trip unit TM80D for Compact NSX 100/160/250 circuit breakers, thermal magnetic, rating 80 A, 4 poles 4d

This TM63D is a 4 poles 4d thermal-magnetic trip unit used on Compact NSX 100/160/250 circuit breakers. This 63A rating thermal-magnetic trip unit is an optimum choice for all distribution applications. It embeds an adjustable thermal overload protection and a fixed magnetic protection against short-circuits. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.
Main
| Characteristic | Value(s) |
|---|---|
| Range | ComPact |
| Range of Product | ComPact NSX100...250 DC ComPact NSX100...250 |
| Product or Component Type | Trip unit |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Range Compatibility | ComPact NSX100 ComPact NSX160 ComPact NSX250 ComPact NSX100 DC |
| Device Application | Distribution |
| Number of poles | 4P |
| Protected poles description | 4t |
| Neutral position | Left |
| Trip unit protection functions | LI |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Trip unit rated current | 63 A 104 °F (40 °C) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz 750 V DC |
| Network type | AC DC |
| Network Frequency | 50/60 Hz |
Complementary
| Characteristic | Value(s) |
|---|---|
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 120â¦400 s 1.5 x In 15 s 6 x Ir |
| Short-time protection pick-up adjustment type Isd | Fixed |
| [Isd] Short-time protection pick-up adjustment range | 500 A |
| Short-time protection delay adjustment type tsd | Fixed |
| Earth-leakage protection | Without |
| Neutral protection settings | 1 x Ir 4t) |

This TM50D is a 4 poles 4d thermal-magnetic trip unit used on Compact NSX 100/160 circuit breakers. This 50A rating thermal-magnetic trip unit is an optimum choice for all distribution applications. It embeds an adjustable thermal overload protection and a fixed magnetic protection against short-circuits. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.
Main
| Characteristic | Value(s) |
|---|---|
| Range | ComPact |
| Range of Product | ComPact NSX100...250 ComPact NSX100...250 DC |
| Product or Component Type | Trip unit |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Range Compatibility | ComPact NSX100 ComPact NSX160 ComPact NSX100 DC |
| Device Application | Distribution |
| Number of poles | 4P |
| Protected poles description | 4t |
| Neutral position | Left |
| Trip unit protection functions | LI |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Trip unit rated current | 50 A 104 °F (40 °C) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz 750 V DC |
| Network type | AC DC |
| Network Frequency | 50/60 Hz |
Complementary
| Characteristic | Value(s) |
|---|---|
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 120â¦400 s 1.5 x In 15 s 6 x Ir |
| Short-time protection pick-up adjustment type Isd | Fixed |
| [Isd] Short-time protection pick-up adjustment range | 500 A |
| Short-time protection delay adjustment type tsd | Fixed |
| Earth-leakage protection | Without |
| Neutral protection settings | 1 x Ir 4t) |

This TM40D is a 4 poles 4d thermal-magnetic trip unit used on Compact NSX 100/160 circuit breakers. This 40A rating thermal-magnetic trip unit is an optimum choice for all distribution applications. It embeds an adjustable thermal overload protection and a fixed magnetic protection against short-circuits. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.
Main
| Characteristic | Value(s) |
|---|---|
| Range | ComPact |
| Range of Product | ComPact NSX100...250 ComPact NSX100...250 DC |
| Product or Component Type | Trip unit |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Range Compatibility | ComPact NSX100 ComPact NSX160 ComPact NSX100 DC |
| Device Application | Distribution |
| Number of poles | 4P |
| Protected poles description | 4t |
| Neutral position | Left |
| Trip unit protection functions | LI |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Trip unit rated current | 40 A 104 °F (40 °C) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz 750 V DC |
| Network type | AC DC |
| Network Frequency | 50/60 Hz |
Complementary
| Characteristic | Value(s) |
|---|---|
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 120â¦400 s 1.5 x In 15 s 6 x Ir |
| Short-time protection pick-up adjustment type Isd | Fixed |
| [Isd] Short-time protection pick-up adjustment range | 500 A |
| Short-time protection delay adjustment type tsd | Fixed |
| Earth-leakage protection | Without |
| Neutral protection settings | 1 x Ir 4t) |

