{"product_id":"xpsak371144p","title":"XPSAK371144P Schneider","description":"\u003cp\u003eThis XPSAK safety module monitors emergency shutdown pushbuttons, limit switches, light curtains and safety mats\/edges. It meets the requirements of Performance Level PL e\/Category 4 conforming to standard EN\/ISO 13849-1 and SILCL3 conforming to EN\/IEC 61508 and EN\/IEC 62061. It can be used for monitoring emergency stop circuits conforming to standards EN\/ISO 13850 and EN\/IEC 60204-1. It can also be used for electrical monitoring of switches activated by protection devices, with optional selection of synchronisation time between signals, monitoring of 4-wire sensing mats or edges. And monitoring of type 4 light curtains conforming to EN\/IEC 61496-1 which have solid-state safety outputs with test function (light curtains XUSL). It is compatible with emergency push buttons, limit switches, safety light curtains and safety mats\/edges, the 4 most common safety sensors in the industry. It has removable terminals for easier and better control wires tightening, thus improving installation reliability. It has additional solid-state output for communication with PLCs about safety status of your process.\u003c\/p\u003e\u003ch2\u003eMain\u003c\/h2\u003e\n\u003ctable border=\"1\" cellpadding=\"5\" cellspacing=\"0\"\u003e\n\u003cthead\u003e\u003ctr\u003e\n\u003cth\u003eCharacteristic\u003c\/th\u003e\n\u003cth\u003eValue(s)\u003c\/th\u003e\n\u003c\/tr\u003e\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eRange of Product\u003c\/td\u003e\n\u003ctd\u003ePreventa Safety automation\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct or Component Type\u003c\/td\u003e\n\u003ctd\u003ePreventa safety module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSafety module name\u003c\/td\u003e\n\u003ctd\u003eXPSAK\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSafety module application\u003c\/td\u003e\n\u003ctd\u003eFor emergency stop, switch, sensing mat\/edges or safety light curtain monitoring\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFunction of module\u003c\/td\u003e\n\u003ctd\u003eMonitoring of a movable guard\u003cbr\u003eMonitoring of electro-sensitive protection equipment (ESPE)\u003cbr\u003eSensing mat and edges monitoring\u003cbr\u003eEmergency stop monitoring 1-channel wiring\u003cbr\u003eMultiple emergency stop monitoring 2-channel wiring\u003cbr\u003eProximity sensor monitoring\u003cbr\u003eMonitoring of a movable guard associated with 2 switches and automatic start\u003cbr\u003eEmergency stop with 2 NC contacts monitoring 2-channel wiring\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSafety level\u003c\/td\u003e\n\u003ctd\u003eCan reach PL e\/category 4 EN\/ISO 13849-1\u003cbr\u003eCan reach SILCL 3 EN\/IEC 62061\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSafety reliability data\u003c\/td\u003e\n\u003ctd\u003eDC \u0026gt; 99 % EN\/ISO 13849-1\u003cbr\u003eMTTFd = 154.5 years EN\/ISO 13849-1\u003cbr\u003ePFHd = 7.39E-9 1\/h EN\/IEC 62061\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eType of start\u003c\/td\u003e\n\u003ctd\u003eConfigurable\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnections - terminals\u003c\/td\u003e\n\u003ctd\u003eCaptive screw clamp terminals, removable terminal block, 1 x 0.2...1 x 2.5 mmÂ² flexible with cable end, with double bezel\u003cbr\u003eCaptive screw clamp terminals, removable terminal block, 1 x 0.2...1 x 2.5 mmÂ² solid with cable end, with double bezel\u003cbr\u003eCaptive screw clamp terminals, removable terminal block, 1 x 0.25...1 x 2.5 mmÂ² flexible with cable end, with double bezel\u003cbr\u003eCaptive screw clamp terminals, removable terminal block, 2 x 0.2...2 x 1 mmÂ² solid with cable end, with double bezel\u003cbr\u003eCaptive screw clamp terminals, removable terminal block, 2 x 0.2...2 x 1.5 mmÂ² flexible with cable end, with double bezel\u003cbr\u003eCaptive screw clamp terminals, removable terminal block, 2 x 0.25...2 x 1 mmÂ² flexible with cable end, with double bezel\u003cbr\u003eCaptive screw clamp terminals, removable terminal block, 2 x 0.5...2 x 1.5 mmÂ² flexible with cable end, with double bezel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput type\u003c\/td\u003e\n\u003ctd\u003eRelay instantaneous opening, 3 NO, volt-free\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of additional circuits\u003c\/td\u003e\n\u003ctd\u003e1 NC + 4 solid state outputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Us] Rated Supply Voltage\u003c\/td\u003e\n\u003ctd\u003e230 V AC - 15...10 %\u003cbr\u003e24 V DC - 15...10 %\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\u003ch2\u003eComplementary\u003c\/h2\u003e\u003ctable border=\"1\" cellpadding=\"5\" cellspacing=\"0\"\u003e\n\u003cthead\u003e\u003ctr\u003e\n\u003cth\u003eCharacteristic\u003c\/th\u003e\n\u003cth\u003eValue(s)\u003c\/th\u003e\n\u003c\/tr\u003e\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eSynchronisation time between inputs\u003c\/td\u003e\n\u003ctd\u003e2 or 4 s depending of wiring (automatic start)\u003cbr\u003eUnlimited (manual start)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupply frequency\u003c\/td\u003e\n\u003ctd\u003e50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum power consumption in VA\u003c\/td\u003e\n\u003ctd\u003e6 VA AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput protection type\u003c\/td\u003e\n\u003ctd\u003eInternal, electronic\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Uc] control circuit voltage\u003c\/td\u003e\n\u003ctd\u003e24 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum line resistance\u003c\/td\u003e\n\u003ctd\u003e28 Ohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBreaking capacity\u003c\/td\u003e\n\u003ctd\u003e180 VA holding AC-15 C300 relay output\u003cbr\u003e1800 VA inrush AC-15 C300 relay output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBreaking capacity\u003c\/td\u003e\n\u003ctd\u003e1.5 A 24 V DC-13)50 ms relay output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput thermal current\u003c\/td\u003e\n\u003ctd\u003e6 A per relay relay output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Ith] conventional free air thermal current\u003c\/td\u003e\n\u003ctd\u003e18 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAssociated fuse rating\u003c\/td\u003e\n\u003ctd\u003e4 A gG or gL relay output EN\/IEC 60947-5-1, DIN VDE 0660 part 200\u003cbr\u003e6 A fast blow relay output EN\/IEC 60947-5-1, DIN VDE 0660 part 200\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMinimum output current\u003c\/td\u003e\n\u003ctd\u003e10 mA relay output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMinimum output voltage\u003c\/td\u003e\n\u003ctd\u003e17 V relay output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum response time on input open\u003c\/td\u003e\n\u003ctd\u003e40 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Ui] rated insulation voltage\u003c\/td\u003e\n\u003ctd\u003e300 V 2)IEC 60947-5-1\u003cbr\u003e300 V 2)DIN VDE 0110 part 1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Uimp] rated impulse withstand voltage\u003c\/td\u003e\n\u003ctd\u003e4 kV III IEC 60947-5-1\u003cbr\u003e4 kV III DIN VDE 0110 part 1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLocal signalling\u003c\/td\u003e\n\u003ctd\u003e4 LEDs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent consumption\u003c\/td\u003e\n\u003ctd\u003e30 mA 24 V AC on power supply\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting Support\u003c\/td\u003e\n\u003ctd\u003e35 mm symmetrical DIN rail\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Weight\u003c\/td\u003e\n\u003ctd\u003e0.9 lb(US) (0.4 kg)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e","brand":"Schneider","offers":[{"title":"Sealed Surplus","offer_id":46840993251550,"sku":"XPSAK371144P-Sealed","price":0.0,"currency_code":"USD","in_stock":false},{"title":"Never Used Surplus","offer_id":35630066434202,"sku":"XPSAK371144P","price":0.0,"currency_code":"USD","in_stock":false},{"title":"Used","offer_id":42379814731998,"sku":"XPSAK371144P-Used","price":478.4,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0349\/2973\/7859\/products\/XPSAK371144P_cd89b61e-369a-4534-bb85-457cd2dca54b.jpg?v=1640701093","url":"https:\/\/plc-direct.com\/products\/xpsak371144p","provider":"PLC Direct","version":"1.0","type":"link"}