |
| UPC | 754554653440 |
| Commodity Code | 85364900 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Product Group | 5837 |
| Group Code | R711 |
| Country of origin | Germany |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 0.518 lb |
| Package size unit of measure | Inch |
| Packaging Quantity | 1 |

| Product | |
| Article Number (Market Facing Number) | 3RV20114AA20 | 3RV20114AA20 |
| Product Description | Circuit breaker size S00 for motor protection, CLASS 10 A-release 10...16 A N-release 208 A Spring-type terminal Standard switching capacity |
| Product family | SIRIUS 3RV2 motor starter protectors |
| Product Lifecycle (PLM) | PM300:Active Product |
| Additional Product Information | |
| EAN | 4011209724402 |
| UPC | 662643924244 |
| Commodity Code | 85362010 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Product Group | 5332 |
| Group Code | R711 |
| Country of origin | Germany |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 0.838 lb |
| Package size unit of measure | Inch |
| Packaging Quantity | 1 |

| Product | |
| Article Number (Market Facing Number) | 3RV10414MA10 | 3RV10414MA10 |
| Product Description | Circuit breaker size S3 for motor protection, Class 10 A-release 80...100 A Short-circuit release 1235 A Screw terminal Standard switching capacity !!! Phased-out product !!! Successor is SIRIUS 3RV2 Preferred successor type is >>3RV2041-4MA10<< |
| Product family | Not available |
| Product Lifecycle (PLM) | PM490:Start of final year of support |
| Additional Product Information | |
| EAN | 4011209299764 |
| UPC | 754554409443 |
| Commodity Code | 85362090 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Product Group | 3717 |
| Group Code | R711 |
| Country of origin | Germany |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 5.022 lb |
| Package size unit of measure | Inch |
| Packaging Quantity | 1 |

| Product | |
| Article Number (Market Facing Number) | 3RV20414MA15 | 3RV20414MA15 |
| Product Description | Circuit breaker size S3 for motor protection, CLASS 10 A-release 80...100 A N-release 1300 A screw terminal Standard switching capacity with transverse auxiliary switches 1 NO+1 NC |
| Product family | SIRIUS 3RV2 motor starter protectors |
| Product Lifecycle (PLM) | PM300:Active Product |
| Additional Product Information | |
| EAN | 4047621013985 |
| UPC | 804766472718 |
| Commodity Code | 85362090 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Product Group | 3673 |
| Group Code | R711 |
| Country of origin | Germany |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 5.053 lb |
| Package size unit of measure | Inch |
| Packaging Quantity | 1 |

| Product | |
| Article Number (Market Facing Number) | 3TX70021BB00 | 3TX70021BB00 |
| Product Description | Output coupling link Phased-out product !!! For further information, please contact our sales department Relay coupler, Screw terminals 1 change-over contact, 24 V AC/DC |
| Product family | Not available |
| Product Lifecycle (PLM) | PM490:Start of final year of support |
| Additional Product Information | |
| EAN | 4011209055179 |
| UPC | 754554203706 |
| Commodity Code | 85364190 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Product Group | 5815 |
| Group Code | R711 |
| Country of origin | Czech Republic |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 0.088 lb |
| Package size unit of measure | Inch |
| Packaging Quantity | 1 |

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

| Product | |
| Article Number (Market Facing Number) | 7ME69101AA301AA0 | 7ME69101AA301AA0 |
| Product Description | MAG 5000, IP67 / NEMA 4X/6, Polyamid enclosure, With display, 11-30V DC/11-24V AC 50/60 Hz Successor product available. Please consider ordering the product SITRANS FMT020. If you need assistance please contact your Siemens sales representative. |
| Product family | SITRANS FM MAG 5000 and 6000 |
| Product Lifecycle (PLM) | PM400:Announcement of product phase-out |
| Additional Product Information | |
| EAN | 4019169842174 |
| UPC | Not available |
| Commodity Code | 9026900000 |
| LKZ_FDB/ CatalogID | FI01-3 |
| Product Group | 4835 |
| Group Code | R3P3 |
| Country of origin | France |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 1.830 lb |
| Package size unit of measure | Inch |
| Packaging Quantity | 1 |

| Product | |
| Article Number (Market Facing Number) | 7ME69201AA301AA0 | 7ME69201AA301AA0 |
| Product Description | MAG 6000, IP67 / NEMA 4X/6, Polyamid enclosure, With display, 11-30V DC/11-24V AC 50/60 Hz Successor product available. Please consider ordering the product SITRANS FMT020. If you need assistance please contact your Siemens sales representative. |
| Product family | SITRANS FM MAG 5000 and 6000 |
| Product Lifecycle (PLM) | PM400:Announcement of product phase-out |
| Additional Product Information | |
| EAN | 4019169842198 |
| UPC | Not available |
| Commodity Code | 9026900000 |
| LKZ_FDB/ CatalogID | FI01-3 |
| Product Group | 4835 |
| Group Code | R3P3 |
| Country of origin | France |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 1.830 lb |
| Package size unit of measure | Inch |
| Packaging Quantity | 1 |

