PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.



PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.



TeSys GV motor circuit breaker, 3 poles (3P), 115A/690V, for protection of 3-phase motors 37-55kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 100kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 65-115A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX).
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | TeSys GV4 |
| Range | TeSys Deca |
| Device short name | GV4PE |
| product name | TeSys GV4 |
| Product or Component Type | Motor circuit breaker |
| Device Application | Motor protection |
| Trip unit technology | Thermal-magnetic Electronic |
Complementary
| Characteristic | Value(s) |
|---|---|
| Poles description | 3P |
| Utilisation category | Category A IEC 60947-2 AC-3 IEC 60947-4-1 |
| Operating position | Any position |
| Motor power kW | 37 kW 400...415 V AC 50/60 Hz 45 kW 400...415 V AC 50/60 Hz 55 kW 400...415 V AC 50/60 Hz 45 kW 500 V AC 50/60 Hz 55 kW 500 V AC 50/60 Hz 75 kW 500 V AC 50/60 Hz 75 kW 660...690 V AC 50/60 Hz 90 kW 660...690 V AC 50/60 Hz 110 kW 660...690 V AC 50/60 Hz |
| Breaking capacity | 120 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 70 kA Icu 440 V AC 50/60 Hz IEC 60947-2 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA Icu 525 V AC 50/60 Hz IEC 60947-2 100 kA 208Y/120 V AC 50/60 Hz UL 60947 100 kA 240 V AC 50/60 Hz UL 60947 65 kA 480Y/277 V AC 50/60 Hz UL 60947 10 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA 600Y/347 V AC 50/60 Hz UL 60947 |
| Control Type | Toggle |
| Line Rated Current | 115 A |
| Magnetic tripping current | 1955 A |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz IEC 60947-2 |
| [Ith] conventional free air thermal current | 115 A IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 8 kV IEC 60947-2 |
| Power dissipation per pole | 4.6 W |
| Mechanical durability | 40000 cycles |
| Electrical durability | 10000 cycles AC-3 440 V In/2 5000 cycles AC-3 440 V In |
| Maximum operating rate | 25 cyc/h |
| Rated duty | Continuous IEC 60947-4-1 |
| Connections - terminals | EverLink BTR screw connectors top) 1 0.002â¦0.1 in² (1.5â¦70 mm²) - solid EverLink BTR screw connectors top) 1 0.002â¦0.08 in² (1.5â¦50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004â¦0.1 in² (2.5â¦95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004â¦0.1 in² (2.5â¦70 mm²) - flexible |
| Tightening torque | 79.7 lbf.in (9 N.m) 0.02â¦0.1 in² (16â¦95 mm²) 44.3 lbf.in (5 N.m) 0.002â¦0.02 in² (1.5â¦10 mm²) |
| Mechanical robustness | Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27 |
| Phase failure sensitivity | Yes IEC 60947-4-1 |
| Height | 6.1 in (155 mm) |
| Width | 3.2 in (81 mm) |
| Depth | 4.6 in (116 mm) |
| Product Weight | 3.20 lb(US) (1.45 kg) |
| color | Gray RAL 7016) |
| Suitability for isolation | Yes IEC 60947-1 |



Specifications
Model |
SL-VC10PM |
|||
Applicable product |
SL-V Series |
|||
Length |
10 m 32.81' |
|||
Note |
12-core shielded cable, brown and blue: 24 AWG (nominal cross section: 0.22 mm2), other: 26 AWG (nominal cross section: 0.14 mm2) |
|||

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.

TeSys GV motor circuit breaker, 3 poles (3P), 115A/690V, for protection of 3-phase motors 37-55kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 25kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 65-115A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX).
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | TeSys GV4 |
| Range | TeSys Deca |
| Device short name | GV4PE |
| product name | TeSys GV4 |
| Product or Component Type | Motor circuit breaker |
| Device Application | Motor protection |
| Trip unit technology | Electronic Thermal-magnetic |
Complementary
| Characteristic | Value(s) |
|---|---|
| Poles description | 3P |
| Utilisation category | Category A IEC 60947-2 AC-3 IEC 60947-4-1 |
| Operating position | Any position |
| Motor power kW | 37 kW 400...415 V AC 50/60 Hz 45 kW 400...415 V AC 50/60 Hz 55 kW 400...415 V AC 50/60 Hz 45 kW 500 V AC 50/60 Hz 55 kW 500 V AC 50/60 Hz 75 kW 500 V AC 50/60 Hz 75 kW 660...690 V AC 50/60 Hz 90 kW 660...690 V AC 50/60 Hz 110 kW 660...690 V AC 50/60 Hz |
| Breaking capacity | 50 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 25 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 35 kA 208Y/120 V AC 50/60 Hz UL 60947 35 kA 240 V AC 50/60 Hz UL 60947 18 kA 480Y/277 V AC 50/60 Hz UL 60947 14 kA 600Y/347 V AC 50/60 Hz UL 60947 |
| Control Type | Toggle |
| Line Rated Current | 115 A |
| Magnetic tripping current | 1955 A |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz IEC 60947-2 |
| [Ith] conventional free air thermal current | 115 A IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 8 kV IEC 60947-2 |
| Power dissipation per pole | 4.6 W |
| Mechanical durability | 40000 cycles |
| Electrical durability | 10000 cycles AC-3 440 V In/2 5000 cycles AC-3 440 V In |
| Maximum operating rate | 25 cyc/h |
| Rated duty | Continuous IEC 60947-4-1 |
| Connections - terminals | EverLink BTR screw connectors top) 1 0.002â¦0.1 in² (1.5â¦70 mm²) - solid EverLink BTR screw connectors top) 1 0.002â¦0.08 in² (1.5â¦50 mm²) - flexible EverLink BTR screw connectors bottom) 1 0.004â¦0.1 in² (2.5â¦95 mm²) - solid EverLink BTR screw connectors bottom) 1 0.004â¦0.1 in² (2.5â¦70 mm²) - flexible |
| Tightening torque | 79.7 lbf.in (9 N.m) 0.02â¦0.1 in² (16â¦95 mm²) 44.3 lbf.in (5 N.m) 0.002â¦0.02 in² (1.5â¦10 mm²) |
| Mechanical robustness | Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27 |
| Phase failure sensitivity | Yes IEC 60947-4-1 |
| Height | 6.1 in (155 mm) |
| Width | 3.2 in (81 mm) |
| Depth | 4.6 in (116 mm) |
| Product Weight | 3.20 lb(US) (1.45 kg) |
| color | Gray RAL 7016) |
| Suitability for isolation | Yes IEC 60947-1 |