This TM32D is a 4 poles 4d thermal-magnetic trip unit used on Compact NSX 100/160 circuit breakers. This 32A rating thermal-magnetic trip unit is an optimum choice for all distribution applications. It embeds an adjustable thermal overload protection and a fixed magnetic protection against short-circuits. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.
Main
| Characteristic | Value(s) |
|---|---|
| Range | ComPact |
| Range of Product | ComPact NSX100...250 ComPact NSX100...250 DC |
| Product or Component Type | Trip unit |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Range Compatibility | ComPact NSX100 ComPact NSX160 ComPact NSX100 DC |
| Device Application | Distribution |
| Number of poles | 4P |
| Protected poles description | 4t |
| Neutral position | Left |
| Trip unit protection functions | LI |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Trip unit rated current | 32 A 104 °F (40 °C) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz 750 V DC |
| Network type | AC DC |
| Network Frequency | 50/60 Hz |
Complementary
| Characteristic | Value(s) |
|---|---|
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 120â¦400 s 1.5 x In 15 s 6 x Ir |
| Short-time protection pick-up adjustment type Isd | Fixed |
| [Isd] Short-time protection pick-up adjustment range | 400 A |
| Short-time protection delay adjustment type tsd | Fixed |
| Earth-leakage protection | Without |
| Neutral protection settings | 1 x Ir 4t) |

This TM16D is a 4 poles 4d thermal-magnetic trip unit used on Compact NSX 100 circuit breakers. This 16A rating thermal-magnetic trip unit is an optimum choice for all distribution applications. It embeds an adjustable thermal overload protection and a fixed magnetic protection against short-circuits. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.
Main
| Characteristic | Value(s) |
|---|---|
| Range | ComPact |
| Range of Product | ComPact NSX100...250 DC ComPact NSX100...250 |
| Product or Component Type | Trip unit |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Range Compatibility | ComPact NSX100 ComPact NSX100 DC |
| Device Application | Distribution |
| Number of poles | 4P |
| Protected poles description | 4t |
| Neutral position | Left |
| Trip unit protection functions | LI |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Trip unit rated current | 16 A 104 °F (40 °C) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz 750 V DC |
| Network type | AC DC |
| Network Frequency | 50/60 Hz |
Complementary
| Characteristic | Value(s) |
|---|---|
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 120â¦400 s 1.5 x In 15 s 6 x Ir |
| Short-time protection pick-up adjustment type Isd | Fixed |
| [Isd] Short-time protection pick-up adjustment range | 190 A |
| Short-time protection delay adjustment type tsd | Fixed |
| Earth-leakage protection | Without |
| Neutral protection settings | 1 x Ir 4t) |

This Micrologic 2.2 is a 3 poles 3d electronic trip unit used on Compact NSX 100/160/250 circuit breakers. This 100A rating electronic trip unit is an optimum choice for all standard and specific applications. It embeds an adjustable long time protection against overloads. It provides also an adjustable short-time protection and a fixed instantaneous protection against short-circuits. Micrologic 2.2 indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.
Main
| Characteristic | Value(s) |
|---|---|
| Range | ComPact |
| Range of Product | ComPact NSX100...250 |
| Product or Component Type | Trip unit |
| Trip unit name | MicroLogic 2.2 |
| Trip unit technology | Electronic |
| Range Compatibility | ComPact NSX100 ComPact NSX160 ComPact NSX250 |
| Device Application | Distribution |
| Number of poles | 3P |
| Protected poles description | 3t |
| Trip unit protection functions | LSoI |
| Protection type | L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection |
| Trip unit rated current | 100 A 104 °F (40 °C) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network Frequency | 50/60 Hz |
Complementary
| Characteristic | Value(s) |
|---|---|
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 40...100 A |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 11 s 7.2 x Ir 16 s 6 x Ir 400 s 1.5 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| [tsd] Short-time protection delay adjustment range | 0.02 s |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 1500 A |
| Earth-leakage protection | Without |
| Zone selective interlocking ZSI | Without |
| Local signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |

trip unit Micrologic 2.2 for Compact NSX 100/160/250 circuit breakers, electronic, rating 40A, 3 poles 3d

trip unit Micrologic 2.2 G for Compact NSX 100/160/250 circuit breakers, electronic, rating 100 A, 3 poles 3d