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

| Product | |
| Article Number (Market Facing Number) | 6ED10521HB080BA2 | 6ED10521HB080BA2 |
| Product Description | LOGO! 24RCE, logic module,display power supply / I/O: 24 V AC/24 V DC/relay, 8 DI/4 DO, memory 400 blocks, modularly expandable, Ethernet, integrated web server, data log, user-defined web pages, standard microSD card for LOGO! Soft Comfort V8.4 or higher, older projects executable cloud connection, MQTT in all LOGO! 8.4 basic units |
| Product family | LOGO! basic modules with display |
| Product Lifecycle (PLM) | PM300:Active Product |
| Additional Product Information | |
| EAN | 4034106034443 |
| UPC | 195125492486 |
| Commodity Code | 85371091 |
| LKZ_FDB/ CatalogID | STLOGO! |
| Product Group | 4071 |
| Group Code | R131 |
| Country of origin | China |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 0.591 lb |
| Package size unit of measure | Inch |
| Packaging Quantity | 1 |

This soft starter can feed 3-phase asynchronous motors in supply line or delta connection. It has a rating of 32A and 230V to 440V, a rated power up to 15kW (400V to 440V in supply line) and up to 22kW (400V to 440V in motor delta connection). It is designed for simple and complex machines such as centrifugal and piston pumps, fans, screw compressors and material handling equipment. Slim form factor improves versatility; allows mounting in frames of any kind of machines. It features an Integrated bypass, this reduces noise and decreases heat dissipation. Compatibility with SoMove software allows configurations and settings to be easily transferred, meaning spares can be quickly installed. It provides smooth starting for your machinery, avoiding mechanical stresses and extending their service life.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Altistart 22 |
| Product or Component Type | Soft starter |
| Product destination | Asynchronous motors |
| Product Specific Application | Pumps and fans |
| Component name | ATS22 |
| Phase | 3 phase |
| [Us] rated supply voltage | 230...440 V - 15...10 % |
| Motor power kW | 15 kW 400 V 15 kW 440 V 7.5 kW 230 V |
| Factory setting current | 28.5 A |
| Power dissipation in W | 44 W for standard applications |
| Utilisation category | AC-53A |
| Type of start | Start with torque control (current limited to 3.5 In) |
| IcL starter rating | 32 A connection in the motor supply line for standard applications |
| IP Degree of Protection | IP20 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Assembly style | With heat sink |
| Function Available | Internal bypass |
| Supply voltage limits | 195â¦484 V |
| Supply frequency | 50...60 Hz - 10...10 % |
| Network Frequency | 45...66 Hz |
| Device connection | In the motor supply line To the motor delta terminals |
| [Uc] control circuit voltage | 230 V - 15...10 % 50/60 Hz |
| Control circuit consumption | 20 W |
| Discrete output number | 2 |
| Discrete output type | Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O |
| Minimum switching current | 100 mA 12 V DC relay outputs) |
| Maximum switching current | 5 A 250 V AC resistive 1 relay outputs 5 A 30 V DC resistive 1 relay outputs 2 A 250 V AC inductive 0.4 20 ms relay outputs 2 A 30 V DC inductive 7 ms relay outputs |
| Discrete input number | 3 |
| Discrete input type | LI1, LI2, LI3) logic, 5 mA 4.3 kOhm |
| Discrete input voltage | 24 V <= 30 V |
| Discrete input logic | Positive logic LI1, LI2, LI3 < 5 V <= 2 mA > 11 V, >= 5 mA |
| Output current | 0.4...1 Icl adjustable |
| PTC probe input | 750 Ohm |
| Communication Port Protocol | Modbus |
| Connector Type | 1 RJ45 |
| Communication data link | Serial |
| Physical interface | RS485 multidrop |
| Transmission Rate | 4800, 9600 or 19200 bps |
| Installed device | 31 |
| Protection type | Phase failure line Thermal protection motor Thermal protection starter |
| Marking | CE |
| type of cooling | Forced convection |
| Operating position | Vertical +/- 10 degree |
| Height | 10.4 in (265 mm) |
| Width | 5.1 in (130 mm) |
| Depth | 6.7 in (169 mm) |
| Product Weight | 15.4 lb(US) (7 kg) |
| Motor power range AC-3 | 7â¦11 kW 200â¦240 V 3 phase 15â¦25 kW 380â¦440 V 3 phase |
| Motor starter type | Soft starter |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Premium Automation platform |
| Product or Component Type | Discrete input module |
| Discrete input number | 32 current sink isolated EN/IEC 61131-2 type 1 |
| Discrete input voltage | 24 V DC positive |
| Sensor power supply | 19â¦30 V |
| Discrete input current | 3.5 mA |
Complementary
| Characteristic | Value(s) |
|---|---|
| Voltage state 1 guaranteed | >= 11 V |
| Current state 1 guaranteed | >= 3 mA |
| Voltage state 0 guaranteed | <= 5 V |
| Current state 0 guaranteed | <= 1.5 mA |
| Input impedance | 6300 Ohm at state 1 |
| Response Time | <= 7 ms 4 ms |
| isalotion resistance | < 10 MOhm 500 V DC |
| Power dissipation | (1 W + 0.1 W x No of channels used) |
| Electrical Connection | HE-10 connector |
| Marking | CE |
| Current consumption | 135 mA 5 V DC 160 mA 24 V DC |
| Module format | Standard |
| Product Weight | 0.7 lb(US) (0.3 kg) |

