This product is part of the Modicon TM3 range, an offer of expansion I/O modules for Modicon M221, M241, M251 and M262. The discrete output module provides 8 transistor outputs with sink (negative)logic. It is an output module with an output voltage of 24V DC and a current consumption of 20mA at 24V DC via bus connector. This product is capable of controlling variable speed drives or any device equipped with a current or voltage input. There is an insulation between output and internal logic at 2300V AC, outputs at 750V AC, output groups at 1500V AC. It is furnished with removable screw terminal for electrical connection with 5.08mm pitch adjustment for outputs. It is an IP20 rated product. Its dimensions are 27.4mm (Width) x 84.6mm (Depth) x 90mm (Height). It weighs 0.76kg. This product is certified by CE, CULus and C-Tick. It meets EN/IEC 61131-2 and EN/IEC 61010-2-201 standards. This module is compatible with Modicon M241, Modicon M251 and Modicon M221 logic controller. It supports top hat type TH35-15, top hat type TH35-7.5 rail conforming to IEC 60715 and plate or panel with fixing kit mount. Modicon TM3 expansion modules have been designed with a simple interlocking assembly mechanism. A bus expansion connector is used to distribute data and the power supply when assembling the Modicon TM3 modules with logic controllers. Boost the performance of your controller with the Modicon TM3 I/O system specially designed for the Modicon M221, M241 and M251 logic controllers.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 |
| Product or Component Type | Discrete output module |
| Range Compatibility | Modicon M241 Modicon M251 Modicon M221 Modicon M262 |
| Discrete output type | Transistor |
| Discrete output number | 8 |
| Discrete output logic | Negative logic (sink) |
| Discrete output voltage | 24 V DC transistor output |
| Discrete output current | 50 mA transistor output |
Complementary
| Characteristic | Value(s) |
|---|---|
| Discrete I/O number | 8 |
| Current consumption | 5 mA 5 V DC via bus connector at state off) 0 mA 24 V DC via bus connector at state off) 20 mA 24 V DC via bus connector at state on) 10 mA 5 V DC via bus connector at state on) |
| Response time | 450 µs (turn-on) 450 µs (turn-off) |
| Maximum leakage current | 0.1 mA transistor output |
| Maximum voltage drop | <0.4 V |
| Local signalling | 1 LED per channel (green) for output status |
| Electrical connection | 11 x 2.5 mm² removable screw terminal block pitch 5.08 mm for outputs |
| Maximum cable distance between devices | Unshielded cable <98.4 ft (30 m) transistor output |
| Insulation | Between output and internal logic 500 V AC Non-insulated between outputs |
| Marking | CE |
| Mounting support | Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit |
| Height | 3.5 in (90 mm) |
| Depth | 3.3 in (84.6 mm) |
| Width | 1.08 in (27.4 mm) |
| Product Weight | 1.68 lb(US) (0.76 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 |
| Product or Component Type | Discrete output module |
| Range Compatibility | Modicon M241 Modicon M251 Modicon M221 Modicon M262 |
| Discrete output type | Transistor |
| Discrete output number | 8 |
| Discrete output logic | Negative logic (sink) |
| Discrete output voltage | 24 V DC transistor output |
| Discrete output current | 50 mA transistor output |
Complementary
| Characteristic | Value(s) |
|---|---|
| Discrete I/O number | 8 |
| Current consumption | 5 mA 5 V DC via bus connector at state off) 0 mA 24 V DC via bus connector at state off) 20 mA 24 V DC via bus connector at state on) 10 mA 5 V DC via bus connector at state on) |
| Response time | 450 µs (turn-on) 450 µs (turn-off) |
| Maximum leakage current | 0.1 mA transistor output |
| Maximum voltage drop | <0.4 V |
| Local signalling | 1 LED per channel (green) for output status |
| Electrical connection | 11 x 2.5 mm² removable spring terminal block pitch 5.08 mm for outputs |
| Maximum cable distance between devices | Unshielded cable <98.4 ft (30 m) transistor output |
| Insulation | Between output and internal logic 500 V AC Non-insulated between outputs |
| Marking | CE |
| Mounting support | Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit |
| Height | 3.5 in (90 mm) |
| Depth | 3.3 in (84.6 mm) |
| Width | 1.08 in (27.4 mm) |
| Product Weight | 1.68 lb(US) (0.76 kg) |

This TM3 safety expansion module monitors emergency shutdown pushbuttons and limit switches to conform to PLd / Category 3. It meets the requirements of PL d/Category 3 conforming to EN/ISO 13849-1 and SILCL 2 conforming to EN/IEC 62061. It has a module locking latch, 2 TM3 bus connectors designed to provide continuity of the link between connected modules, a symmetrical rail locking clip, display block for the module channels and diagnostics. It completes your Modicon M221, M241 or M251 PLC configuration with a dedicated safety I/O, without the need to use a complete safety controller. It has removable terminals for easier and better control wires tightening, thus improving installation reliability.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 Safety |
| Product or Component Type | Safety module |
| Device short name | TM3SAC |
| Safety module application | For emergency stop and switch monitoring |
| Function of module | Emergency stop monitoring 1-channel wiring Emergency stop monitoring 2-channel wiring Monitoring of a movable guard with 2 switches and automatic start |
| Safety level | Can reach PL d/category 3 ISO 13849-1 2008 Can reach PL d/category 3 ISO 13849-2 2012 Can reach SILCL 2 IEC 62061 2005 Can reach SIL 2 IEC 61508 2010 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Safety reliability data | DC = 95 % ISO 13849-1 PFHd = 5E-9 1/h IEC 61508-1 1 operation/hour DC-13 24 V DC, <4 A PFHd = 30E-9 1/h IEC 61508-1 60 operations/hour DC-13 24 V DC, <1 A MTTFd = 500 years ISO 13849-1 1 operation/hour DC-13 24 V DC, <4 A MTTFd = 85 years ISO 13849-1 60 operations/hour DC-13 24 V DC, <1 A SFF = 95 % IEC 61508-1 HFT = 1 IEC 61508-1 Type = A IEC 61508-1 |
| Synchronisation time between inputs | Unlimited |
| Connections - terminals | Captive screw clamp terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² flexible without cable end 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² solid without cable end 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, with bezel 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 2 x 0.2...2 x 1.5 mm² flexible without cable end 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 2 x 0.2...2 x 1.5 mm² solid without cable end 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 2 x 0.25...2 x 1 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² flexible without cable end other terminals Captive screw clamp terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² solid without cable end other terminals Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 0.5 mm² flexible with cable end, with bezel other terminals Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 1.5 mm² flexible with cable end, without bezel other terminals Captive screw clamp terminals, removable terminal block 2 x 0.14...2 x 0.5 mm² flexible without cable end other terminals Captive screw clamp terminals, removable terminal block 2 x 0.14...2 x 0.75 mm² solid without cable end other terminals Captive screw clamp terminals, removable terminal block 2 x 0.25...2 x 0.34 mm² flexible with cable end, without bezel other terminals Captive screw clamp terminals, removable terminal block 2 x 0.5 mm² flexible with cable end, with double bezel other terminals |
| Output type | Relay instantaneous opening, 3 NO, potential free |
| Number of safety circuits | 3 NO relay instantaneous opening |
| Maximum switching voltage | 230 V AC-15 50 Hz relay instantaneous opening) 24 V DC-13 relay instantaneous opening) |
| [Us] rated supply voltage | 24 V - 15...20 % DC |
| Power consumption in W | 0.2 W 5 V DC 3.6 W 24 V DC |
| Input protection type | Internal, electronic |
| [Uc] control circuit voltage | 24 V DC |
| Maximum cable distance between devices | 98.4 ft (30 m) |
| Breaking capacity | 360 VA holding AC-15 B300 relay output 3600 VA inrush AC-15 B300 relay output |
| Breaking capacity | 4 A 24 V 50 ms DC-13 relay output |
| Output thermal current | 6 A per relay relay output |
