Main
| Characteristic | Value(s) |
|---|---|
| Accessory / separate part category | Connection accessories |
| Accessory / Separate Part Type | Connecting cable |
| Accessory / separate part designation | Connection cordset for PC terminal |
| Accessory / separate part destination | Unity processor |
| Cable length | 9.8 ft (3 m) |
Complementary
| Characteristic | Value(s) |
|---|---|
| Product Compatibility | 140CPU65160S 140CPU67160S 140CPU67160 140CPU65150 140CPU65160 140CPU31110 |
| Range Compatibility | Modicon Quantum automation platform Modicon Momentum automation platform |
| Electrical connection | 1 connector RJ45 PC side 1 connector RJ45 processor side |

Main
| Characteristic | Value(s) |
|---|---|
| Accessory / separate part category | Connection accessories |
| Accessory / Separate Part Type | Connecting cable |
| Accessory / separate part designation | Connection cordset for PC terminal |
| Accessory / separate part destination | Unity processor |
| Cable length | 9.8 ft (3 m) |
Complementary
| Characteristic | Value(s) |
|---|---|
| Product Compatibility | 140CPU65160S 140CPU67160S 140CPU67160 140CPU65150 140CPU65160 140CPU31110 |
| Range Compatibility | Modicon Quantum automation platform Modicon Momentum automation platform |
| Electrical connection | 1 connector RJ45 PC side 1 connector RJ45 processor side |


SERVO MOTOR, 1.6 HP, 5250 RPM, RARE EARTH LOW INTERTIA AC, 460VAC, FRAME = 100MM (APPROX. STATOR SIZE), IEC METRIC FLANGE W/ KEYWAY

AC Servo Motor, 460V AC, Frame Size 4 = 100mm, 6.2A, 2.8kW, 9.0Nm, Rated Speed 4300RPM, 10.2Nm (90lb in) Holding Brake with 24V DC Coil

Main
| Characteristic | Value(s) |
|---|---|
| Range of Product | Modicon Quantum automation platform |
| Product or Component Type | Analogue input module |
| Type of filter | Single pole low pass - 3 dB at 15 Hz +/- 20 % |
Complementary
| Characteristic | Value(s) |
|---|---|
| Analogue input number | 8 |
| Input type | Differential |
| Addressing requirement | 9 input words |
| Analogue input resolution | 12 bits |
| Linear measuring range | 1...5 V 4...20 mA |
| Absolute maximum input | 50 V DC 25 mA |
| Input impedance | 250 Ohm current +/- 0.01 % > 20 MOhm voltage |
| Absolute accuracy error | +/- 0.05 % of full scale +/- 0.1 % of full scale maximum |
| Linearity error | +/- 0.04 % |
| Accuracy drift according to temperature | +/- 0.0025 % of full scale/°C <= 0.005 % of full scale/°C |
| Common mode rejection | > - 72 dB 60 Hz |
| Isolation between channels and bus | 1000 V DC 3000 V DC 60 s |
| Isolation between channels | 30 V DC |
| Update time | 5 ms |
| Fault type | Broken wire 4...20 mA Undervoltage range 1...5 V |
| Marking | CE |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault 8 LEDs (green) for channel is turned on 8 LEDs (red) for channel fault |
| Bus current requirement | 240 mA |
| Power dissipation in W | 2 W |
| Module format | Standard |
| Product Weight | 0.7 lb(US) (0.3 kg) |