Modules

822 products

Showing 817 - 822 of 822 products

Showing 817 - 822 of 822 products
View
XPSMF1DI1601 Schneider Electric

Main

Characteristic Value(s)
Range of Product Preventa Safety automation
Product or Component Type Preventa safety remote input module
Safety module name XPSMF1
Safety module application Extension of I/O capacity
Safety use category Category 4 maximum EN 954-1
Performance level e EN/ISO 13849-1
SIL 3 EN/IEC 61508
Function of module Monitoring safety detection discrete input
Monitoring safety dialogue discrete input
Monitoring short-circuit and line break remote line control output
[Us] Rated Supply Voltage 24 V DC - 15...20 %
Supply SELV or PELV EN/IEC 60950
Discrete input number 16 not isolated
Number of outputs 4 not isolated line control outputs
Structure type 10BASE-T/100BASE-TX

Complementary

Characteristic Value(s)
Response Time Depending on size of application
Voltage state 0 guaranteed <= 5 V discrete input
Voltage state 1 guaranteed >= 15 V discrete input
Current state 0 guaranteed 1...1.5 mA discrete input)
Current state 1 guaranteed >= 2 mA discrete input)
Discrete input voltage 19.2 V
Discrete input current 40 mA
Input protection type Protected against short-circuit
Output voltage 20 V line control outputs
Nominal output current 60 mA line control outputs
Switching voltage 7.5 V discrete input
Switching time 250 µs discrete input
Communication port protocol Safe Ethernet 2 RJ45 100 Mbps, 10 Mbps dual twisted pair cable, category 5D or better
Exchange mode Half duplex, full duplex, autonegotiation
Number of terminal blocks 1 discrete output
1 power supply
4 discrete input
Current consumption 0.8 A 24 V DC on power supply
Mounting Support 35 mm symmetrical DIN rail
Depth 2.6 in (66.5 mm)
Height 4.3 in (109 mm)
Width 6.0 in (152 mm)
Product Weight 1.5 lb(US) (0.7 kg)
XPSMF2DO801 Schneider Electric

Main

Characteristic Value(s)
Range of Product Preventa Safety automation
Product or Component Type Preventa safety remote output relay module
Safety module name XPSMF2
Safety module application Extension of I/O capacity
Safety use category Category 4 maximum EN 954-1
Performance level e EN/ISO 13849-1
SIL 3 EN/IEC 61508
Function of module Monitoring safety actuators
Monitoring safety dialogue
[Us] Rated Supply Voltage 24 V DC - 15...20 %
Supply SELV or PELV EN/IEC 60950
Number of outputs 8 relay
Structure type 10BASE-T/100BASE-TX

Complementary

Characteristic Value(s)
Response Time Depending on size of application
Associated fuse rating 10 A, slow-blow
Output type Relay, 2 NO per output, volt-free
Minimum switching voltage 5 V 250 V AC output relay
5 V 250 V DC output relay
Switching current capacity 3 A / 100 A with internal fuse relay output
Maximum switching capacity in VA <240 VA 0.5 relay output
Maximum switching capacity in W <90 / 30 V relay output
<30 / 127 V relay output
<35 / 70 V relay output
Contacts material Silver alloy (Ag/Ni) relay output
Electrical durability 250000 cycles relay output
Mechanical durability 1000000 cycles relay output
Communication port protocol Safe Ethernet 2 RJ45 100 Mbps, 10 Mbps dual twisted pair cable, category 5D or better
Exchange mode Half duplex, full duplex, autonegotiation
Number of terminal blocks 1 power supply
8 relay output
Current consumption 0.6 A 24 V DC on power supply
Mounting Support 35 mm symmetrical DIN rail
Depth 3.4 in (86.5 mm)
Height 4.3 in (109 mm)
Width 8.1 in (207 mm)
Product Weight 2.9 lb(US) (1.3 kg)
XPSMF3AIO8401 Schneider Electric

Main

Characteristic Value(s)
Range of Product Preventa Safety automation
Product or Component Type Preventa safety remote mixed I/O module
Safety module name XPSMF3
Safety module application Extension of I/O capacity
Safety use category Category 4 maximum EN 954-1
Performance level e EN/ISO 13849-1
SIL 3 EN/IEC 61508
Structure type 10BASE-T/100BASE-TX