This Micrologic 2.2 G is a 3 poles 3d electronic trip unit used on Compact NSX 100/160/250 circuit breakers. This 40A rating electronic trip unit is an optimum choice for generator protection applications. It embeds an adjustable long time protection against overloads. It provides also an adjustable short-time protection and a fixed instantaneous protection against short-circuits. Micrologic 2.2 G indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.
Main
| Characteristic | Value(s) |
|---|---|
| Range | ComPact |
| Range of Product | ComPact NSX100...250 |
| Product or Component Type | Trip unit |
| Trip unit name | MicroLogic 2.2 G |
| Trip unit technology | Electronic |
| Range Compatibility | ComPact NSX100 ComPact NSX160 ComPact NSX250 |
| Device Application | Generator |
| Number of poles | 3P |
| Protected poles description | 3t |
| Trip unit protection functions | LSoI |
| Protection type | L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection |
| Trip unit rated current | 40 A 104 °F (40 °C) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network Frequency | 50/60 Hz |
Complementary
| Characteristic | Value(s) |
|---|---|
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 18...40 A |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 15 s 1.5 x Ir 0.35 s 7.2 x Ir 0.5 s 6 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable |
| [Isd] Short-time protection pick-up adjustment range | 1.5...9 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| [tsd] Short-time protection delay adjustment range | 0.14 s |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 600 A |
| Earth-leakage protection | Without |
| Zone selective interlocking ZSI | Without |
| Local signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |

trip unit Micrologic 2.2 for Compact NSX 100/160/250 circuit breakers, electronic, rating 100A, 4 poles 4d

This Micrologic 2.2 is a 4 poles 4d electronic trip unit used on Compact NSX 100/160/250 circuit breakers. This 40A rating electronic trip unit is an optimum choice for all standard and specific applications. It embeds an adjustable long time protection against overloads. It provides also an adjustable short-time protection and a fixed instantaneous protection against short-circuits. Micrologic 2.2 indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.
Main
| Characteristic | Value(s) |
|---|---|
| Range | ComPact |
| Range of Product | ComPact NSX100...250 |
| Product or Component Type | Trip unit |
| Trip unit name | MicroLogic 2.2 |
| Trip unit technology | Electronic |
| Range Compatibility | ComPact NSX100 ComPact NSX160 ComPact NSX250 |
| Device Application | Distribution |
| Number of poles | 4P |
| Protected poles description | 3t 3t + N/2 4t |
| Neutral position | Left |
| Trip unit protection functions | LSoI |
| Protection type | L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection |
| Trip unit rated current | 40 A 104 °F (40 °C) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network Frequency | 50/60 Hz |
Complementary
| Characteristic | Value(s) |
|---|---|
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 18...40 A |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 11 s 7.2 x Ir 16 s 6 x Ir 400 s 1.5 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| [tsd] Short-time protection delay adjustment range | 0.02 s |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 600 A |
| Earth-leakage protection | Without |
| Neutral protection settings | 0.5 x Ir 3t + N/2) 1 x Ir 4t) No protection 3t) |
| Zone selective interlocking ZSI | Without |
| Local signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |

trip unit Micrologic 2.2 G for Compact NSX 100/160/250 circuit breakers, electronic, rating 100 A, 4 poles 4d

trip unit Micrologic 2.2 G for Compact NSX 100/160/250 circuit breakers, electronic, rating 40 A, 4 poles 4d

trip unit Micrologic 5.2 A-Z for Compact NSX 100/160/250 circuit breakers, electronic, rating 100 A, 3 poles 3d

trip unit Micrologic 5.2 A for Compact NSX 100/160/250 circuit breakers, electronic, rating 100A, 3 poles 3d