PLC Direct is not an authorized distributor. We offer a broad range of in-stock products with minimal lead time.


Specifications
Model |
SL-V104H |
|||
Detection capability |
ø0.98" ø25 mm |
|||
Beam axis spacing/Lens diameter |
20 mm/ø5 mm 0.79"/ø0.20" |
|||
Effective aperture angle |
Max. ±2.5 ° (When operating distance is 3 m 98.23' or more) |
|||
Working distance |
0.1 to 7 m |
|||
Response time (ms) |
ON→OFF |
20.2*1 |
||
OFF→ON |
60.2*1 |
|||
Light source |
Infrared LED (850 nm) |
|||
Operation mode |
Turns on when no interruptions are present in the detection zone (excluding when the muting function is used) |
|||
OSSD output |
Output |
2 outputs each for PNP and NPN. Can be changed by using the connector cable. |
||
Max. l oad current |
500 mA*2 |
|||
Residual vol tage (during ON) |
Max. 2.5 V (with a cable length of 7 m 22.97') |
|||
Leakage current |
Max. 100 µA*3 |
|||
Max. capacitive load |
2.2 µF (with a load resistance of 100 Ω) |
|||
Load wiring resistance |
Max. 2.5 Ω*4 |
|||
Non safety-rel ated output |
AUX |
Output with automatic PNP/NPN switching function, 50 mA max. |
||
Interlock-reset-ready output | ||||
Alarm output | ||||
Clear/blocked output | ||||
State information output 1, 2 | ||||
Muting lamp output |
Incandescent lamp (24 VDC, 1 to 7 W) or LED lamp (load current: 10 to 300 mA)*5 can be connected |
|||
Input |
EDM input |
Short-circuit current 10 mA |
||
Wait input |
Short-circuit current 2.5 mA |
|||
Reset input | ||||
Muting input 1, 2 | ||||
Override input | ||||
Protection circuit |
Reverse current protection, short-circuit protection for each output, surge protection for each output |
|||
Approved standards |
EMC |
EMS |
IEC61496-1, EN61496-1, UL61496-1 |
|
EMI |
EN55011 Class A, FCC Part15B Class A |
|||
Safety |
IEC61496-1, EN61496-1, UL61496-1 (Type 4 ESPE) |
|||
Rating |
Power voltage |
24 VDC +10 %, -20 %, Ripple (P-P) 10 % or less |
||
Current consumption (mA) |
When the center indicator is ON |
Transmitter |
159*6 |
|
Receiver |
107*6 |
|||
When the center indicator is OFF |
Transmitter |
143*6 |
||
Receiver |
84*6 |
|||
Environmental resistance |
Enclosure rating |
IP65 (IEC60529) |
||
Overvoltage category |
II |
|||
Ambient light |
Incandescent lamp: 5,000 lux max., Sunlight: 20,000 lux max. |
|||
Operating ambient temperature |
-10 to +55 °C 14 to 131 °F (No freezing) |
|||
Operating relative humidity |
15 to 85 % RH (No condensation) |
|||
Storage temperature |
-25 to +60 °C -13 to 140 °F (No freezing) |
|||
Storage relative humidity |
15 to 95 % RH |
|||
Vibration resistance |
10 to 55 Hz, Double amplitude 0.7 mm 0.03", 20 sweeps in each of the X, Y, and Z directions |
|||
Shock resistance |
100 m/s2 (Approx. 10 G), 16 ms pulse, 1,000 times in each of the X, Y, and Z directions |
|||
Material |
Main unit case |
Aluminum |
||
Upper case/lower case |
Zinc die-cast |
|||
Front cover |
Polycarbonate, SUS304 |
|||
Weight |
Transmitter |
1,360 g |
||
Receiver |
1,405 g |
|||
*1 When connecting the SL-V units in series, the response time (ON to OFF) is the sum of the response times of al l the individual SL-V units, but the response time (OFF to ON) is the same as that of a singl e SL-V unit. | ||||