Motor circuit breaker, TeSys GV4, 3P, 12.5A, Icu 50kA, thermal magnetic multifunction, Everlink terminals

TeSys GV motor circuit breaker, 3 poles (3P), 32A/690V, for 3-phase motor applications 15kW@400V. It provides a thermal-magnetic protection with a thermal setting range 23-32A, magnetic tripping at 14xIn, high breaking capacity Icu 100kA@400V. Upstream connection by Everlink BTR screw terminals, without downstream power terminal block for a direct assembly with a LC1D40A to D80A contactor. Start-stop control by rotary knob guaranteed for 50 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
Main
| Characteristic | Value(s) |
|---|---|
| Range | TeSys Deca |
| product name | TeSys GV3 |
| Product or component type | Motor circuit breaker |
| Device short name | GV3P |
| Device application | Motor protection |
| Trip unit technology | Thermal-magnetic |
Complementary
| Characteristic | Value(s) |
|---|---|
| Poles description | 3P |
| Network type | AC |
| Utilisation category | Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Motor power kW | 15 kW at 400/415 V AC 50/60 Hz 18.5 kW at 500 V AC 50/60 Hz 22 kW at 690 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| control type | Rotary handle |
| [In] rated current | 32 A |
| Thermal protection adjustment range | 23â¦32 A conforming to IEC 60947-2 |
| Magnetic tripping current | 448 A |
| [Ith] conventional free air thermal current | 32 A conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Power dissipation per pole | 8 W |
| Mechanical durability | 50000 cycles |
| Electrical durability | 50000 cycles for AC-3 at 415 V In |
| Rated duty | Uninterrupted conforming to IEC 60947-4-1 |
| Tightening torque | 5 N.m - on screw clamp terminal |
| Fixing mode | 35 mm symmetrical DIN rail: clipped Panel: screwed (with 3 x M4 screws) |
| Mounting position | Horizontal Vertical |
| Width | 55 mm |
| Height | 132 mm |
| Depth | 136 mm |
| Product weight | 0.96 kg |
| Colour | Dark grey |

TeSys GV motor circuit breaker, 3 poles (3P), 25A/690V, for protection of 3-phase motors 5.5-11kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 25kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 10-25A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX).
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | TeSys GV4 |
| Range | TeSys Deca |
| Device short name | GV4PE |
| product name | TeSys GV4 |
| Product or Component Type | Motor circuit breaker |
| Device Application | Motor protection |
| Trip unit technology | Electronic Thermal-magnetic |
Complementary
| Characteristic | Value(s) |
|---|---|
| Poles description | 3P |
| Utilisation category | Category A IEC 60947-2 AC-3 IEC 60947-4-1 |
| Operating position | Any position |
| Motor power kW | 7.5 kW 660...690 V AC 50/60 Hz 5.5 kW 400...415 V AC 50/60 Hz 7.5 kW 500 V AC 50/60 Hz 9 kW 660...690 V AC 50/60 Hz 11 kW 660...690 V AC 50/60 Hz 7.5 kW 400...415 V AC 50/60 Hz 9 kW 400...415 V AC 50/60 Hz 11 kW 400...415 V AC 50/60 Hz 9 kW 500 V AC 50/60 Hz 11 kW 500 V AC 50/60 Hz 15 kW 500 V AC 50/60 Hz 15 kW 660...690 V AC 50/60 Hz 18.5 kW 660...690 V AC 50/60 Hz |
| Breaking capacity | 50 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 25 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 35 kA 208Y/120 V AC 50/60 Hz UL 60947 35 kA 240 V AC 50/60 Hz UL 60947 18 kA 480Y/277 V AC 50/60 Hz UL 60947 14 kA 600Y/347 V AC 50/60 Hz UL 60947 |
| Control Type | Toggle |
| Line Rated Current | 25 A |
| Magnetic tripping current | 425 A |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz IEC 60947-2 |
| [Ith] conventional free air thermal current | 115 A IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 8 kV IEC 60947-2 |
| Power dissipation per pole | 4.6 W |
| Mechanical durability | 40000 cycles |
| Electrical durability | 40000 cycles AC-3 440 V In/2 20000 cycles AC-3 440 V In |
| Maximum operating rate | 25 cyc/h |
| Rated duty | Continuous IEC 60947-4-1 |
| Connections - terminals | EverLink BTR screw connectors top) 1 0.002â¦0.1 in² (1.5â¦70 mm²) - solid EverLink BTR screw connectors top) 1 0.002â¦0.08 in² (1.5â¦50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004â¦0.1 in² (2.5â¦95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004â¦0.1 in² (2.5â¦70 mm²) - flexible |
| Tightening torque | 79.7 lbf.in (9 N.m) 0.02â¦0.1 in² (16â¦95 mm²) 44.3 lbf.in (5 N.m) 0.002â¦0.02 in² (1.5â¦10 mm²) |
| Mechanical robustness | Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27 |
| Phase failure sensitivity | Yes IEC 60947-4-1 |
| Height | 6.1 in (155 mm) |
| Width | 3.2 in (81 mm) |
| Depth | 4.6 in (116 mm) |
| Product Weight | 3.20 lb(US) (1.45 kg) |
| color | Gray RAL 7016) |
| Suitability for isolation | Yes IEC 60947-1 |