This Micrologic 5.2 A (Ammeter) is a 3 poles 3d electronic trip unit used on Compact NSX 100/160/250 circuit breakers. This 40A rating electronic trip unit is an optimum choice for all standard and specific applications. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 5.2 A indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. Micrologic 5.2 A is equipped with a display module that gives current measurement and allows fine adjustment settings. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.
Main
| Characteristic | Value(s) |
|---|---|
| Range | ComPact |
| Range of Product | ComPact NSX100...250 |
| Product or Component Type | Trip unit |
| Trip unit name | MicroLogic 5.2 A |
| Trip unit technology | Electronic |
| Range Compatibility | ComPact NSX100 ComPact NSX160 ComPact NSX250 |
| Device Application | Distribution |
| Number of poles | 3P |
| Protected poles description | 3t |
| Trip unit protection functions | LSI |
| Protection type | L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection |
| Trip unit rated current | 40 A 104 °F (40 °C) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network Frequency | 50/60 Hz |
Complementary
| Characteristic | Value(s) |
|---|---|
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 18...40 A |
| Long-time protection delay adjustment type tr | Adjustable |
| [tr] long-time protection delay adjustment range | 15â¦400 s 1.5 x Ir 0.35â¦11 s 7.2 x Ir 0.5â¦16 s 6 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Adjustable |
| [tsd] Short-time protection delay adjustment range | 0â¦0.4 s I²t=off 0.1â¦0.4 s I²t=on |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 1.5...15 x In |
| Earth-leakage protection | Without |
| Zone selective interlocking ZSI | With |
| Local signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |
| Display Type | LCD display |
| Type of Measurement | Ammeter |
| Communication of data | Maximeters/minimeters Demand current and power Maintenance indicators Energy metering Instantaneous and demand values Protection and alarm settings Power quality Time-stamped histories and event tables |
| Electrical data recording | Maintenance indicators |

trip unit Micrologic 5.2 E for Compact NSX 100/160/250 circuit breakers, electronic, rating 100A, 3 poles 3d

trip unit Micrologic 5.2 E for Compact NSX 100/160/250 circuit breakers, electronic, rating 40A, 3 poles 3d

This Micrologic 5.2 A (Ammeter) is a 4 poles 4d electronic trip unit used on Compact NSX 100/160/250 circuit breakers. This 100A rating electronic trip unit is an optimum choice for all standard and specific applications. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 5.2 A indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. Micrologic 5.2 A is equipped with a display module that gives current measurement and allows fine adjustment settings. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.
Main
| Characteristic | Value(s) |
|---|---|
| Range | ComPact |
| Range of Product | ComPact NSX100...250 |
| Product or Component Type | Trip unit |
| Trip unit name | MicroLogic 5.2 A |
| Trip unit technology | Electronic |
| Range Compatibility | ComPact NSX100 ComPact NSX160 ComPact NSX250 |
| Device Application | Distribution |
| Number of poles | 4P |
| Protected poles description | 3t + OSN 4t 3t + N/2 3t |
| Neutral position | Left |
| Trip unit protection functions | LSI |
| Protection type | L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection |
| Trip unit rated current | 100 A 104 °F (40 °C) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network Frequency | 50/60 Hz |
Complementary
| Characteristic | Value(s) |
|---|---|
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 40...100 A |
| Long-time protection delay adjustment type tr | Adjustable |
| [tr] long-time protection delay adjustment range | 15â¦400 s 1.5 x Ir 0.35â¦11 s 7.2 x Ir 0.5â¦16 s 6 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Adjustable |
| [tsd] Short-time protection delay adjustment range | 0â¦0.4 s I²t=off 0.1â¦0.4 s I²t=on |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 1.5...15 x In |
| Earth-leakage protection | Without |
| Neutral protection settings | 0.5 x Ir 3t + N/2) 1 x Ir 4t) 1.6 x Ir 3t + OSN) No protection 3t) |
| Zone selective interlocking ZSI | With |
| Local signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |
| Display Type | LCD display |
| Type of Measurement | Ammeter |
| Communication of data | Protection and alarm settings Maximeters/minimeters Instantaneous and demand values Demand current and power Maintenance indicators Power quality Energy metering Time-stamped histories and event tables |
| Electrical data recording | Maintenance indicators |