| [Ith] conventional free air thermal current | 18 A |
| Associated fuse rating | 4 A gG or gL relay output IEC 60947-5-1 6 A fast blow relay output IEC 60947-5-1 |
| Minimum output current | 10 mA relay output |
| Output voltage | 10 V relay output |
| Maximum response time on input open | 40 ms |
| [Ui] rated insulation voltage | 300 V 2)IEC 60647-5-1 |
| [Uimp] rated impulse withstand voltage | 4 kV III IEC 60647-5-1 |
| Current consumption | 100 mA 24 V DC external supply at state on) |
| Local signalling | 6 LEDs (green/red) for user |
| Electrical Connection | Screw terminal |
| Standards | ISO 13849-1:2008 ISO 13849-2:2012 IEC 62061:2005 IEC 61508:2010 IEC 60947-5-1:2010 IEC 61131-2:2007 IEC 60204-1:2005 IEC 60204-1:2009/A1 IEC 61010-1:2010 EN 50581:2012 |
| Product Certifications | TÃV CSA 61010-2-201 (pending) CSA Haz Loc Class 1 Division 2 (pending) RCM ANSI Haz Loc Class 1 Division 2 (pending) EAC UL 61010-2-201 |
| Marking | EFUP 10 RCM CSA UL TÃV CE EAC |
| Electromagnetic compatibility | Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2 Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz to 1 GHz) conforming to IEC 61000-4-3 Susceptibility to electromagnetic fields - test level: 3 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3 Susceptibility to electromagnetic fields - test level: 1 V/m (2 GHz...3 GHz) conforming to IEC 61000-4-3 Magnetic field at power frequency - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8 Electrical fast transient/burst immunity test - test level: 3 kV (power lines (DC)) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV (I/O) conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to IEC 61000-4-5 Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6 Radiated emission - test level: 40 dBµV/m class A (24 V) conforming to IEC 55011 Radiated emission - test level: 47 dBµV/m class A (24 V) conforming to IEC 55011 |
| Mounting support | Top hat type TH35-7.5 rail IEC 60715 Top hat type TH35-15 rail IEC 60715 wall mount using attached fasteners |
| Height | 3.7 in (94 mm) |
| Depth | 2.9 in (73 mm) |
| Width | 1.7 in (43.7 mm) |
| Product Weight | 0.42 lb(US) (0.19 kg) |

This TM3 safety expansion module monitors emergency shutdown pushbuttons and limit switches. It meets the requirements of PL e/Category 4 conforming to EN/ISO 13849-1 and SILCL3 conforming to EN/IEC 62061. It has a module locking latch, 2 TM3 bus connectors designed to provide continuity of the link between connected modules, a symmetrical rail locking clip, display block for the module channels and diagnostics. It completes your Modicon M221, M241 or M251 PLC configuration with a dedicated safety I/O, without the need to use a complete safety controller. It has removable terminals for easier and better control wires tightening, thus improving installation reliability.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 Safety |
| Product or Component Type | Safety module |
| Device short name | TM3SAF |
| Safety module application | For emergency stop and switch monitoring |
| Function of module | Emergency stop monitoring 1-channel wiring Emergency stop monitoring 2-channel wiring Monitoring of a movable guard with 2 switches and automatic start |
| Safety level | Can reach PL e/category 4 ISO 13849-1 2008 Can reach PL e/category 4 ISO 13849-2 2012 Can reach SILCL 3 IEC 62061 2005 Can reach SIL 3 IEC 61508 2010 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Safety reliability data | DC = 95 % ISO 13849-1 PFHd = 5E-9 1/h IEC 61508-1 1 operation/hour DC-13 24 V DC, <4 A PFHd = 30E-9 1/h IEC 61508-1 60 operations/hour DC-13 24 V DC, <1 A MTTFd = 500 years ISO 13849-1 1 operation/hour DC-13 24 V DC, <4 A MTTFd = 85 years ISO 13849-1 60 operations/hour DC-13 24 V DC, <1 A SFF = 95 % IEC 61508-1 HFT = 1 IEC 61508-1 Type = A IEC 61508-1 |
| Synchronisation time between inputs | Unlimited |
| Connections - terminals | Captive screw clamp terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² flexible without cable end 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² solid without cable end 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, with bezel 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 2 x 0.2...2 x 1.5 mm² flexible without cable end 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 2 x 0.2...2 x 1.5 mm² solid without cable end 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 2 x 0.25...2 x 1 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² flexible without cable end other terminals Captive screw clamp terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² solid without cable end other terminals Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 0.5 mm² flexible with cable end, with bezel other terminals Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 1.5 mm² flexible with cable end, without bezel other terminals Captive screw clamp terminals, removable terminal block 2 x 0.14...2 x 0.5 mm² flexible without cable end other terminals Captive screw clamp terminals, removable terminal block 2 x 0.14...2 x 0.75 mm² solid without cable end other terminals Captive screw clamp terminals, removable terminal block 2 x 0.25...2 x 0.34 mm² flexible with cable end, without bezel other terminals Captive screw clamp terminals, removable terminal block 2 x 0.5 mm² flexible with cable end, with double bezel other terminals |
| Output type | Relay instantaneous opening, 3 NO, potential free |
| Number of safety circuits | 3 NO relay instantaneous opening |
| Maximum switching voltage | 230 V AC-15 50 Hz relay instantaneous opening) 24 V DC-13 relay instantaneous opening) |
| [Us] rated supply voltage | 24 V - 15...20 % DC |
| Power consumption in W | 0.2 W 5 V DC 3.6 W 24 V DC |
| Input protection type | Internal, electronic |
| [Uc] control circuit voltage | 24 V DC |
| Maximum cable distance between devices | 98.4 ft (30 m) |
| Breaking capacity | 360 VA holding AC-15 B300 relay output 3600 VA inrush AC-15 B300 relay output |
| Breaking capacity | 4 A 24 V 50 ms DC-13 relay output |
| Output thermal current | 6 A per relay relay output |
| [Ith] conventional free air thermal current | 18 A |
| Associated fuse rating | 4 A gG or gL relay output IEC 60947-5-1 6 A fast blow relay output IEC 60947-5-1 |
| Minimum output current | 10 mA relay output |
| Output voltage | 10 V relay output |
| Maximum response time on input open | 40 ms |
| [Ui] rated insulation voltage | 300 V 2)IEC 60647-5-1 |
| [Uimp] rated impulse withstand voltage | 4 kV III IEC 60647-5-1 |
| Current consumption | 100 mA 24 V DC external supply |
| Local signalling | 8 LEDs (green/red) for user |
| Electrical Connection | Screw terminal |
| Standards | ISO 13849-1:2008 ISO 13849-2:2012 IEC 62061:2005 IEC 61508:2010 IEC 60947-5-1:2010 IEC 61131-2:2007 IEC 60204-1:2005 IEC 60204-1:2009/A1 IEC 61010-1:2010 EN 50581:2012 |
| Product Certifications | EAC CSA Haz Loc Class 1 Division 2 (pending) RCM TÃV UL 61010-2-201 CSA 61010-2-201 (pending) ANSI Haz Loc Class 1 Division 2 (pending) |
| Marking | CE UL EFUP 10 EAC RCM TÃV CSA |
| Electromagnetic compatibility | Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2 Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz to 1 GHz) conforming to IEC 61000-4-3 Susceptibility to electromagnetic fields - test level: 3 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3 Susceptibility to electromagnetic fields - test level: 1 V/m (2 GHz...3 GHz) conforming to IEC 61000-4-3 Magnetic field at power frequency - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8 Electrical fast transient/burst immunity test - test level: 3 kV (power lines (DC)) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV (I/O) conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to IEC 61000-4-5 Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6 Radiated emission - test level: 40 dBµV/m class A (24 V) conforming to IEC 55011 Radiated emission - test level: 47 dBµV/m class A (24 V) conforming to IEC 55011 |
| Mounting support | Top hat type TH35-7.5 rail IEC 60715 Top hat type TH35-15 rail IEC 60715 wall mount using attached fasteners |
| Height | 3.7 in (94 mm) |
| Depth | 2.9 in (73 mm) |
| Width | 1.7 in (43.7 mm) |
| Product Weight | 0.42 lb(US) (0.19 kg) |