Complementary

Characteristic Value(s)
Function of module Single-pole measuring of 0 to 10 V voltages
Measuring, using shunt, 0/4 to 20 mA currents
Closed circuit scanning of input channels
[Us] Rated Supply Voltage 24 V DC - 15...20 %
Supply SELV or PELV EN/IEC 60950
Response Time Depending on size of application
Analogue input number 8
Analogue Input Type Not isolated
External resistance 250 Ohm analogue input circuit
500 Ohm analogue input circuit
Analogue input range 0...20 mA 500 Ohm
0...10 V
Input voltage limits 0.1...11.5 V
Input current limits 0.4…23 mA 500 Ohm
Analogue input resolution 12 bits
Safety accuracy +/- 2 % analogue input circuit
Maximum internal input resistance 500 MOhm for signal source
2 Ohm
Input overvoltage protection -4…15 V
Analogue output number 4
Analogue Output Type Not isolated
Analogue output range 4...20 mA
Output current limits 0…20 mA
Analogue output resolution 12 bits
Load impedance ohmic <= 600 Ohm analogue output
Relative error +/- 1 %
Maximum cable distance between devices 11.8 in (300 mm) analogue input circuit
11.8 in (300 mm) analogue output
Communication port protocol Safe Ethernet 2 RJ45 100 Mbps, 10 Mbps dual twisted pair cable, category 5D or better
Exchange mode Half duplex, full duplex, autonegotiation
Number of terminal blocks 1 power supply
5 analogue input/output circuit
Current consumption 0.8 A 24 V DC on power supply
Mounting Support 35 mm symmetrical DIN rail
Depth 8.1 in (207 mm)
Height 4.3 in (109 mm)
Width 3.8 in (97.5 mm)
Product Weight 2.09 lb(US) (0.95 kg)
XPSMF3DIO16801 Schneider Electric

Main

Characteristic Value(s)
Range of Product Preventa Safety automation
Product or Component Type Preventa safety remote mixed I/O module
Safety module name XPSMF3
Safety module application Extension of I/O capacity
Safety use category Category 4 maximum EN 954-1
Performance level e EN/ISO 13849-1
SIL 3 EN/IEC 61508
Function of module Monitoring safety actuators discrete input
Monitoring safety actuators discrete output
Monitoring safety detection discrete input
Monitoring safety dialogue discrete input
Monitoring safety dialogue discrete output
Monitoring short-circuit and line break line control outputs
[Us] Rated Supply Voltage 24 V DC - 15...20 %
Supply SELV or PELV EN/IEC 60950
Discrete input number 16 not isolated
Number of outputs 2 not isolated line control outputs
Discrete output number 16, not isolated
Structure type 10BASE-T/100BASE-TX

Complementary

Characteristic Value(s)
Response Time Depending on size of application
Associated fuse rating 16 A, slow-blow
Voltage state 0 guaranteed <= 5 V discrete input
Voltage state 1 guaranteed 15...< 30 V discrete input
Current state 0 guaranteed 1...1.5 mA discrete input)
Current state 1 guaranteed <= 2 mA discrete input)
Discrete input voltage 20 V
Discrete input current 40 mA
Input protection type Protected against short-circuit
Output voltage 20 V line control outputs
Nominal output current 60 mA line control outputs
Switching voltage 7.5 V discrete input
Switching time 250 µs
Discrete output voltage 24 V DC
Output voltage tolerance +/- 3 %
Discrete output current > 10 mA 140 °F (60 °C) channels 1 to 3, 5 to 7, 4 and 8)
1 A 140 °F (60 °C) channels 1 to 3, 5 to 7, 4 and 8)
2 A 104 °F (40 °C) channels 1 to 3, 5 to 7, 4 and 8)
<= 9 A all channels)
Inductive load 500 mH discrete output
Maximum tungsten load <25 W discrete output
Maximum line resistance 5 kOhm discrete output
Minimum load 2 mA per channel
Maximum leakage current 1 mA 2 V at state 0 discrete output
Communication port protocol Safe Ethernet 2 RJ45 100 Mbps, 10 Mbps dual twisted pair cable, category 5D or better
Exchange mode Half duplex, full duplex, autonegotiation
Number of terminal blocks 1 line control outputs
1 power supply
3 discrete output
4 discrete input
Current consumption 14 A 24 V DC on power supply
Mounting Support 35 mm symmetrical DIN rail
Depth 3.4 in (86.5 mm)
Height 4.3 in (109 mm)
Width 8.07 in (205 mm)
Product Weight 2.9 lb(US) (1.3 kg)
XPSMF3DIO20802 Schneider Electric

Main

Characteristic Value(s)
Range of Product Preventa Safety automation
Product or Component Type Preventa safety remote mixed I/O module
Safety module name XPSMF3
Safety module application Extension of I/O capacity
Safety use category Category 4 maximum EN 954-1
Performance level e EN/ISO 13849-1
SIL 3 EN/IEC 61508
Function of module Monitoring safety actuators discrete input
Monitoring safety actuators discrete output
Monitoring safety detection discrete input
Monitoring safety dialogue discrete input
[Us] Rated Supply Voltage 24 V DC - 15...20 %
Supply SELV or PELV EN/IEC 60950
Discrete input number 20 not isolated
Discrete output number 8, not isolated
Structure type 10BASE-T/100BASE-TX