This Schneider Electric Altivar CANopen daisy chain communication module has 2 ports with RJ45 connectors. It complies with CANopen Daisy Chain communications protocol. This communication module enables integration of your drive in your CANopen daisy chain process control network. It is simple to install and remove from Altivar drives thanks to its modular withdrawable design. It is compatible with Altivar Process ATV600 (ATV630, ATV650)Altivar Process ATV900 (ATV930, ATV950), Altivar Machine ATV320, Lexium 32, Altivar 32, and Altivar Machine ATV340. Removable module allows last minute decisions on drive communication protocol, facilitates installation project management.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Altivar |
| Product or Component Type | Communication module |
| Accessory / separate part category | Communication accessories |
Complementary
| Characteristic | Value(s) |
|---|---|
| Product Compatibility | Lexium 32M |
| Range compatibility | Altivar 32 Altivar Machine ATV320 Altivar Machine ATV340 except Sercos drives Lexium 32 Altivar Process Modular Altivar Process ATV900 Altivar Process ATV600 |
| Communication Port Protocol | CANopen, CANmotion |
| Electrical connection | 2 connectors RJ45 |

This ComPacT NSX100H is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 70kA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds a 25A rating thermal-magnetic trip unit (TMD). TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection. This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX100H is part of Schneider Electric EcoStruxure Power architecture.
Main
| Characteristic | Value(s) |
|---|---|
| Range | ComPacT |
| product name | ComPacT NSX |
| Device short name | NSX100H |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3D |
| [In] rated current | 25 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| [Icu] rated ultimate short-circuit breaking capacity | 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1 |
| Performance level | H 70 kA 415 V AC |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit protection functions | LI |
| control type | Toggle |
| Circuit breaker mounting mode | Fixed |
Complementary
| Characteristic | Value(s) |
|---|---|
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ics] rated service short-circuit breaking capacity | 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 50000 cycles |
| Electrical durability | 50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In |
| Power dissipation per pole | 4.01 W |
| Mounting support | Backplate |
| Mounting position | Horizontal and vertical Flat on the back |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 35 mm |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Trip unit rating | 25 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 120â¦400 s at 1.5 x In 15 s at 6 x Ir |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 300 A |
| Earth-leakage protection | Without |
| Number of slots for electrical auxiliaries | 5 slot(s) |
| Width (W) | 105 mm |
| Height (H) | 161 mm |
| Depth (D) | 86 mm |
| Product weight | 2.05 kg |