This TM3 safety expansion module monitors emergency shutdown pushbuttons, limit switches and light curtains to conform to PLd / Category 3. It meets the requirements of PL d/Category 3 conforming to EN/ISO 13849-1 and SILCL 2 conforming to EN/IEC 62061. It has a module locking latch, 2 TM3 bus connectors designed to provide continuity of the link between connected modules, a symmetrical rail locking clip, display block for the module channels and diagnostics. It completes your Modicon M221, M241 or M251 PLC configuration with a dedicated safety I/O, without the need to use a complete safety controller. It has removable terminals for easier and better control wires tightening, thus improving installation reliability. It is compatible with emergency push buttons, limit switches and safety light curtains, the 3 most common safety sensors in the industry.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 Safety |
| Product or Component Type | Safety module |
| Device short name | TM3SAFL |
| Safety module application | For emergency stop, switch and safety light curtain monitoring |
| Function of module | Emergency stop monitoring 2-channel wiring Monitoring of a movable guard with 2 switches and automatic start Monitoring of a movable guard Multiple emergency stop monitoring 2-channel wiring Proximity sensor monitoring PNP/PNP Monitoring of electro-sensitive protection equipment (ESPE) PNP/PNP |
| Safety level | Can reach PL d/category 3 ISO 13849-1 2008 Can reach PL d/category 3 ISO 13849-2 2012 Can reach SILCL 2 IEC 62061 2005 Can reach SIL 2 IEC 61508 2010 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Safety reliability data | DC = 95 % ISO 13849-1 PFHd = 5E-9 1/h IEC 61508-1 1 operation/hour DC-13 24 V DC, <4 A PFHd = 30E-9 1/h IEC 61508-1 60 operations/hour DC-13 24 V DC, <1 A MTTFd = 500 years ISO 13849-1 1 operation/hour DC-13 24 V DC, <4 A MTTFd = 85 years ISO 13849-1 60 operations/hour DC-13 24 V DC, <1 A SFF = 95 % IEC 61508-1 HFT = 1 IEC 61508-1 Type = A IEC 61508-1 |
| Synchronisation time between inputs | Unlimited |
| Connections - terminals | Captive screw clamp terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² flexible without cable end 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² solid without cable end 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, with bezel 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 2 x 0.2...2 x 1.5 mm² flexible without cable end 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 2 x 0.2...2 x 1.5 mm² solid without cable end 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 2 x 0.25...2 x 1 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² flexible without cable end other terminals Captive screw clamp terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² solid without cable end other terminals Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 0.5 mm² flexible with cable end, with bezel other terminals Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 1.5 mm² flexible with cable end, without bezel other terminals Captive screw clamp terminals, removable terminal block 2 x 0.14...2 x 0.5 mm² flexible without cable end other terminals Captive screw clamp terminals, removable terminal block 2 x 0.14...2 x 0.75 mm² solid without cable end other terminals Captive screw clamp terminals, removable terminal block 2 x 0.25...2 x 0.34 mm² flexible with cable end, without bezel other terminals Captive screw clamp terminals, removable terminal block 2 x 0.5 mm² flexible with cable end, with double bezel other terminals |
| Output type | Relay instantaneous opening, 3 NO, potential free |
| Number of safety circuits | 3 NO relay instantaneous opening |
| Maximum switching voltage | 230 V AC-15 50 Hz relay instantaneous opening) 24 V DC-13 relay instantaneous opening) |
| [Us] rated supply voltage | 24 V - 15...20 % DC |
| Power consumption in W | 0.2 W 5 V DC 3.6 W 24 V DC |
| Input protection type | Internal, electronic |
| [Uc] control circuit voltage | 24 V DC |
| Maximum cable distance between devices | 98.4 ft (30 m) |
| Breaking capacity | 360 VA holding AC-15 B300 relay output 3600 VA inrush AC-15 B300 relay output |
| Breaking capacity | 4 A 24 V 50 ms DC-13 relay output |
| Output thermal current | 6 A per relay relay output |
| [Ith] conventional free air thermal current | 18 A |
| Associated fuse rating | 4 A gG or gL relay output IEC 60947-5-1 6 A fast blow relay output IEC 60947-5-1 |
| Minimum output current | 10 mA relay output |
| Output voltage | 10 V relay output |
| Maximum response time on input open | 40 ms |
| [Ui] rated insulation voltage | 300 V 2)IEC 60647-5-1 |
| [Uimp] rated impulse withstand voltage | 4 kV III IEC 60647-5-1 |
| Current consumption | 100 mA 24 V DC external supply |
| Local signalling | 8 LEDs (green/red) for user |
| Electrical Connection | Screw terminal |
| Product compatibility | Safety light curtains EN/IEC 61496-1 (type 4) |
| Standards | ISO 13849-1:2008 ISO 13849-2:2012 IEC 62061:2005 IEC 61508:2010 IEC 60947-5-1:2010 IEC 61131-2:2007 IEC 60204-1:2005 IEC 60204-1:2009/A1 IEC 61010-1:2010 EN 50581:2012 |
| Product Certifications | TÃV RCM ANSI Haz Loc Class 1 Division 2 (pending) CSA Haz Loc Class 1 Division 2 (pending) EAC CSA 61010-2-201 (pending) UL 61010-2-201 |
| Marking | CE EFUP 10 UL CSA EAC RCM TÃV |
| Electromagnetic compatibility | Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2 Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz to 1 GHz) conforming to IEC 61000-4-3 Susceptibility to electromagnetic fields - test level: 3 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3 Susceptibility to electromagnetic fields - test level: 1 V/m (2 GHz...3 GHz) conforming to IEC 61000-4-3 Magnetic field at power frequency - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8 Electrical fast transient/burst immunity test - test level: 3 kV (power lines (DC)) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV (I/O) conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to IEC 61000-4-5 Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6 Radiated emission - test level: 40 dBµV/m class A (24 V) conforming to IEC 55011 Radiated emission - test level: 47 dBµV/m class A (24 V) conforming to IEC 55011 |
| Mounting support | Top hat type TH35-7.5 rail IEC 60715 Top hat type TH35-15 rail IEC 60715 wall mount using attached fasteners |
| Height | 3.7 in (94 mm) |
| Depth | 2.9 in (73 mm) |
| Width | 1.7 in (43.7 mm) |
| Product Weight | 0.42 lb(US) (0.19 kg) |

This product is part of the Modicon TM3 range, an offer of expansion I/O modules for Modicon M221, M241, M251 and M262. The safety module provides 3 normally opened contacts and unlimited synchronisation time between inputs. It is a safety module with a rated supply voltage of 24V DC, an external supply current consumption of 100mA at 24V DC on power supply and a power consumption 0.2W at 5V DC, 3.6W at 24V DC. The main functions of this module are emergency stop, movable guard, multiple emergency stop, proximity sensor and electro-sensitive protection equipment (ESPE) monitoring. It is furnished with spring terminal for electrical connection. It is an IP20 rated product. Its dimensions are 43.7mm (Width) x 73mm (Depth) x 94mm (Height). It weighs 0.19kg. It is suitable for emergency stop, switch and safety light curtain monitoring applications. This product is certified by RCM, CSA, UL, TÃV, ANSI Haz Loc Class 1 Division 2, EAC. It supports wall mount using attached fasteners. Modicon TM3 expansion modules have been designed with a simple interlocking assembly mechanism. A bus expansion connector is used to distribute data and the power supply when assembling the Modicon TM3 modules with logic controllers. Boost the performance of your controller with the Modicon TM3 I/O system specially designed for the Modicon M221, M241 and M251 logic controllers.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 Safety |
| Product or Component Type | Safety module |
| Device short name | TM3SAFL |
| Safety module application | For emergency stop, switch and safety light curtain monitoring |
| Function of module | Emergency stop monitoring 2-channel wiring Monitoring of a movable guard with 2 switches and automatic start Monitoring of a movable guard Multiple emergency stop monitoring 2-channel wiring Proximity sensor monitoring PNP/PNP Monitoring of electro-sensitive protection equipment (ESPE) PNP/PNP |