TeSys GV motor circuit breaker, 3 poles (3P), 2A/690V, for protection of 3-phase motors 0.25-0.75kW@400V. It provides magnetic protection, breaking capacity Icu 100kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Magnetic protection adjustable by dial, setting range 6-14 In. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). To be used in association with a class 10 or 20 thermal overload relay to complete motor protection. Multi standards certified (IEC, CCC, EAC, Marine).
Main
| Characteristic | Value(s) |
|---|---|
| Range of product | TeSys GV4 |
| Range | TeSys Deca |
| Device short name | GV4L |
| product name | TeSys GV4 |
| Product or component type | Motor circuit breaker |
| Device application | Motor protection |
| Trip unit technology | Magnetic Electronic |
Complementary
| Characteristic | Value(s) |
|---|---|
| Poles description | 3P |
| Utilisation category | Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 |
| Operating position | Any position |
| Motor power kW | 0.25 kW at 400...415 V AC 50/60 Hz 0.37 kW at 400...415 V AC 50/60 Hz 0.55 kW at 400...415 V AC 50/60 Hz 0.75 kW at 400...415 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz 1.1 kW at 500 V AC 50/60 Hz 0.55 kW at 660...690 V AC 50/60 Hz 0.75 kW at 660...690 V AC 50/60 Hz 1.1 kW at 660...690 V AC 50/60 Hz 1.5 kW at 660...690 V AC 50/60 Hz |
| Breaking capacity | 120 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 |
| control type | Toggle |
| [In] rated current | 2 A |
| Magnetic tripping current | 12â¦28 A |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ith] conventional free air thermal current | 115 A conforming to IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| Power dissipation per pole | 6.1 W |
| Mechanical durability | 40000 cycles |
| Electrical durability | 40000 cycles for AC-3 at 440 V In/2 40000 cycles for AC-3 at 440 V In |
| Maximum operating rate | 25 cyc/h |
| Rated duty | Continuous conforming to IEC 60947-4-1 |
| Connections - terminals | EverLink BTR screw connectors (top) 1 cable(s) 1.5â¦70 mm² - solid EverLink BTR screw connectors (top) 1 cable(s) 1.5â¦50 mm² - flexible EverLink BTR screw connectors (bottom) 1 cable(s) 2.5â¦95 mm² - solid EverLink BTR screw connectors (bottom) 1 cable(s) 2.5â¦70 mm² - flexible |
| Tightening torque | 9 N.m for cable 16â¦95 mm² 5 N.m for cable 1.5â¦10 mm² |
| Mechanical robustness | Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 Shocks: 15 gn 11 ms conforming to IEC 60068-2-27 |
| Height | 155 mm |
| Width | 81 mm |
| Depth | 116 mm |
| Product weight | 1.5 kg |
| Colour | Grey (RAL 7016) |
| Suitability for isolation | Yes conforming to IEC 60947-1 |



Main
| Characteristic | Value(s) |
|---|---|
| Range | TeSys |
| Product or Component Type | Comb busbar |
| Accessory / separate part category | Connection accessory |
| Range compatibility | TeSys Deca TeSys GV3 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Product Compatibility | GV3P LC1D40A...D65A GV3L |
| Poles description | 3P |
| Product Weight | 0.229 lb(US) (0.104 kg) |