This safety relay is designed for monitoring Emergency stop, Guard switch, Magnetic switch, Proximity safety switch, PNP, NPN sensors, RFID safety switch, Safety light curtain or Sensing mat/edges. The safety relay is powered with 48-240V AC/DC, and equipped with a screw removable terminal block. This universal safety module embeds pre-defined safety functions, or selectable safety functions via rotary selectors. This safety relay embeds 2 safety inputs, 3 ON/OFF configurable pulsed outputs, 2 NO, 1 NC safety outputs, and 1 solid state diagnostic output with complete status information. The maximum safety level achieved by this safety relay is PLe/Category 4 conforming to ISO 13849-1, SILC L 3 conforming to IEC 62061, and SIL 3 conforming to IEC 61508. This safety relay weighs 0,200kg. Its dimensions are 22,5mm (Width) x 120mm (Depth) x 100mm (Height). This safety relay weighs 0,200kg. Its dimensions are 22,5mm (Width) x 120mm (Depth) x 100mm (Height). This safety relays is suitable for applications such as Food and Beverage, Hoisting, Material Handling, Material Working, Packaging. This safe relay conforms to IEC60947-5-1, IEC61508-1/2/3, ISO13849-1, IEC62061 functional safety standards, is certified by cULus, TÃV, EAC, CCC and KC marking. Harmony safety relays are compatible with Modicon logic controllers. This relay is mounted on a 35mm symmetrical DIN rail. Harmony XPS Basic and Universal safety relays are the first choice for managing single safety functions easily, typically in machines of simple to medium complexity. Harmony XPS Universal is the first choice for a broad range of simple to mid-complex machines.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Harmony Safety Automation |
| Product or Component Type | Safety module |
| Safety module name | XPSUAK |
| Safety module application | Monitoring antivalent contacts For emergency stop, guard and light curtain monitoring Monitoring of pressure-sensitive 4-wire protective devices |
| Function of module | Emergency stop button with 2 NC contacts Guard monitoring with 1 or 2 limit switches Monitoring 2 PNP sensors Magnetic switch monitoring Light curtain monitoring RFID switch Monitoring of electro-sensitive protection equipment (ESPE) Sensing mat/edges Proximity sensor monitoring Monitoring 1 PNP + 1 NPN sensor |
| Safety level | Can reach PL e/category 4 for normally open relay contact ISO 13849-1 Can reach SILCL 3 for normally open relay contact IEC 62061 Can reach SIL 3 for normally open relay contact IEC 61508 Can reach PL c/category 1 for normally closed relay contact ISO 13849-1 Can reach SILCL 1 for normally closed relay contact IEC 62061 Can reach SIL 1 for normally closed relay contact IEC 61508 |
| Safety reliability data | MTTFd > 30 years ISO 13849-1 Dcavg >= 99 % ISO 13849-1 PFHd = 1.61E-09 ISO 13849-1 HFT = 1 IEC 62061 PFHd = 1.61E-09 IEC 62061 SFF > 99% IEC 62061 HFT = 1 IEC 61508-1 PFHd = 1.61E-09 IEC 61508-1 SFF > 99% IEC 61508-1 Type = B IEC 61508-1 |
| Electrical circuit type | NC pair PNP pair Antivalent pair OSSD pair |
| Connections - terminals | Removable screw terminal block, 0.2...2.5 mm² solid or flexible Removable screw terminal block, 0.25...2.5 mm² flexible with ferrule single conductor Removable screw terminal block, 0.2...1.5 mm² solid or flexible twin conductor Removable screw terminal block, 2 x 0.25...1 mm² flexible with ferrule without cable end, with bezel Removable screw terminal block, 2 x 0.5...1.5 mm² flexible with ferrule with cable end, with bezel |
| [Us] Rated Supply Voltage | 48...240 V AC/DC - 10...10 % |
Complementary
| Characteristic | Value(s) |
|---|---|
| Synchronisation time between inputs | 0.5 s 2 s 4 s |
| Type of start | Automatic/manual/monitored |
| Power consumption in W | 3.0 W 48 V DC |
| Power consumption in VA | 6.5 VA 240 V AC 50/60 Hz |
| Input protection type | Internal, electronic |
| safety outputs | 2 NO + 1 NC |
| safety inputs | 2 safety input 24 V DC 5 mA |
| maximum wire resistance | 500 Ohm |
| Input compatibility | Normally closed circuit ISO 14119 XC limit switch ISO 14119 Mechanical contact ISO 14119 Normally closed circuit ISO 13850 Antivalent pair ISO 14119 OSSD pair IEC 61496-1-2 3-wire proximity sensors PNP |
| [Ie] rated operational current | 5 A AC-1 for normally open relay contact 3 A AC-15 for normally open relay contact 5 A DC-1 for normally open relay contact 3 A DC-13 for normally open relay contact 3 A AC-1 for normally closed relay contact 1 A AC-15 for normally closed relay contact 3 A DC-1 for normally closed relay contact 1 A DC-13 for normally closed relay contact |
| control outputs | 3 on/off configurable pulsed output |
| Input/output type | Semiconductor pulsed diagnostic output 24 V DC, 20 mA Z1, not safety-related |
| [Ith] conventional free air thermal current | 8 A |
| Associated fuse rating | 10 A gG NO relay output circuit IEC 60947-1 |
| Minimum output current | 10 mA relay output |
| Minimum output voltage | 12 V relay output |
| [Ui] rated insulation voltage | 250 V 2)IEC 60947-1 |
| [Uimp] rated impulse withstand voltage | 4 kV II IEC 60947-1 |
| Mounting Support | 35 mm symmetrical DIN rail |
| Depth | 4.7 in (120 mm) |
| Height | 3.9 in (100 mm) |
| Width | 0.9 in (22.5 mm) |
| Product Weight | 0.441 lb(US) (0.200 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of product | Harmony iDisplay |
| Product or component type | Flat screen |
| Terminal type | Touchscreen display |
| Integrated connection type | USB or RS232C port VGA or DVI-D port |
Complementary
| Characteristic | Value(s) |
|---|---|
| Device mounting | Flush |
| Provided equipment | 1 cable 5 m for DVI-D 1 cable 3 m for VGA |
| [Us] rated supply voltage | 100...240 V AC power supply conforming to EN 61131-2 |
| Supply voltage limits | 98â¦264 V |
| Network frequency | 50/60 Hz (tolerance: +/- 3 Hz) conforming to EN 61131-2 |
| Power consumption in VA | 120 VA |
| Display size | 15 inch |
| Display type | Active matrix colour TFT LCD |
| Display resolution | 1024 x 768 pixels XGA |
| Display colour | 16777216 colors |
| Luminance | 200 cd/m² |
| Backlight lifespan | 50000 hours |
| Touch panel | Analogue resistive 35000000 cycles |
| Type of installation | Indoor installation |
| Width | 395 mm |
| Height | 294 mm |
| Depth | 60 mm |
| Product weight | 7 kg |