| Safety level | Can reach PL d/category 3 ISO 13849-1 2008 Can reach PL d/category 3 ISO 13849-2 2012 Can reach SILCL 2 IEC 62061 2005 Can reach SIL 2 IEC 61508 2010 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Safety reliability data | DC = 95 % ISO 13849-1 PFHd = 5E-9 1/h IEC 61508-1 1 operation/hour DC-13 24 V DC, <4 A PFHd = 30E-9 1/h IEC 61508-1 60 operations/hour DC-13 24 V DC, <1 A MTTFd = 500 years ISO 13849-1 1 operation/hour DC-13 24 V DC, <4 A MTTFd = 85 years ISO 13849-1 60 operations/hour DC-13 24 V DC, <1 A SFF = 95 % IEC 61508-1 HFT = 1 IEC 61508-1 Type = A IEC 61508-1 |
| Synchronisation time between inputs | Unlimited |
| Connections - terminals | Captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² flexible without cable end 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² solid without cable end 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, with bezel 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² flexible without cable end other terminals Captive spring terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² solid without cable end other terminals Captive spring terminals, removable terminal block 1 x 0.25...1 x 0.5 mm² flexible with cable end, with bezel other terminals Captive spring terminals, removable terminal block 1 x 0.25...1 x 1.5 mm² flexible with cable end, without bezel other terminals |
| Output type | Relay instantaneous opening, 3 NO, potential free |
| Number of safety circuits | 3 NO relay instantaneous opening |
| Maximum switching voltage | 230 V AC-15 50 Hz relay instantaneous opening) 24 V DC-13 relay instantaneous opening) |
| [Us] rated supply voltage | 24 V - 15...20 % DC |
| Power consumption in W | 0.2 W 5 V DC 3.6 W 24 V DC |
| Input protection type | Internal, electronic |
| [Uc] control circuit voltage | 24 V DC |
| Maximum cable distance between devices | 98.4 ft (30 m) |
| Breaking capacity | 360 VA holding AC-15 B300 relay output 3600 VA inrush AC-15 B300 relay output |
| Breaking capacity | 4 A 24 V 50 ms DC-13 relay output |
| Output thermal current | 6 A per relay relay output |
| [Ith] conventional free air thermal current | 18 A |
| Associated fuse rating | 4 A gG or gL relay output IEC 60947-5-1 6 A fast blow relay output IEC 60947-5-1 |
| Minimum output current | 10 mA relay output |
| Output voltage | 10 V relay output |
| Maximum response time on input open | 40 ms |
| [Ui] rated insulation voltage | 300 V 2)IEC 60647-5-1 |
| [Uimp] rated impulse withstand voltage | 4 kV III IEC 60647-5-1 |
| Current consumption | 100 mA 24 V DC external supply |
| Local signalling | 8 LEDs (green/red) for user |
| Electrical Connection | Spring terminal |
| Product compatibility | Safety light curtains EN/IEC 61496-1 (type 4) |
| Standards | ISO 13849-1:2008 ISO 13849-2:2012 IEC 62061:2005 IEC 61508:2010 IEC 60947-5-1:2010 IEC 61131-2:2007 IEC 60204-1:2005 IEC 60204-1:2009/A1 IEC 61010-1:2010 EN 50581:2012 |
| Product Certifications | CSA 61010-2-201 (pending) RCM UL 61010-2-201 EAC ANSI Haz Loc Class 1 Division 2 (pending) CSA Haz Loc Class 1 Division 2 (pending) TÃV |
| Marking | RCM UL CSA EAC CE TÃV EFUP 10 |
| Electromagnetic compatibility | Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2 Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz to 1 GHz) conforming to IEC 61000-4-3 Susceptibility to electromagnetic fields - test level: 3 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3 Susceptibility to electromagnetic fields - test level: 1 V/m (2 GHz...3 GHz) conforming to IEC 61000-4-3 Magnetic field at power frequency - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8 Electrical fast transient/burst immunity test - test level: 3 kV (power lines (DC)) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV (I/O) conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to IEC 61000-4-5 Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6 Radiated emission - test level: 40 dBµV/m class A (24 V) conforming to IEC 55011 Radiated emission - test level: 47 dBµV/m class A (24 V) conforming to IEC 55011 |
| Mounting support | Top hat type TH35-7.5 rail IEC 60715 Top hat type TH35-15 rail IEC 60715 wall mount using attached fasteners |
| Height | 3.7 in (94 mm) |
| Depth | 2.9 in (73 mm) |
| Width | 1.7 in (43.7 mm) |
| Product Weight | 0.42 lb(US) (0.19 kg) |

This TM3 safety expansion module monitors emergency shutdown pushbuttons, limit switches, light curtains and safety mats/edges. It meets the requirements of PL e/Category 4 conforming to EN/ISO 13849-1 and SILCL3 conforming to EN/IEC 62061. It has a module locking latch, 2 TM3 bus connectors designed to provide continuity of the link between connected modules, a symmetrical rail locking clip, display block for the module channels and diagnostics. It completes your Modicon M221, M241 or M251 PLC configuration with a dedicated safety I/O, without the need to use a complete safety controller. It has removable terminals for easier and better control wires tightening, thus improving installation reliability. It is compatible with emergency push buttons, limit switches, safety light curtains and safety mats/edges, the 4 most common safety sensors in the industry. It has spring terminals for fast and reliable wiring of safety circuits.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 Safety |
| Product or Component Type | Safety module |
| Device short name | TM3SAK |
| Safety module application | For emergency stop, switch, sensing mat/edges or safety light curtain monitoring |
| Function of module | Emergency stop monitoring 1-channel wiring Emergency stop monitoring 2-channel wiring Monitoring of a movable guard with 2 switches and automatic start Monitoring of a movable guard Multiple emergency stop monitoring 2-channel wiring Proximity sensor monitoring PNP/PNP Proximity sensor monitoring PNP/NPN Sensing mat and edges monitoring Monitoring of electro-sensitive protection equipment (ESPE) PNP/PNP Monitoring of electro-sensitive protection equipment (ESPE) PNP/NPN |
| Safety level | Can reach PL e/category 4 ISO 13849-1 2008 Can reach PL e/category 4 ISO 13849-2 2012 Can reach SILCL 3 IEC 62061 2005 Can reach SIL 3 IEC 61508 2010 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Safety reliability data | DC = 95 % ISO 13849-1 PFHd = 5E-9 1/h IEC 61508-1 1 operation/hour DC-13 24 V DC, <4 A PFHd = 30E-9 1/h IEC 61508-1 60 operations/hour DC-13 24 V DC, <1 A MTTFd = 500 years ISO 13849-1 1 operation/hour DC-13 24 V DC, <4 A MTTFd = 85 years ISO 13849-1 60 operations/hour DC-13 24 V DC, <1 A SFF = 95 % IEC 61508-1 HFT = 1 IEC 61508-1 Type = A IEC 61508-1 |
| Synchronisation time between inputs | Unlimited 2 or 4 s depending of wiring configurable by software |
| Connections - terminals | Captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² flexible without cable end 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² solid without cable end 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, with bezel 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² flexible without cable end other terminals Captive spring terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² solid without cable end other terminals Captive spring terminals, removable terminal block 1 x 0.25...1 x 0.5 mm² flexible with cable end, with bezel other terminals Captive spring terminals, removable terminal block 1 x 0.25...1 x 1.5 mm² flexible with cable end, without bezel other terminals |
| Output type | Relay instantaneous opening, 3 NO, potential free |
| Number of safety circuits | 3 NO relay instantaneous opening |
| Maximum switching voltage | 230 V AC-15 50 Hz relay instantaneous opening) 24 V DC-13 relay instantaneous opening) |
| [Us] rated supply voltage | 24 V - 15...20 % DC |
| Power consumption in W | 0.2 W 5 V DC 3.6 W 24 V DC |
| Input protection type | Internal, electronic |
| [Uc] control circuit voltage | 24 V DC |
| Maximum cable distance between devices | 98.4 ft (30 m) |
| Breaking capacity | 360 VA holding AC-15 B300 relay output 3600 VA inrush AC-15 B300 relay output |
| Breaking capacity | 4 A 24 V 50 ms DC-13 relay output |