This Micrologic 5.2 A (Ammeter) is a 4 poles 4d electronic trip unit used on Compact NSX 100/160/250 circuit breakers. This 40A rating electronic trip unit is an optimum choice for all standard and specific applications. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 5.2 A indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. Micrologic 5.2 A is equipped with a display module that gives current measurement and allows fine adjustment settings. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.
Main
| Characteristic | Value(s) |
|---|---|
| Range | ComPact |
| Range of Product | ComPact NSX100...250 |
| Product or Component Type | Trip unit |
| Trip unit name | MicroLogic 5.2 A |
| Trip unit technology | Electronic |
| Range Compatibility | ComPact NSX100 ComPact NSX160 ComPact NSX250 |
| Device Application | Distribution |
| Number of poles | 4P |
| Protected poles description | 3t + N/2 3t + OSN 3t 4t |
| Neutral position | Left |
| Trip unit protection functions | LSI |
| Protection type | L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection |
| Trip unit rated current | 40 A 104 °F (40 °C) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network Frequency | 50/60 Hz |
Complementary
| Characteristic | Value(s) |
|---|---|
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 18...40 A |
| Long-time protection delay adjustment type tr | Adjustable |
| [tr] long-time protection delay adjustment range | 15â¦400 s 1.5 x Ir 0.35â¦11 s 7.2 x Ir 0.5â¦16 s 6 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Adjustable |
| [tsd] Short-time protection delay adjustment range | 0â¦0.4 s I²t=off 0.1â¦0.4 s I²t=on |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 1.5...15 x In |
| Earth-leakage protection | Without |
| Neutral protection settings | 0.5 x Ir 3t + N/2) 1 x Ir 4t) 1.6 x Ir 3t + OSN) No protection 3t) |
| Zone selective interlocking ZSI | With |
| Local signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |
| Display Type | LCD display |
| Type of Measurement | Ammeter |
| Communication of data | Maximeters/minimeters Power quality Time-stamped histories and event tables Energy metering Demand current and power Maintenance indicators Protection and alarm settings Instantaneous and demand values |
| Electrical data recording | Maintenance indicators |

This Micrologic 5.2 E (Energy) is a 4 poles 4d electronic trip unit used on Compact NSX 100/160/250 circuit breakers. This 100A rating electronic trip unit is an optimum choice for all standard and specific applications. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 5.2 E indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. Micrologic 5.2 E is equipped with a display module that gives energy measurement and allows fine adjustment settings. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.
Main
| Characteristic | Value(s) |
|---|---|
| Range | ComPact |
| Range of Product | ComPact NSX100...250 |
| Product or Component Type | Trip unit |
| Trip unit name | MicroLogic 5.2 E |
| Trip unit technology | Electronic |
| Range Compatibility | ComPact NSX100 ComPact NSX160 ComPact NSX250 |
| Device Application | Distribution |
| Number of poles | 4P |
| Protected poles description | 3t + N/2 3t + OSN 4t 3t |
| Neutral position | Left |
| Trip unit protection functions | LSI |
| Protection type | L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection |
| Trip unit rated current | 100 A 104 °F (40 °C) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network Frequency | 50/60 Hz |
Complementary
| Characteristic | Value(s) |
|---|---|
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 40...100 A |
| Long-time protection delay adjustment type tr | Adjustable |
| [tr] long-time protection delay adjustment range | 15â¦400 s 1.5 x Ir 0.35â¦11 s 7.2 x Ir 0.5â¦16 s 6 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Adjustable |
| [tsd] Short-time protection delay adjustment range | 0â¦0.4 s I²t=off 0.1â¦0.4 s I²t=on |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 1.5...15 x In |
| Earth-leakage protection | Without |
| Neutral protection settings | 0.5 x Ir 3t + N/2) 1 x Ir 4t) 1.6 x Ir 3t + OSN) No protection 3t) |
| Zone selective interlocking ZSI | With |
| Local signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |
| Display Type | LCD display |
| Type of Measurement | Energy meter |
| Communication of data | Instantaneous and demand values Maintenance indicators Energy metering Demand current and power Maximeters/minimeters Time-stamped histories and event tables Power quality Protection and alarm settings |
| Electrical data recording | Maintenance indicators |