This proxy module is part of the Modicon M340 range, an offer of Programmable Automation Controllers (PAC). This module has 128 slaves, 10/100BASE-T and RS485 physical interfaces. It is a proxy module with an external current consumption 300mA at 24V DC. This Modbus Plus Proxy module allows PLCs to communicate with existing Modbus Plus devices without the need to modify these devices applications. It features 2 Ethernet TCP/IP - RJ45 for Modbus TCP and 2 Modbus - SUB-D 9 for Modbus plus for integrated connections. Its current consumption is 300 mA at 24V DC external. It shows a white coating. It is suitable for process industries, renewable energies, water, cement, manufacturing, infrastructures and machines applications. It conforms to UL 508, CSA 22.2, cUL, EMI EN 55011, EN 61131-2, and C-Tick specifications. This module is compatible with Modicon M340 Programmable Logic Controllers (PLC). The module is provided with a mounting plate, 2 front-mounted power supply connectors (2 positions). It can be attached either to a rack or to a DIN rail. Compact-shaped, Modicon M340 offers in small box flexibility and integrated functions. In the heart of process, it provides you plug and work solutions with both Schneider Electric and third party devices.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon X80 |
| Product or Component Type | Modbus Plus proxy module |
| Range Compatibility | Modicon M340 Modicon M580 |
| Structure type | Industrial bus |
Complementary
| Characteristic | Value(s) |
|---|---|
| Communication gateway | Ethernet Modbus TCP to Modbus Plus |
| Physical interface | 10/100BASE-T RS485 |
| Method of access | Token ring Modbus Plus CSMA/CD Modbus TCP |
| Transmission support medium | Modbus Plus single twisted pair cable Modbus TCP category 5 shielded twisted pair (STP) |
| Transmission rate | 1 Mbit/s, 1476.4 ft (450 m) Modbus Plus per segment 1 Mbit/s, 5905.5 ft (1800 m) Modbus Plus with 3 repeaters 10...100 Mbit/s, 328.08 ft (100 m) Modbus TCP without repeater |
| Number of server device(s) | 128 |
| Communication service | Modbus TCP messaging Modbus Plus messaging Configuration control Diagnostics Modbus Plus server (scanned by the PLC) FDR SNMP network management Read/write variables Global Data Peer cop dialogue |
| Integrated connection type | 2 Ethernet TCP/IP - RJ45 Modbus TCP 2 Modbus - SUB-D 9 Modbus Plus |
| Current consumption | 300 mA 24 V DC external |
| Module format | Standard |