| Output thermal current | 6 A per relay relay output |
| [Ith] conventional free air thermal current | 18 A |
| Associated fuse rating | 4 A gG or gL relay output IEC 60947-5-1 6 A fast blow relay output IEC 60947-5-1 |
| Minimum output current | 10 mA relay output |
| Output voltage | 10 V relay output |
| Maximum response time on input open | 40 ms |
| [Ui] rated insulation voltage | 300 V 2)IEC 60647-5-1 |
| [Uimp] rated impulse withstand voltage | 4 kV III IEC 60647-5-1 |
| Current consumption | 100 mA 24 V DC external supply |
| Local signalling | 8 LEDs (green/red) for user |
| Electrical Connection | Spring terminal |
| Product compatibility | Safety light curtains EN/IEC 61496-1 (type 4) Sensing mat/edges EN 1760-1 |
| Standards | ISO 13849-1:2008 ISO 13849-2:2012 IEC 62061:2005 IEC 61508:2010 IEC 60947-5-1:2010 IEC 61131-2:2007 IEC 60204-1:2005 IEC 60204-1:2009/A1 IEC 61010-1:2010 EN 50581:2012 |
| Product Certifications | CSA 61010-2-201 (pending) TÃV CSA Haz Loc Class 1 Division 2 (pending) EAC RCM UL 61010-2-201 ANSI Haz Loc Class 1 Division 2 (pending) |
| Marking | CSA RCM UL EFUP 10 CE TÃV EAC |
| Electromagnetic compatibility | Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2 Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz to 1 GHz) conforming to IEC 61000-4-3 Susceptibility to electromagnetic fields - test level: 3 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3 Susceptibility to electromagnetic fields - test level: 1 V/m (2 GHz...3 GHz) conforming to IEC 61000-4-3 Magnetic field at power frequency - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8 Electrical fast transient/burst immunity test - test level: 3 kV (power lines (DC)) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV (I/O) conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to IEC 61000-4-5 Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6 Radiated emission - test level: 40 dBµV/m class A (24 V) conforming to IEC 55011 Radiated emission - test level: 47 dBµV/m class A (24 V) conforming to IEC 55011 |
| Mounting support | Top hat type TH35-7.5 rail IEC 60715 Top hat type TH35-15 rail IEC 60715 wall mount using attached fasteners |
| Height | 3.7 in (94 mm) |
| Depth | 2.9 in (73 mm) |
| Width | 1.7 in (43.7 mm) |
| Product Weight | 0.42 lb(US) (0.19 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 |
| Product or Component Type | Analog input module |
| Range Compatibility | Modicon M221 Modicon M241 Modicon M251 Modicon M262 |
| Analogue input number | 4 |
| Analogue input type | thermocouple - 200...1000 °C thermocouple J thermocouple - 200...1300 °C thermocouple K thermocouple 0...1760 °C thermocouple R thermocouple 0...1760 °C thermocouple S thermocouple 0...1820 °C thermocouple B thermocouple - 200...400 °C thermocouple T thermocouple - 200...1300 °C thermocouple N thermocouple - 200...800 °C thermocouple E thermocouple 0...2315 °C thermocouple C |
Complementary
| Characteristic | Value(s) |
|---|---|
| Analogue input resolution | 16 bits 15 bits + sign |
| Permissible continuous overload | 13 V voltage 40 mA current |
| Input impedance | >= 1 MOhm thermocouple |
| LSB value | 0.1 °C thermocouple |
| Conversion time | 100 ms + 100 ms per channel + 1 controller cycle time thermocouple |
| Sampling duration | 100 ms thermocouple |
| Absolute accuracy error | +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple C 0...2315 °C +/- 6 °C at 77 °F (25 °C) for thermocouple R, S 0...200 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple R, S 200...1760 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple B 300...1820 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple K - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple K 0...1300 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple J - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple J 0...1000 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple E - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple E 0...800 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple T - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple T 0...400 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple N - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple N 0...1300 °C |
| Temperature Drift | +/- 0.01 %FS/°C |
| Repeat accuracy | +/-0.5 %FS |
| Non-linearity | +/- 0.2 %FS |
| Cross talk | <= 1 LSB |
| [Us] rated supply voltage | 24 V DC |
| Supply voltage limits | 20.4â¦28.8 V |
| Type of cable | Twisted shielded pairs cable <98.4 ft (30 m) input |
| Current consumption | 45 mA 5 V DC via bus connector 50 mA 5 V DC via bus connector 35 mA 24 V DC via external supply 40 mA 24 V DC via external supply |
| Local signalling | 1 LED (green) for PWR |
| Electrical connection | 10 x 1.5 mm² removable screw terminal block pitch 3.81 mm for inputs and supply 10 x 1.5 mm² removable screw terminal block pitch 3.81 mm for inputs |
| Insulation | Between input and supply 1500 V AC Between input and internal logic 500 V AC |
| Marking | CE |
| Surge withstand | 1 kV power supply common mode IEC 61000-4-5 0.5 kV power supply differential mode IEC 61000-4-5 1 kV input common mode IEC 61000-4-5 |
| Mounting support | Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit |
| Height | 3.5 in (90 mm) |
| Depth | 2.8 in (70 mm) |
| Width | 0.9 in (23.6 mm) |
| Product Weight | 0.24 lb(US) (0.11 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 |
| Product or Component Type | Analog input module |
| Range Compatibility | Modicon M221 Modicon M241 Modicon M251 Modicon M262 |
| Analogue input number | 4 |
| Analogue input type | thermocouple - 200...1000 °C thermocouple J thermocouple - 200...1300 °C thermocouple K thermocouple 0...1760 °C thermocouple R thermocouple 0...1760 °C thermocouple S thermocouple 0...1820 °C thermocouple B thermocouple - 200...400 °C thermocouple T thermocouple - 200...1300 °C thermocouple N thermocouple - 200...800 °C thermocouple E thermocouple 0...2315 °C thermocouple C |
Complementary
| Characteristic | Value(s) |
|---|---|
| Analogue input resolution | 16 bits 15 bits + sign |
| Permissible continuous overload | 13 V voltage 40 mA current |
| Input impedance | >= 1 MOhm thermocouple |
| LSB value | 0.1 °C thermocouple |
| Conversion time | 100 ms + 100 ms per channel + 1 controller cycle time thermocouple |
| Sampling duration | 100 ms thermocouple |
| Absolute accuracy error | +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple C 0...2315 °C +/- 6 °C at 77 °F (25 °C) for thermocouple R, S 0...200 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple R, S 200...1760 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple B 300...1820 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple K - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple K 0...1300 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple J - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple J 0...1000 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple E - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple E 0...800 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple T - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple T 0...400 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple N - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple N 0...1300 °C |
| Temperature Drift | +/- 0.01 %FS/°C |
| Repeat accuracy | +/-0.5 %FS |
| Non-linearity | +/- 0.2 %FS |
| Cross talk | <= 1 LSB |
| [Us] rated supply voltage | 24 V DC |
| Supply voltage limits | 20.4â¦28.8 V |
| Type of cable | Twisted shielded pairs cable <98.4 ft (30 m) input |
| Current consumption | 45 mA 5 V DC via bus connector 50 mA 5 V DC via bus connector 35 mA 24 V DC via external supply 40 mA 24 V DC via external supply |
| Local signalling | 1 LED (green) for PWR |
| Electrical connection | 10 x 1.5 mm² removable spring terminal block pitch 3.81 mm for inputs and supply 10 x 1.5 mm² removable spring terminal block pitch 3.81 mm for inputs |
| Insulation | Between input and supply 1500 V AC Between input and internal logic 500 V AC |
| Marking | CE |
| Surge withstand | 1 kV power supply common mode IEC 61000-4-5 0.5 kV power supply differential mode IEC 61000-4-5 1 kV input common mode IEC 61000-4-5 |
| Mounting support | Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit |
| Height | 3.5 in (90 mm) |
| Depth | 2.8 in (70 mm) |
| Width | 0.9 in (23.6 mm) |
| Product Weight | 0.24 lb(US) (0.11 kg) |

This product is part of the Modicon TM3 range, an offer of expansion I/O modules for Modicon M221, M241, M251 and M262. The analogue input module provides 8 inputs with 16bit and 15bit + sign resolution. It is an input module with a rated supply voltage of 24V DC and a current consumption of 30mA at 24V DC via external supply, 45mA/40mA at 5V DC via bus connector. This product is capable of controlling variable speed drives or any device equipped with a current or voltage input. There is an insulation between input and supply at 1500V AC, input and internal logic at 500V AC. It is furnished with removable screw terminal for electrical connection with pitch 3.81mm adjustment for inputs and supply. It is an IP20 rated product. Its dimensions are 23.6mm (Width) x 70mm (Depth) x 90mm (Height). It weighs 0.11kg. This product is certified by CE. It meets EN/IEC 61131-2 and EN/IEC 61010-2-201 standards. This module is compatible with Modicon M262, Modicon M241, Modicon M251 and Modicon M221 logic controller. It supports top hat type TH35-15, top hat type TH35-7.5 rail conforming to IEC 60715 and plate or panel with fixing kit mount. Modicon TM3 expansion modules have been designed with a simple interlocking assembly mechanism. A bus expansion connector is used to distribute data and the power supply when assembling the Modicon TM3 modules with logic controllers. Boost the performance of your controller with the Modicon TM3 I/O system specially designed for the Modicon M221, M241 and M251 logic controllers.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 |
| Product or Component Type | Analog input module |
| Range Compatibility | Modicon M221 Modicon M241 Modicon M251 Modicon M262 |
| Analogue input number | 8 |
| Analogue input type | thermocouple - 200...1000 °C thermocouple J thermocouple - 200...1300 °C thermocouple K thermocouple 0...1760 °C thermocouple R thermocouple 0...1760 °C thermocouple S thermocouple 0...1820 °C thermocouple B thermocouple - 200...400 °C thermocouple T thermocouple - 200...1300 °C thermocouple N thermocouple - 200...800 °C thermocouple E thermocouple 0...2315 °C thermocouple C NTC 10k thermistor -90...150 °C PTC thermistor 100...10000 Ohm thermocouple - 200...1000 °C |
Complementary
| Characteristic | Value(s) |
|---|---|
| Analogue input resolution | 16 bits 15 bits + sign |
| Input impedance | >= 1 MOhm thermocouple >= 1 MOhm temperature probe >= 1 MOhm thermistor |
| LSB value | 0.1 °C thermocouple 0.1 °C NTC 1 Ohm PTC/NTC |
| Conversion time | 100 ms + 100 ms per channel + 1 controller cycle time |
| Sampling duration | 100 ms |
| Absolute accuracy error | +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple C 0...2315 °C +/- 6 °C at 77 °F (25 °C) for thermocouple R, S 0...200 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple R, S 200...1760 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple B 300...1820 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple K - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple K 0...1300 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple J - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple J 0...1000 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple E - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple E 0...800 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple T - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple T 0...400 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple N - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple N 0...1300 °C |
| Temperature Drift | +/- 0.01 %FS/°C |
| Repeat accuracy | +/-0.5 %FS |
| Non-linearity | +/- 0.2 %FS |
| Cross talk | <= 1 LSB |
| [Us] rated supply voltage | 24 V DC |
| Supply voltage limits | 20.4â¦28.8 V |
| Type of cable | Twisted shielded pairs cable <98.4 ft (30 m) input |
| Current consumption | 30 mA 24 V DC via external supply 45 mA 5 V DC via bus connector 40 mA 5 V DC via bus connector |
| Local signalling | 1 LED (green) for PWR |
| Electrical connection | 10 x 1.5 mm² removable screw terminal block pitch 3.81 mm for inputs and supply 10 x 1.5 mm² removable screw terminal block pitch 3.81 mm for inputs |
| Insulation | Between input and supply 1500 V AC Between input and internal logic 500 V AC |
| Marking | CE |
| Surge withstand | 1 kV power supply common mode IEC 61000-4-5 0.5 kV power supply differential mode IEC 61000-4-5 1 kV input common mode IEC 61000-4-5 |
| Mounting support | Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit |
| Height | 3.5 in (90 mm) |
| Depth | 2.8 in (70 mm) |
| Width | 0.9 in (23.6 mm) |
| Product Weight | 0.24 lb(US) (0.11 kg) |

This product is part of the Modicon TM3 range, an offer of expansion I/O modules for Modicon M221, M241, M251 and M262. The analogue input module provides 8 inputs with 16bit and 15bit + sign resolution. It is an input module with a rated supply voltage of 24V DC and a current consumption of 30mA at 24V DC via external supply, 45mA/40mA at 5V DC via bus connector. This product is capable of controlling variable speed drives or any device equipped with a current or voltage input. There is an insulation between input and supply at 1500V AC, input and internal logic at 500V AC. It is furnished with removable spring terminal for electrical connection with pitch 3.81mm adjustment for inputs and supply. It is an IP20 rated product. Its dimensions are 23.6mm (Width) x 70mm (Depth) x 90mm (Height). It weighs 0.1kg. This product is certified by CE. It meets EN/IEC 61131-2 and EN/IEC 61010-2-201 standards. This module is compatible with Modicon M241, Modicon M251 and Modicon M221 logic controller. It supports top hat type TH35-15, top hat type TH35-7.5 rail conforming to IEC 60715 and plate or panel with fixing kit mount. Modicon TM3 expansion modules have been designed with a simple interlocking assembly mechanism. A bus expansion connector is used to distribute data and the power supply when assembling the Modicon TM3 modules with logic controllers. Boost the performance of your controller with the Modicon TM3 I/O system specially designed for the Modicon M221, M241 and M251 logic controllers.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 |
| Product or Component Type | Analog input module |
| Range Compatibility | Modicon M221 Modicon M241 Modicon M251 Modicon M262 |
| Analogue input number | 8 |
| Analogue input type | thermocouple - 200...1000 °C thermocouple J thermocouple - 200...1300 °C thermocouple K thermocouple 0...1760 °C thermocouple R thermocouple 0...1760 °C thermocouple S thermocouple 0...1820 °C thermocouple B thermocouple - 200...400 °C thermocouple T thermocouple - 200...1300 °C thermocouple N thermocouple - 200...800 °C thermocouple E NTC 10k thermistor -90...150 °C PTC thermistor 100...10000 Ohm |
Complementary
| Characteristic | Value(s) |
|---|---|
| Analogue input resolution | 16 bits 15 bits + sign |
| Input impedance | >= 1 MOhm thermocouple >= 1 MOhm temperature probe >= 1 MOhm thermistor |
| LSB value | 0.1 °C thermocouple 0.1 °C NTC 1 Ohm PTC/NTC |
| Conversion time | 100 ms + 100 ms per channel + 1 controller cycle time |
| Sampling duration | 100 ms |
| Absolute accuracy error | +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple C 0...2315 °C +/- 6 °C at 77 °F (25 °C) for thermocouple R, S 0...200 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple R, S 200...1760 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple B 300...1820 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple K - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple K 0...1300 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple J - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple J 0...1000 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple E - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple E 0...800 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple T - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple T 0...400 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple N - 200...0 °C +/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple N 0...1300 °C |
