{"product_id":"lucd05bl","title":"LUCD05BL Schneider Electric","description":"\u003cp\u003eTeSys U control and diagnostic unit to be inserted in advanced power bases LUB120, LUB320, LUB380 to form a TeSys U starter controller, for 3-phase motor applications up to 1.5kW@400V. It provides full protection to motors with a rated current Ir 1.25-5A (Ir adjustable), overload tripping class 20, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only). It provides a thermal overload alarm to be used locally using a LUFDA module or remotely using a LULC module, and a test push button for overload simulation. To be used with a 24V DC voltage for the control of the starter (through the control terminals A1\/A2 located in the power base). Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC, Marine).\u003c\/p\u003e\u003ch2\u003eMain\u003c\/h2\u003e\n\u003ctable border=\"1\" cellpadding=\"5\" cellspacing=\"0\"\u003e\n\u003cthead\u003e\u003ctr\u003e\n\u003cth\u003eCharacteristic\u003c\/th\u003e\n\u003cth\u003eValue(s)\u003c\/th\u003e\n\u003c\/tr\u003e\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eRange\u003c\/td\u003e\n\u003ctd\u003eTeSys\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRange of Product\u003c\/td\u003e\n\u003ctd\u003eTeSys Ultra\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eproduct name\u003c\/td\u003e\n\u003ctd\u003eTeSys Ultra\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDevice short name\u003c\/td\u003e\n\u003ctd\u003eLUCD\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct or Component Type\u003c\/td\u003e\n\u003ctd\u003eAdvanced control unit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDevice Application\u003c\/td\u003e\n\u003ctd\u003eMotor control\u003cbr\u003eMotor protection\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Specific Application\u003c\/td\u003e\n\u003ctd\u003eBasic protection and advanced functions, communication\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003emain function available\u003c\/td\u003e\n\u003ctd\u003eProtection against phase failure and phase imbalance\u003cbr\u003eManual reset\u003cbr\u003eProtection against overload and short-circuit\u003cbr\u003eEarth fault protection\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct compatibility\u003c\/td\u003e\n\u003ctd\u003ePower base LUB12\u003cbr\u003ePower base LUB32\u003cbr\u003ePower base LUB38\u003cbr\u003ePower base LUB120\u003cbr\u003ePower base LUB320\u003cbr\u003ePower base LUB380\u003cbr\u003eReversing contactor breaker LU2B12BL\u003cbr\u003eReversing contactor breaker LU2B32BL\u003cbr\u003eReversing contactor breaker LU2B38BL\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Ue] rated operational voltage\u003c\/td\u003e\n\u003ctd\u003e690 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNetwork frequency\u003c\/td\u003e\n\u003ctd\u003e40...60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLoad type\u003c\/td\u003e\n\u003ctd\u003e3-phase motor self-cooled\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUtilisation category\u003c\/td\u003e\n\u003ctd\u003eAC-41\u003cbr\u003eAC-44\u003cbr\u003eAC-43\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMotor power kW\u003c\/td\u003e\n\u003ctd\u003e1.5 kW 400...440 V AC 50\/60 Hz\u003cbr\u003e2.2 kW 500 V AC 50\/60 Hz\u003cbr\u003e3 kW 690 V AC 50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003erated motor current adjustment range\u003c\/td\u003e\n\u003ctd\u003e1.25â¦5 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eThermal overload class\u003c\/td\u003e\n\u003ctd\u003eClass 20 40â¦60 Hz -13â¦158 Â°F (-25â¦70 Â°C) IEC 60947-6-2\u003cbr\u003eClass 20 40â¦60 Hz -13â¦158 Â°F (-25â¦70 Â°C) UL 508\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTripping threshold\u003c\/td\u003e\n\u003ctd\u003e14.2 x Ir +\/- 20 %\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePhase failure