TeSys GV motor circuit breaker, 3 poles (3P), 115A/690V, for protection of 3-phase motors 37-55kW@400V. It provides magnetic protection, breaking capacity Icu 50kA@400V, start-stop control by rotary handle, connection for bars or cables with lugs. Magnetic protection adjustable by dial, setting range 6-14 In. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). To be used in association with a class 10 or 20 thermal overload relay to complete motor protection. Multi standards certified (IEC, CCC, EAC, Marine).
Main
| Characteristic | Value(s) |
|---|---|
| Range of product | TeSys GV4 |
| Range | TeSys Deca |
| Device short name | GV4L |
| product name | TeSys GV4 |
| Product or component type | Motor circuit breaker |
| Device application | Motor protection |
| Trip unit technology | Magnetic Electronic |
Complementary
| Characteristic | Value(s) |
|---|---|
| Poles description | 3P |
| Utilisation category | Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 |
| Operating position | Any position |
| Motor power kW | 37 kW at 400...415 V AC 50/60 Hz 45 kW at 400...415 V AC 50/60 Hz 55 kW at 400...415 V AC 50/60 Hz 45 kW at 500 V AC 50/60 Hz 55 kW at 500 V AC 50/60 Hz 75 kW at 500 V AC 50/60 Hz 75 kW at 660...690 V AC 50/60 Hz 90 kW at 660...690 V AC 50/60 Hz 110 kW at 660...690 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| control type | Rotary handle |
| [In] rated current | 115 A |
| Magnetic tripping current | 690â¦1610 A |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ith] conventional free air thermal current | 115 A conforming to IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| Power dissipation per pole | 6.1 W |
| Mechanical durability | 40000 cycles |
| Electrical durability | 10000 cycles for AC-3 at 440 V In/2 5000 cycles for AC-3 at 440 V In |
| Maximum operating rate | 25 cyc/h |
| Rated duty | Continuous conforming to IEC 60947-4-1 |
| Connection pitch | 27 mm without spreaders 35 mm with spreaders |
| Connections - terminals | Lugs-ring terminals |
| Tightening torque | 9 N.m for cable 16â¦95 mm² 5 N.m for cable 1.5â¦10 mm² |
| Mechanical robustness | Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 Shocks: 15 gn 11 ms conforming to IEC 60068-2-27 |
| Height | 155 mm |
| Width | 81 mm |
| Depth | 165 mm |
| Product weight | 1.65 kg |
| Colour | Grey (RAL 7016) |
| Suitability for isolation | Yes conforming to IEC 60947-1 |

TeSys GV motor circuit breaker, 3 poles (3P), 32A/690V, for 3-phase motor applications 15kW@400V. It provides a magnetic protection with a tripping level at 13xIn, high breaking capacity Icu 10kA@400V. Connection by screw clamp terminals. Start-stop control by toggle guaranteed for 100 000 cycles AC-3. To complete motor protection, use in association with a thermal overload relay LRD32 (to be ordered separately). Multi standards certified (IEC, CCC, EAC, Marine).
Main
| Characteristic | Value(s) |
|---|---|
| Range | TeSys Deca |
| product name | TeSys GV2 |
| Product or Component Type | Motor circuit breaker |
| Device short name | GV2LE |
| Device Application | Motor protection |
| Trip unit technology | Magnetic |
Complementary
| Characteristic | Value(s) |
|---|---|
| Poles description | 3P |
| Network type | AC |
| Utilisation category | Category A IEC 60947-2 AC-3 IEC 60947-4-1 AC-3e IEC 60947-4-1 |
| Network frequency | 50/60 Hz IEC 60947-2 |
| Motor power kW | 15 kW 400/415 V AC 50/60 Hz 18.5 kW 500 V AC 50/60 Hz 22 kW 690 V AC 50/60 Hz |
| Breaking capacity | 50 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 10 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 6 kA Icu 440 V AC 50/60 Hz IEC 60947-2 4 kA Icu 500 V AC 50/60 Hz IEC 60947-2 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % 230/240 V AC 50/60 Hz IEC 60947-2 50 % 400/415 V AC 50/60 Hz IEC 60947-2 50 % 440 V AC 50/60 Hz IEC 60947-2 75 % 500 V AC 50/60 Hz IEC 60947-2 75 % 690 V AC 50/60 Hz IEC 60947-2 |
| Control Type | Toggle |
| Line Rated Current | 32 A |
| Magnetic tripping current | 537.6 A |
| [Ith] conventional free air thermal current | 32 A IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV IEC 60947-2 |
| Suitability for isolation | Yes IEC 60947-1 |
| Power dissipation per pole | 1.8 W |
| Mechanical durability | 100000 cycles |
| Electrical durability | 100000 cycles AC-3 415 V In 100000 cycles AC-3e 415 V In |
| Rated duty | Uninterrupted IEC 60947-4-1 |
| Connections - terminals | Power circuit screw clamp terminal 2 0.002â¦0.009 in² (1â¦6 mm²)solid Power circuit screw clamp terminal 2 0.002â¦0.009 in² (1.5â¦6 mm²)flexible without cable end Power circuit screw clamp terminal 2 0.002â¦0.006 in² (1â¦4 mm²)flexible with cable end |
| Tightening torque | 15.05 lbf.in (1.7 N.m) screw clamp terminal |
| Fixing mode | 35 mm symmetrical DIN rail clipped Panel screwed with adaptor plate) |
| Mounting position | Horizontal Vertical |
| Width | 1.8 in (45 mm) |
| Height | 3.5 in (89 mm) |
| Depth | 3.09 in (78.5 mm) |
| Product Weight | 0.73 lb(US) (0.33 kg) |
| color | Dark grey |