This Magelis SCU small touchscreen operator interface controller (HMI) is supplied with 24V DC, has a 5.7" color TFT LCD display and 128MB EPROM. It also has 8 digital inputs, 8 digital outputs, 4 analog inputs, 2 analog outputs, 1 host + 1 mini-B USB ports, 1 RS232C / RS485 port and 1 CANopen port. It is ideal for optimized information and communication with automation systems in industry and infrastructure such as compact machines, handling systems, food & beverage machines and pharmaceutical industry. The screen displays text messages, graphic objects and mimic diagrams, control and configuration of data. Its RS485 and CANopen host ports make it ideal to supervise and control simple systems and machines. Its multiple I/O, including high speed counters, allowing you to processes with fast sensing chains.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Harmony SCU |
| Product or Component Type | Small touch HMI controller |
| Display size | 5.7 inch |
| Display type | Backlit LED colour TFT LCD |
| Touch panel | Analogue |
| Device presentation | Complete product |
Complementary
| Characteristic | Value(s) |
|---|---|
| Display Resolution | 320 x 240 pixels QVGA |
| Backlight lifespan | 50000 hours 65000 colours |
| Brightness | 16 levels via touch panel |
| View angle horiz x vert | 60° left 60° right 40° top 60° bottom |
| Character font | Chinese (simplified Chinese) Japanese (ANK, Kanji) ASCII Korean Taiwanese (traditional Chinese) |
| Supply | External source |
| [Us] rated supply voltage | 24 V 20.4â¦28.8 V)DC |
| Immunity to microbreaks | 10 ms |
| Inrush current | 30 A |
| Power Consumption in W | 24 W |
| Local signalling | No indicator |
| Number of pages | Limited by internal memory capacity |
| Software Designation | SoMachine |
| Operating System | Harmony |
| Processor name | CPU RISC |
| Processor frequency | 333 MHz |
| Memory description | Flash NAND, 128 MB Internal data storage FRAM, 128 kB Application run DRAM, 128 MB |
| Integrated connection type | 1 serial link - RJ45 - RS232/RS485 <= 115.2 kbits/s) 1 Ethernet TCP/IP - RJ45 1 USB 2.0 type mini B 1 USB 2.0 type A CANopen master bus - SUB-D 9 |
| Realtime clock | Built-in |
| Downloadable protocols | Modbus Modbus TCP/IP CANopen |
| Fixing mode | By 1 nut à 22 mm 1...6 mm thick panel |
| Enclosure Material | PC/PBT and PAA |
| Shock resistance | 147 m/s² 11 ms on DIN rail)IEC 60068-2-27 294 m/s² 6 ms on panel mounting)IEC 60068-2-27 |
| Vibration resistance | +/- 3.5 mm 5â¦9 Hz) IEC 60068-2-6 1 gn 9â¦150 Hz) IEC 60068-2-6 |
| Electromagnetic compatibility | Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2 Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz...3 GHz) conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test - test level: 2 kV (power lines) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 1 kV (between analogue I/O and operating voltage) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV (relay wires) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 1 kV (Ethernet line) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 1 kV (COM line) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 1 kV (CAN line) conforming to IEC 61000-4-4 Surge immunity test - test level: 2 kV (power supply (common mode)) conforming to IEC 61000-4-5 Surge immunity test - test level: 1 kV (power supply (differential mode)) conforming to IEC 61000-4-5 Surge immunity test - test level: 1 kV common mode (digital I/O) conforming to IEC 61000-4-5 Surge immunity test - test level: 0.5 kV differential mode (digital I/O) conforming to IEC 61000-4-5 Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6 Conducted emission - test level: 150 kHz...30 MHz conforming to EN 55011 Radiated emission - test level: 30 MHz...1 GHz conforming to EN 55011 |