sensitivity\u003c\/td\u003e\n\u003ctd\u003eYes\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Uc] control circuit voltage\u003c\/td\u003e\n\u003ctd\u003e24 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\u003ch2\u003eComplementary\u003c\/h2\u003e\u003ctable border=\"1\" cellpadding=\"5\" cellspacing=\"0\"\u003e\n\u003cthead\u003e\u003ctr\u003e\n\u003cth\u003eCharacteristic\u003c\/th\u003e\n\u003cth\u003eValue(s)\u003c\/th\u003e\n\u003c\/tr\u003e\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eControl circuit voltage limits\u003c\/td\u003e\n\u003ctd\u003e20...27 V DC 24 V in operation\u003cbr\u003e14.5 V DC 24 V drop-out\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTypical current consumption\u003c\/td\u003e\n\u003ctd\u003e130 mA 24 V DC I maximum while closing with LUB12\u003cbr\u003e220 mA 24 V DC I maximum while closing with LUB32\u003cbr\u003e220 mA 24 V DC I maximum while closing with LUB38\u003cbr\u003e60 mA 24 V DC I rms sealed with LUB12\u003cbr\u003e80 mA 24 V DC I rms sealed with LUB32\u003cbr\u003e80 mA 24 V DC I rms sealed with LUB38\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHeat dissipation\u003c\/td\u003e\n\u003ctd\u003e2 W control circuit with LUB12\u003cbr\u003e3 W control circuit with LUB32\u003cbr\u003e3 W control circuit with LUB38\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating time\u003c\/td\u003e\n\u003ctd\u003e35 ms opening with LUB12 control circuit\u003cbr\u003e35 ms opening with LUB32 control circuit\u003cbr\u003e35 ms opening with LUB38 control circuit\u003cbr\u003e70 ms closing with LUB12 control circuit\u003cbr\u003e70 ms closing with LUB32 control circuit\u003cbr\u003e70 ms closing with LUB38 control circuit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eReset\u003c\/td\u003e\n\u003ctd\u003eManual reset\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStandards\u003c\/td\u003e\n\u003ctd\u003eEN 60947-6-2\u003cbr\u003eIEC 60947-6-2\u003cbr\u003eUL 60947-4-1, with phase barrier\u003cbr\u003eCSA C22.2 No 60947-4-1, with phase barrier\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Certifications\u003c\/td\u003e\n\u003ctd\u003eCE\u003cbr\u003eUL\u003cbr\u003eCSA\u003cbr\u003eCCC\u003cbr\u003eEAC\u003cbr\u003eASEFA\u003cbr\u003eATEX\u003cbr\u003eMarine\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Ui] rated insulation voltage\u003c\/td\u003e\n\u003ctd\u003e690 V IEC 60947-6-2\u003cbr\u003e600 V UL 60947-4-1\u003cbr\u003e600 V CSA C22.2 No 60947-4-1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Uimp] rated impulse withstand voltage\u003c\/td\u003e\n\u003ctd\u003e6 kV IEC 60947-6-2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSafe separation of circuit\u003c\/td\u003e\n\u003ctd\u003e400 V SELV between the control and auxiliary circuits IEC 60947-1\u003cbr\u003e400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFixing mode\u003c\/td\u003e\n\u003ctd\u003ePlug-in (front face)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWidth\u003c\/td\u003e\n\u003ctd\u003e1.8 in (45 mm)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHeight\u003c\/td\u003e\n\u003ctd\u003e2.6 in (66 mm)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDepth\u003c\/td\u003e\n\u003ctd\u003e2.4 in (60 mm)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCompatibility code\u003c\/td\u003e\n\u003ctd\u003eLUCD\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e","brand":"Schneider","offers":[{"title":"Sealed Surplus","offer_id":46840659149022,"sku":"LUCD05BL-Sealed","price":0.0,"currency_code":"USD","in_stock":false},{"title":"Never Used Surplus","offer_id":42694269698270,"sku":"LUCD05BL","price":0.0,"currency_code":"USD","in_stock":false},{"title":"Used","offer_id":42694269731038,"sku":"LUCD05BL-Used","price":0.0,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0349\/2973\/7859\/products\/LUCD05BL.jpg?v=1650048405","url":"https:\/\/plc-direct.com\/products\/lucd05bl","provider":"PLC Direct","version":"1.0","type":"link"}