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

| Product | |
| Article Number (Market Facing Number) | 3RN20102CW30 | 3RN20102CW30 |
| Product Description | |
| Product family | SIRIUS 3RN2 thermistor motor protection |
| Product Lifecycle (PLM) | PM300:Active Product |
| Additional Product Information | |
| EAN | 4047621004440 |
| UPC | 804766415548 |
| Commodity Code | 85364900 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Product Group | 4953 |
| Group Code | R711 |
| Country of origin | Germany |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 0.309 lb |
| Package size unit of measure | in |
| Packaging Quantity | 1 |

| Product | |
| Article Number (Market Facing Number) | 3RU21264PC1 | 3RU21264PC1 |
| Product Description | Overload relay 30...36 A Thermal For motor protection Size S0, Class 10 Stand-alone installation Main circuit: Spring-type terminal Auxiliary circuit: spring-type terminal Manual-Automatic-Reset |
| Product family | SIRIUS 3RU2 thermal overload relays |
| Product Lifecycle (PLM) | PM300:Active Product |
| Additional Product Information | |
| EAN | 4011209781306 |
| UPC | 662643919554 |
| Commodity Code | 85364900 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Product Group | 5346 |
| Group Code | R711 |
| Country of origin | Germany |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 0.705 lb |
| Package size unit of measure | in |
| Packaging Quantity | 1 |

| Product | |
| Article Number (Market Facing Number) | 3RN10122GB00 | 3RN10122GB00 |
| Product Description | !!! Phased-out product !!! The preferred successor is 3RN2012-2BA30 Thermistor motor protection Standard evaluation unit Manual/Auto/Remote 2 W, hard gold-plated, 24 V AC/DC |
| Product family | Not available |
| Product Lifecycle (PLM) | PM490:Start of final year of support |
| Additional Product Information | |
| EAN | 4011209568259 |
| UPC | 887621853945 |
| Commodity Code | 85364190 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Product Group | 5883 |
| Group Code | R711 |
| Country of origin | Germany |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 0.317 lb |
| Package size unit of measure | Inch |
| Packaging Quantity | 1 |

| Product | |
| Article Number (Market Facing Number) | 3RU21364HB0 | 3RU21364HB0 |
| Product Description | Overload relay 40... 50 A Thermal For motor protection Size S2, Class 10 Contactor mounting Main circuit: Screw Auxiliary circuit: Screw Manual-Automatic-Reset |
| Product family | SIRIUS 3RU2 thermal overload relays |
| Product Lifecycle (PLM) | PM300:Active Product |
| Additional Product Information | |
| EAN | 4011209916753 |
| UPC | 887621919641 |
| Commodity Code | 85364900 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Product Group | 5346 |
| Group Code | R711 |
| Country of origin | Germany |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 0.705 lb |
| Package size unit of measure | Inch |
| Packaging Quantity | 1 |

| Product | |
| Article Number (Market Facing Number) | 3RU21160CC0 | 3RU21160CC0 |
| Product Description | Overload relay 0.18...0.25 A Thermal For motor protection Size S00, Class 10 Contactor mounting Main circuit: Spring-type terminal Auxiliary circuit: spring-type terminal Manual-Automatic-Reset |
| Product family | SIRIUS 3RU2 thermal overload relays |
| Product Lifecycle (PLM) | PM300:Active Product |
| Additional Product Information | |
| EAN | 4011209781948 |
| UPC | 662643919714 |
| Commodity Code | 85364900 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Product Group | 5346 |
| Group Code | R711 |
| Country of origin | Germany |
| SCIP number | Not available |
| Delivery information | |
| Net Weight (lb) | 0.375 lb |
| Package size unit of measure | in |
| Packaging Quantity | 1 |