Complementary

Characteristic Value(s)
Response Time Depending on size of application
Voltage state 0 guaranteed <= 5 V discrete input
Voltage state 1 guaranteed 15...< 30 V discrete input
Current state 0 guaranteed 1.25...1.5 mA discrete input)
Current state 1 guaranteed <= 2 mA discrete input)
Discrete input voltage 20 V
Discrete input current 100 mA
Input protection type Protected against short-circuit
Switching voltage 7.5 V discrete input
Discrete output voltage 24 V DC
Output voltage tolerance +/- 2%
Discrete output current 1 A 140 °F (60 °C) channels 4 and 8)
2 A 122 °F (50 °C) channels 4 and 8)
0.5 A 140 °F (60 °C) channels 1 to 3 and 5 to 7)
<= 7 A all channels)
Minimum load 2 mA per channel
Maximum leakage current 1 mA 2 V at state 0 discrete output
Communication port protocol Safe Ethernet 2 RJ45 100 Mbps, 10 Mbps dual twisted pair cable, category 5D or better
Exchange mode Half duplex, full duplex, autonegotiation
Number of terminal blocks 1 power supply
2 discrete input
2 discrete output
Current consumption 8 A 24 V DC on power supply
Mounting Support 35 mm symmetrical DIN rail
Depth 2.6 in (66.5 mm)
Height 4.3 in (109 mm)
Width 8.1 in (207 mm)
Product Weight 2.2 lb(US) (1 kg)
XPSMF3DIO8801 Schneider Electric

Main

Characteristic Value(s)
Range of Product Preventa Safety automation
Product or Component Type Preventa safety remote mixed I/O module
Safety module name XPSMF3
Safety module application Extension of I/O capacity
Safety use category Category 4 maximum EN 954-1
Performance level e EN/ISO 13849-1
SIL 3 EN/IEC 61508
Function of module Monitoring safety actuators discrete input
Monitoring safety actuators discrete output
Monitoring safety detection discrete input
Monitoring safety dialogue discrete input
Monitoring safety dialogue discrete output
Monitoring short-circuit and line break line control outputs
[Us] Rated Supply Voltage 24 V DC - 15...20 %
Supply SELV or PELV EN/IEC 60950
Discrete input number 8 not isolated
Number of outputs 2 not isolated line control outputs
Discrete output number 10, not isolated
Structure type 10BASE-T/100BASE-TX

Complementary

Characteristic Value(s)
Response Time Depending on size of application
Associated fuse rating 10 A, slow-blow
Voltage state 0 guaranteed <= 5 V discrete input
Voltage state 1 guaranteed 15...< 30 V discrete input
Current state 0 guaranteed 1.25...1.5 mA discrete input)
Current state 1 guaranteed <= 2 mA discrete input)
Discrete input voltage 20 V
Discrete input current 100 mA
Input protection type Protected against short-circuit
Output voltage 20 V line control outputs
Nominal output current 60 mA line control outputs
Switching voltage 7.5 V discrete input
Discrete output voltage 24 V DC
Output voltage tolerance +/- 2%
Discrete output current 1 A 140 °F (60 °C) channels 1 and 2)
1 A 140 °F (60 °C) channels 4 and 8)
2 A 104 °F (40 °C) channels 4 and 8)
0.5 A 140 °F (60 °C) channels 1 to 3 and 5 to 7)
<= 7 A all channels)
Inductive load 500 mH discrete output
Maximum tungsten load <10 W, channels 1 to 3 and 5 to 7 discrete output
<25 W, channels 1 and 2 discrete output
<25 W, channels 4 and 8 discrete output
Minimum load 2 mA per channel
Maximum leakage current 1 mA 2 V at state 0 discrete output
Communication port protocol Safe Ethernet 2 RJ45 100 Mbps, 10 Mbps dual twisted pair cable, category 5D or better
Exchange mode Half duplex, full duplex, autonegotiation
Number of terminal blocks 1 power supply
2 discrete input
2 discrete output
2 line control outputs
Current consumption 8 A 24 V DC on power supply
Mounting Support 35 mm symmetrical DIN rail
Depth 2.6 in (66.5 mm)
Height 4.3 in (109 mm)
Width 6.0 in (152 mm)
Product Weight 2.2 lb(US) (1 kg)

Recently viewed