| Discrete input number | 2 fast input (normal mode) IEC 61131-2 Type 1 6 digital input IEC 61131-2 Type 1 |
| Discrete input voltage | 24 V DC sink or source (positive/negative) |
| Number of common point | 1 fast input (HSC mode) 1 digital input |
| Discrete input current | 7.83 mA fast input 5 mA digital |
| Input impedance | 4.7 kOhm 2.81 kOhm |
| Sensor power supply | 15â¦28.8 V DC >= 15 V >= 5 mA <= 5 V <= 1.5 mA 15â¦28.8 V DC >= 15 V >= 2.5 mA <= 5 V <= 1 mA |
| Configurable filtering time | 0 ms no filter none) 0.004...0.04 ms bounce filter latch/event and cumulative filter by step Nx0.5ms (64>=N>=2)) 3...12 ms integrator none/run/stop) |
| Maximum input frequency | 100 kHz fast input (encoder mode) A/B 100 kHz fast input single phase 100 kHz fast input pulse/direction |
| Maximum cable distance between devices | Shielded cable <32.8 ft (10 m) fast input Shielded cable <328.08 ft (100 m) digital input Unshielded cable <164.04 ft (50 m) digital input |
| Connection pitch | 0.1 in (3.5 mm) |
| Overvoltage protection | With |
| Isolation between channels and internal logic | 500 V DC |
| Isolation between channels | None |
| Discrete output number | 2 fast output (normal mode) source 6 digital output source |
| Discrete output voltage | 24 V DC 19.2...28.8 V)transistor 24 V DC 5...30 V)relay 220 V AC 100...250 V)relay |
| Input/output number | 2 fast input FI0...FI1 2 fast output FQ0...FQ1 6 digital input DI0...DI5 6 digital output DQ0...DQ5 |
| Discrete output current | 2 A 4 A)5 ms opening contact digital output 2 A 4 A)2 ms closing contact digital output 300 mA2 ms fast output (normal mode) 50 mA2 ms fast output (PWM or PTO mode) |
| Insulation resistance | > 10 MOhm between the I/O and internal logic > 10 MOhm between power supply and earth |
| Maximum output frequency | 100 kHz fast output (PTO mode) 1 kHz fast output (PWM mode) |
| Absolute accuracy error | +/- 0.1 % of full scale cyclic ratio 1...99% fast output (PWM or PTO mode) 1 % of full scale cyclic ratio 1...99% fast output (PWM or PTO mode) +/- 5 % of full scale cyclic ratio 10...90% fast output (PWM or PTO mode) +/- 10 % of full scale cyclic ratio 20...80% fast output (PWM or PTO mode) +/- 15 % of full scale cyclic ratio 30...70% fast output (PWM or PTO mode) |
| Analogue input number | 2 analog input 2 RTDs |
| Analogue input range | 0...20 mA/4...20 mA 12 bits 250 Ohm +/- 1 %) -10...+10 V or 0...10 V 12 bits + sign >= 1 MOhm |
| Analogue input type | RTD - 200...600 °C 16 bitsPt 100/Pt 1000 RTD - 50...200 °C 16 bitsNi 100/Ni 1000 RTD - 200...760 °C 16 bits thermocouple J) RTD - 240...1370 °C 16 bits thermocouple K) RTD 0...1600 °C 16 bits thermocouple R) RTD 200...1800 °C 16 bits thermocouple B) RTD 0...1600 °C 16 bits thermocouple S) RTD - 200...400 °C 16 bits thermocouple T) RTD - 200...900 °C 16 bits thermocouple E) RTD - 200...1300 °C 16 bits thermocouple N) |
| Analogue output number | 2 resistive load 12 bits + sign |
| Analogue output range | 0...20 mA/4...20 mA > 300 Ohm)open-circuit -10...10 V/0...10 V > 2 kOhm)short-circuit |
| Height | 5.09 in (129.4 mm) |
| Width | 6.4 in (163 mm) |
| Depth | 3.0008 in (76.22 mm) |
| Product Weight | 1.770 lb(US) (0.803 kg) |