| Temperature Drift | +/- 0.01 %FS/°C |
| Repeat accuracy | +/-0.5 %FS |
| Non-linearity | +/- 0.2 %FS |
| Cross talk | <= 1 LSB |
| [Us] rated supply voltage | 24 V DC |
| Supply voltage limits | 20.4â¦28.8 V |
| Type of cable | Twisted shielded pairs cable <98.4 ft (30 m) input |
| Current consumption | 30 mA 24 V DC via external supply 45 mA 5 V DC via bus connector 40 mA 5 V DC via bus connector |
| Local signalling | 1 LED (green) for PWR |
| Electrical connection | 10 x 1.5 mm² removable screw terminal block pitch 3.81 mm for inputs and supply 10 x 1.5 mm² removable screw terminal block pitch 3.81 mm for inputs |
| Insulation | Between input and supply 1500 V AC Between input and internal logic 500 V AC |
| Marking | CE |
| Surge withstand | 1 kV power supply common mode IEC 61000-4-5 0.5 kV power supply differential mode IEC 61000-4-5 1 kV input common mode IEC 61000-4-5 |
| Mounting support | Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit |
| Height | 3.5 in (90 mm) |
| Depth | 2.8 in (70 mm) |
| Width | 0.9 in (23.6 mm) |
| Product Weight | 0.2 lb(US) (0.1 kg) |

This product is part of the Modicon TM3 range, an offer of expansion I/O modules for Modicon M221, M241, M251 and M262. The analogue I/O module provides 2 inputs, 1 output with 16bit, 15bit + sign input resolution. It is an I/O module with a rated supply voltage of 24V DC, a current consumption of 60mA, 55mA at 5V DC via bus connector, 55mA, 80mA at 24V DC via external supply. This product is capable of controlling variable speed drives or any device equipped with a current or voltage input. There is an insulation between input and supply at 1500V AC, input and internal logic at 500V AC, output and supply at 1500V AC and output and internal logic at 500V AC. It is furnished with removable spring terminal for electrical connection with 5.08mm pitch adjustment for inputs, outputs and supply. It is an IP20 rated product. Its dimensions are 23.6mm (Width) x 70mm (Depth) x 90mm (Height). It weighs 0.1kg. This product is certified by CE. It meets EN/IEC 61131-2 and EN/IEC 61010-2-201 standards. This module is compatible with Modicon M241, Modicon M251 and Modicon M221 logic controller. It supports top hat type TH35-15, top hat type TH35-7.5 rail conforming to IEC 60715 and plate or panel with fixing kit mount. Modicon TM3 expansion modules have been designed with a simple interlocking assembly mechanism. A bus expansion connector is used to distribute data and the power supply when assembling the Modicon TM3 modules with logic controllers. Boost the performance of your controller with the Modicon TM3 I/O system specially designed for the Modicon M221, M241 and M251 logic controllers.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 |
| Product or Component Type | Input/output analog module |
| Range Compatibility | Modicon M221 Modicon M241 Modicon M251 Modicon M262 |
| Analogue input number | 2 |
| Analogue input type | current 4...20 mA current 0...20 mA voltage 0...10 V voltage - 10...10 V thermocouple - 200...1000 °C thermocouple J thermocouple - 200...1300 °C thermocouple K thermocouple 0...1760 °C thermocouple R thermocouple 0...1760 °C thermocouple S thermocouple 0...1820 °C thermocouple B thermocouple - 200...400 °C thermocouple T thermocouple - 200...1300 °C thermocouple N thermocouple - 200...800 °C thermocouple E thermocouple 0...2315 °C thermocouple C Ni 100/Ni 1000 temperature probe - 60...180 °C Pt 100 temperature probe - 200...850 °C Pt 1000 temperature probe - 200...600 °C |
| Analogue output number | 1 |
| Analogue output type | Current 4...20 mA Current 0...20 mA Voltage 0...10 V Voltage - 10...10 V |
Complementary
| Characteristic | Value(s) |
|---|---|
| Analogue input resolution | 16 bits 15 bits + sign |
| Permissible continuous overload | 13 V voltage 40 mA current |
| Input impedance | <= 50 Ohm current >= 1 MOhm voltage >= 1 MOhm thermocouple >= 1 MOhm temperature probe |
| Analogue output resolution | 12 bits |
| LSB value | 0.15 mV 0...10 V voltage 0.30 mV - 10...10 V voltage 0.30 µA 0...20 mA current 0.244 µA 4...20 mA current 0.1 °C temperature probe 0.1 °C thermocouple 2.44 mV 0...10 V voltage 4.88 mV - 10...10 V voltage 4.88 µA 0...20 mA current 3.91 µA 4...20 mA current |
| Load type | Resistive |
| Load impedance ohmic | 1 kOhm voltage 300 Ohm current |
| Stabilisation time | 1 ms |
| Conversion time | 100 ms + 100 ms per channel + 1 controller cycle time thermocouple 100 ms + 100 ms per channel + 1 controller cycle time temperature probe 10 ms + 10 ms per channel + 1 controller cycle time voltage/current |
| Sampling duration | 10 ms voltage/current 100 ms voltage/current 100 ms thermocouple 100 ms temperature probe |
| Absolute accuracy error | +/- 6 °C at 77 °F (25 °C) for thermocouple R, S 0...200 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple K - 200...0 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple J - 200...0 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple E - 200...0 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple T - 200...0 °C +/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple N - 200...0 °C +/- 0.1 % of full scale at 77 °F (25 °C) for analogue input voltage/current +/- 0.1 % of full scale at 77 °F (25 °C) for thermocouple C 0...2315 °C +/- 0.1 % of full scale at 77 °F (25 °C) for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe +/- 0.1 % of full scale at 77 °F (25 °C) for thermocouple R, S 200...1760 °C +/- 0.1 % of full scale at 77 °F (25 °C) for thermocouple B 300...1820 °C +/- 0.1 % of full scale at 77 °F (25 °C) for thermocouple K 0...1300 °C +/- 0.1 % of full scale at 77 °F (25 °C) for thermocouple J 0...1000 °C +/- 0.1 % of full scale at 77 °F (25 °C) for thermocouple E 0...800 °C +/- 0.1 % of full scale at 77 °F (25 °C) for thermocouple T 0...400 °C +/- 0.1 % of full scale at 77 °F (25 °C) for thermocouple N 0...1300 °C +/- 0.1 % of full scale at 77 °F (25 °C) for analogue output voltage/current |
| Temperature Drift | +/- 0.006 %FS/°C |
| Repeat accuracy | +/-0.5 %FS input +/- 0.4 %FS output |
| Non-linearity | +/- 0.01 %FS analog output +/- 0.1 %FS analog input |
| Output ripple | 20 mV |
| Cross talk | <= 1 LSB |
| [Us] rated supply voltage | 24 V DC |
| Supply voltage limits | 20.4â¦28.8 V |
| Type of cable | Twisted shielded pairs cable <98.4 ft (30 m) input/output |
| Current consumption | 55 mA 24 V DC via external supply no load 55 mA 5 V DC via bus connector no load 60 mA 5 V DC via bus connector full load 80 mA 24 V DC via external supply full load |
| Local signalling | 1 LED (green) for PWR |
| Electrical connection | 11 x 2.5 mm² removable spring terminal block pitch 5.08 mm for inputs, outputs and supply |
| Insulation | Between input and supply 1500 V AC Between input and internal logic 500 V AC Between output and supply 1500 V AC Between output and internal logic 500 V AC |
| Marking | CE |
| Surge withstand | 1 kV power supply common mode IEC 61000-4-5 0.5 kV power supply differential mode IEC 61000-4-5 1 kV I/O common mode IEC 61000-4-5 0.5 kV I/O differential mode IEC 61000-4-5 |
| Mounting support | Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit |
| Height | 3.5 in (90 mm) |
| Depth | 2.8 in (70 mm) |
| Width | 0.9 in (23.6 mm) |
| Product Weight | 0.2 lb(US) (0.1 kg) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 |
| Product or Component Type | Module hight speed counting |
| Range Compatibility | Modicon M262 |
| [Us] rated supply voltage | 24 V DC external supply - 15...20 %) |
| Number of input channels | 10 |
| Number of output channels | 8 |
| Discrete I/O number | 18 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Current consumption | 100 mA 5 V DC 50 mA 24 V DC |
| Counting frequency | 200 kHz |
| Discrete input voltage | 24 V DC |
| Electrical circuit type | Standard input Latch input |
| Discrete input logic | Sink or source |
| Output voltage | 24 V DC transistor output |
| Output voltage limits | 30 V DC |
| Discrete output current | 300 mA fast output Q0...Q7) |
| Discrete output logic | Source |
| Output protection type | Against overload and short-circuits |
| Reset | Automatic reset |
| Local signalling | 1 LED I/O 1 LED RUN 1 LED ERR |
| Mounting support | Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit |
| Services | HSC simple One shot/Modulo HSC main single phase One shot/Modulo/Event counting HSC main dual phase Modulo/Free-large Period meter Edge to Edge, Edge to Opposite |
| Counting mode | 2 main expert function (main counting function, frequency meter, period meter) Max 8 simple counting function |
| Event management | 8 maximum per PLC <= 100 µs Thresholds < 10 µs |
| Height | 3.5 in (90 mm) |
| Depth | 3.3 in (85 mm) |
| Width | 1.5 in (39 mm) |
| Product Weight | 5.3 oz (150 g) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 |
| Product or Component Type | Module hight speed counting |
| Range Compatibility | Modicon M262 |
| [Us] rated supply voltage | 24 V DC external supply - 15...20 %) |
| Number of input channels | 10 |
| Number of output channels | 8 |
| Discrete I/O number | 18 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Current consumption | 100 mA 5 V DC 50 mA 24 V DC |
| Counting frequency | 200 kHz |
| Discrete input voltage | 24 V DC |
| Electrical circuit type | Standard input Latch input |
| Discrete input logic | Sink or source |
| Output voltage | 24 V DC transistor output |
| Output voltage limits | 30 V DC |
| Discrete output current | 300 mA fast output Q0...Q7) |
| Discrete output logic | Source |
| Output protection type | Against overload and short-circuits |
| Reset | Automatic reset |
| Local signalling | 1 LED I/O 1 LED RUN 1 LED ERR |
| Mounting support | Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit |
| Services | HSC simple One shot/Modulo HSC main single phase One shot/Modulo/Event counting HSC main dual phase Modulo/Free-large Period meter Edge to Edge, Edge to Opposite |
| Counting mode | 2 main expert function (main counting function, frequency meter, period meter) Max 8 simple counting function |
| Event management | 8 maximum per PLC <= 100 µs Thresholds < 10 µs |
| Height | 3.5 in (90 mm) |
| Depth | 3.3 in (85 mm) |
| Width | 1.5 in (39 mm) |
| Product Weight | 5.3 oz (150 g) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 |
| Product or Component Type | Module hight speed counting |
| Range Compatibility | Modicon M262 |
| [Us] rated supply voltage | 24 V DC external supply - 15...20 %) |
| Number of input channels | 10 |
| Number of output channels | 8 |
| Discrete I/O number | 18 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Current consumption | 100 mA 5 V DC 50 mA 24 V DC |
| Counting frequency | 200 kHz |
| Discrete input voltage | 24 V DC |
| Electrical circuit type | Standard input Latch input |
| Discrete input logic | Sink or source |
| Output voltage | 24 V DC transistor output |
| Output voltage limits | 30 V DC |
| Discrete output current | 300 mA fast output Q0...Q7) |
| Discrete output logic | Source |
| Output protection type | Against overload and short-circuits |
| Reset | Automatic reset |
| Local signalling | 1 LED I/O 1 LED RUN 1 LED ERR |
| Mounting support | Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit |
| Services | HSC simple One shot/Modulo HSC main single phase One shot/Modulo/Event counting HSC main dual phase Modulo/Free-large Period meter Edge to Edge, Edge to Opposite |
| Counting mode | 2 main expert function (main counting function, frequency meter, period meter) Max 8 simple counting function |
| Event management | No event Thresholds < 10 µs |
| Height | 3.5 in (90 mm) |
| Depth | 3.3 in (85 mm) |
| Width | 1.5 in (39 mm) |
| Product Weight | 5.3 oz (150 g) |

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 |
| Product or Component Type | Module hight speed counting |
| Range Compatibility | Modicon M262 |
| [Us] rated supply voltage | 24 V DC external supply - 15...20 %) |
| Number of input channels | 10 |
| Number of output channels | 8 |
| Discrete I/O number | 18 |
Complementary
| Characteristic | Value(s) |
|---|---|
| Current consumption | 100 mA 5 V DC 50 mA 24 V DC |
| Counting frequency | 200 kHz |
| Discrete input voltage | 24 V DC |
| Electrical circuit type | Standard input Latch input |
| Discrete input logic | Sink or source |
| Output voltage | 24 V DC transistor output |
| Output voltage limits | 30 V DC |
| Discrete output current | 300 mA fast output Q0...Q7) |
| Discrete output logic | Source |
| Output protection type | Against overload and short-circuits |
| Reset | Automatic reset |
| Local signalling | 1 LED I/O 1 LED RUN 1 LED ERR |
| Mounting support | Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit |
| Services | HSC simple One shot/Modulo HSC main single phase One shot/Modulo/Event counting HSC main dual phase Modulo/Free-large Period meter Edge to Edge, Edge to Opposite |
| Counting mode | 2 main expert function (main counting function, frequency meter, period meter) Max 8 simple counting function |
| Event management | No event Thresholds < 10 µs |
| Height | 3.5 in (90 mm) |
| Depth | 3.3 in (85 mm) |
| Width | 1.5 in (39 mm) |
| Product Weight | 5.3 oz (150 g) |

This product is part of the Modicon TM3 range, an offer of expansion I/O modules for Modicon M221, M241, M251 and M262. The remote receiver module is physically connected by a bus expansion cable, provides 7 I/O channels. It is remote receiver module with a rated supply voltage of 24V DC, a current consumption of 40mA at 24V DC via bus connector and a maximum power dissipation of 1W. The cable distance between devices is 0.5mm to 5mm extension cable with 2 RJ45 conductor between receiver and transmitter. It is furnished with RJ45 connector for connecting the bus transmitter, removable screw terminal block, 3 terminals for electrical connection. It is an IP20 rated product. Its dimensions are 23.65mm (Width) x 73.3mm (Depth) x 90mm (Height). It weighs 0.075kg. This product is certified by CE, Merchant Navy, GOST, CSA HazLoc, C-Tick. It meets Class I Division 2 Groups A/B/C/D CSA C22.2 No 213, Class I Division 2 Groups A/B/C UL 1604, CSA C22.2 No 142, IEC 61131-2 and UL 508 standards. This module is compatible with Modicon M262, Modicon M241, Modicon M251 and Modicon M221 logic controller. It supports top hat type TH35-15 rail conforming to IEC 60715, top hat type TH35-7.5 rail conforming to IEC 60715, plate or panel with fixing kit mount. Modicon TM3 expansion modules have been designed with a simple interlocking assembly mechanism. A bus expansion connector is used to distribute data and the power supply when assembling the Modicon TM3 modules with logic controllers. Boost the performance of your controller with the Modicon TM3 I/O system specially designed for the Modicon M221, M241 and M251 logic controllers.
Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon TM3 |
| Product or Component Type | Remote receiver module |
| Range Compatibility | Modicon M221 Modicon M251 Modicon M241 Modicon M262 |
| [Us] rated supply voltage | 24 V DC external supply - 15...20 %) |
Complementary
| Characteristic | Value(s) |
|---|---|
| Maximum Number of I/O Expansion Module | 7 |
| Power supply output current | 560 mA 5 V expansion bus 560 mA 24 V expansion bus |
| Current consumption | 40 mA 24 V DC via bus connector |
| Maximum power dissipation in W | 1 W |
| Cable distance between devices | 0.02â¦0.2 in (0.5â¦5 mm) extension cable 2 RJ45 between receiver and transmitter |
| Local signalling | 1 LED (green) for power supply 1 LED (green) for link status |
| Electrical connection | RJ45 connector for connecting the bus transmitter removable screw terminal block, 3 for connecting the 24 V DC power supply |
| Marking | CE |
| Resistance to electrostatic discharge | 8 kV in air IEC 61000-4-2 6 kV on contact IEC 61000-4-2 |
| Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80 MHz...1 GHz IEC 61000-4-3 2.7 V/m (3 V/m) 1.4 GHz...2 GHz IEC 61000-4-3 0.9 V/m (1 V/m) 2...2.7 GHz IEC 61000-4-3 |
| Resistance to conducted disturbances | 10 V 0.15...80 MHz IEC 61000-4-6 3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) Marine specification (LR, ABS, DNV, GL) |
| Electromagnetic emission | Radiated emissions 40 dBμV/m QP class A 10 m)30â¦230 MHz IEC 55011 Radiated emissions 47 dBμV/m QP class A 10 m)230â¦1000 MHz IEC 55011 |
| Mounting support | Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit |
| Height | 3.5 in (90 mm) |
| Depth | 2.9 in (73.3 mm) |
| Width | 0.93 in (23.65 mm) |
| Product Weight | 0.165 lb(US) (0.075 kg) |
Modules