This XPSMP safety contoller can handle 2 independent safety functions. This safety controller with pre-defined functions meets the requirements of PL e/Category 4 conforming EN ISO 13849-1 and SILCL 3 conforming to EN/IEC 61508 and EN/IEC 62061. It enables two independent safety functions (selected from a choice of 15 pre-defined configurations) to be performed using the same product. It complies with the most stringent functional safety requirements thanks to multiple configurable safety functions. It has additional solid-state output for communication with PLCs about safety status of your process.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Preventa Safety automation |
| Product or Component Type | Safety controller with pre-defined function |
| Safety module name | XPSMP |
| Safety module application | 2 independent functions |
| Safety use category | Category 4 maximum EN/IEC 60954-1 |
| Type of start | Automatic or unmonitored 1) Automatic or unmonitored 10) Automatic or unmonitored 11) Automatic or unmonitored 14) Automatic or unmonitored 3) Automatic or unmonitored 5) Automatic or unmonitored 7) Monitored 12) Monitored 13) Monitored 15) Monitored 2) Monitored 4) Monitored 6) Monitored 8) Monitored 9) |
| Checks | Configuration 10) Configuration 13) Configuration 3) Configuration 4) Configuration 5) Configuration 6) Configuration 9) |
| Standards | EN/IEC 60947-1 + A11 EN/IEC 60947-5-1 EN/IEC 60204-1 DIN V VDE 801 + A1 |
| Product Certifications | UL CSA BIA |
| [Us] Rated Supply Voltage | 24 V DC - 20...20 % |
| Connections - terminals | Captive screw clamp terminals flexible 0.14...0.75 mm² without cable end, 2 wires Captive screw clamp terminals solid 0.14...0.75 mm² without cable end, 2 wires Captive screw clamp terminals flexible 0.14...2.5 mm² without cable end, 1 wire Captive screw clamp terminals solid 0.14...2.5 mm² without cable end, 1 wire Captive screw clamp terminals flexible 0.25...1 mm² with cable end, without bezel, 2 wires Captive screw clamp terminals flexible 0.25...1.5 mm² with cable end, with bezel, 1 wire Captive screw clamp terminals flexible 0.25...2.5 mm² with cable end, without bezel, 1 wire Captive screw clamp terminals flexible 0.5...1.5 mm² with cable end, with double bezel, 2 wires |
| Safety level | Can reach PL e/category 4 EN/ISO 13849-1 Can reach SIL 3 EN/IEC 62061 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Function of module | 0 functions disabled (factory setting) 1 emergency stop monitoring 1-channel wiring, category 2 10 enabling grip switch monitoring (3-position switch), category 4 11 sensing mat and edges monitoring, category 3 12 sensing mat and edges monitoring, category 3 13 relay output safety light curtain monitoring, category 4 14 coded magnetic switch monitoring, category 4 15 coded magnetic switch monitoring, category 4 2 emergency stop monitoring 1-channel wiring, category 2 3 emergency stop monitoring 2-channel wiring, or guard monitoring, category 4 4 emergency stop monitoring 2-channel wiring, or guard monitoring, category 4 5 emergency stop monitoring 2-channel wiring, or guard monitoring, category 4 6 emergency stop monitoring 2-channel wiring, or guard monitoring, category 4 7 emergency stop monitoring 2-channel wiring, or guard monitoring, category 4 8 emergency stop monitoring 2-channel wiring, or guard monitoring, category 4 9 guard monitoring for injection presses and blowing machines, category 4 |
| Synchronisation time between inputs | 0.5 s 13) 1.5 s 14) 1.5 s 15) 1.5 s 5) 1.5 s 6) 1.5 s 9) Unlimited 3) Unlimited 4) Unlimited 7) Unlimited 8) |
| Power Consumption in W | 5 W |
| Input protection type | Internal, electronic |
| [Uc] control circuit voltage | 24 V |
| Maximum line resistance | 100 Ohm <6561.7 ft (2000 m) |
| Number of safety circuits | 3 NO relays per function (6 NO total), volt-free |
| Number of additional circuits | 3 solid state outputs |
| Breaking capacity | 180 VA holding AC-15 C300 relay output 1800 VA inrush AC-15 C300 relay output |
| Breaking capacity | 20 mA 24 V static output circuit 1.5 A 24 V DC-13)50 ms relay output |
| Output thermal current | 2 A for 1 output and 4 A for the other 2 outputs relay 3.3 A for all 3 outputs relay simultaneously 6 A for 1 output and 2 A for the other 2 outputs relay |
| [Ith] conventional free air thermal current | 20 A |
| Associated fuse rating | 4 A gG relay output EN/IEC 60947-5-1, DIN VDE 0660 part 200 6 A fast blow relay output EN/IEC 60947-5-1, DIN VDE 0660 part 200 |
| Minimum output current | 10 mA relay output |
| Minimum output voltage | 17 V relay output |
| Maximum response time on input open | 30 ms |
| [Ui] rated insulation voltage | 300 V 2)EN/IEC 60947-5-1, DIN VDE 0110 parts 1 & 2 |
| [Uimp] rated impulse withstand voltage | 4 kV III EN/IEC 60947-5-1, DIN VDE 0110 parts 1 & 2 |
| Local signalling | 12 LEDs |
| Mounting Support | 35 mm symmetrical DIN rail |
| Depth | 4.5 in (114 mm) |
| Height | 3.9 in (99 mm) |
| Width | 1.8 in (45 mm) |
| Product Weight | 0.71 lb(US) (0.32 kg) |