{"product_id":"56170","title":"56170 Schneider","description":"\u003cp\u003eVigiPacT RH99M is a DIN rail mounting residual current protection relay. It protects against people direct or indirect contact, property fire hazards and motors. It measures the earth leakage current in an electrical installation via its associated toroid. It trips the associated circuit breaker when the set residual operation current is overrun. The operational supply voltage is 12\/24VAC 50\/60Hz, or 12\/48VDC. The current sensitivity is selectable with 9 thresholds from 30 mA to 30 A. The time delay is selectable with 9 settings from instantaneous to 4.5s. It requires a local manual reset after a fault clearance. The monitored distribution system voltage is up to 1000 VAC 50\/60\/400 Hz. It is installed on a DIN-rail inside a switchboard and the protection degree is IP40. It must be associated with a compatible Schneider Electric type A toroid or rectangular sensor.\u003c\/p\u003e\u003ch2\u003eMain\u003c\/h2\u003e\n\u003ctable border=\"1\" cellpadding=\"5\" cellspacing=\"0\"\u003e\n\u003cthead\u003e\u003ctr\u003e\n\u003cth\u003eCharacteristic\u003c\/th\u003e\n\u003cth\u003eValue(s)\u003c\/th\u003e\n\u003c\/tr\u003e\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eRange\u003c\/td\u003e\n\u003ctd\u003eVigiPacT\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDevice short name\u003c\/td\u003e\n\u003ctd\u003eRH99M\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct or Component Type\u003c\/td\u003e\n\u003ctd\u003eResidual current protection relay\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelay application\u003c\/td\u003e\n\u003ctd\u003eProtection relay\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting Support\u003c\/td\u003e\n\u003ctd\u003eDIN rail\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEarth-leakage protection class\u003c\/td\u003e\n\u003ctd\u003eType A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eType of setting\u003c\/td\u003e\n\u003ctd\u003eSelector\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResidual earth-leakage sensitity adjustment type\u003c\/td\u003e\n\u003ctd\u003eAdjustable 9 settings\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEarth-leakage sensitivity\u003c\/td\u003e\n\u003ctd\u003e0.03â¦30 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEarth-leakage time delay\u003c\/td\u003e\n\u003ctd\u003eInstantaneous for 0.03 A\u003cbr\u003eAdjustable 9 settings 0â¦4.5 s for 0.03â¦30 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent sensors compatibility\u003c\/td\u003e\n\u003ctd\u003eVigiPacT TOA earth leakage current sensor\u003cbr\u003eVigiPacT A earth leakage current sensor\u003cbr\u003eVigiPacT L earth leakage current sensor\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Ithe] conventional enclosed thermal current\u003c\/td\u003e\n\u003ctd\u003e8 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMinimum load\u003c\/td\u003e\n\u003ctd\u003e10 mA 12 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Us] rated supply voltage\u003c\/td\u003e\n\u003ctd\u003e12...24 V AC 50\/60 Hz 55...120 %\u003cbr\u003e12...48 V DC 55...120 %\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption in VA\u003c\/td\u003e\n\u003ctd\u003e4 VA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMonitored distribution system\u003c\/td\u003e\n\u003ctd\u003e1000 V - AC 50\/60 Hz maximum) \u003cbr\u003e1000 V - AC 400 Hz maximum)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEarthing system\u003c\/td\u003e\n\u003ctd\u003eTN-S\u003cbr\u003eIT\u003cbr\u003eTT\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Uimp] rated impulse withstand voltage\u003c\/td\u003e\n\u003ctd\u003e8 kV\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eReset\u003c\/td\u003e\n\u003ctd\u003eManual reset\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\u003ch2\u003eComplementary\u003c\/h2\u003e\u003ctable border=\"1\" cellpadding=\"5\" cellspacing=\"0\"\u003e\n\u003cthead\u003e\u003ctr\u003e\n\u003cth\u003eCharacteristic\u003c\/th\u003e\n\u003cth\u003eValue(s)\u003c\/th\u003e\n\u003c\/tr\u003e\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eTest function\u003c\/td\u003e\n\u003ctd\u003eRemote test\u003cbr\u003eLocal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMonitoring\u003c\/td\u003e\n\u003ctd\u003eElectronics continuous) \u003cbr\u003ePower supply continuous) \u003cbr\u003eRelay\/sensor link continuous)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eType of measurement\u003c\/td\u003e\n\u003ctd\u003eEarth fault current internal measurement 80...100 %\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTamperproof of settings\u003c\/td\u003e\n\u003ctd\u003eProtected by sealable cover\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnections - terminals\u003c\/td\u003e\n\u003ctd\u003eAuxiliary power supply terminal block 0.0003â¦0.004 inÂ² (0.2â¦2.5 mmÂ²) flexible AWG 24...AWG 12\u003cbr\u003eAuxiliary power supply terminal block 0.0003â¦0.004 inÂ² (0.2â¦2.5 mmÂ²) rigid AWG 24...AWG 12\u003cbr\u003eAuxiliary power supply terminal block 0.0004â¦0.004 inÂ² (0.25â¦2.5 mmÂ²) flexible AWG 24...AWG 12\u003cbr\u003eFault screw terminal 0.0003â¦0.004 inÂ² (0.2â¦2.5 mmÂ²) flexible AWG 24...AWG 12\u003cbr\u003eFault screw terminal 0.0003â¦0.006 inÂ² (0.2â¦4 mmÂ²) rigid AWG 24...AWG 12\u003cbr\u003eFault screw terminal 0.0004â¦0.004 inÂ² (0.25â¦2.5 mmÂ²) flexible AWG 24...AWG 12\u003cbr\u003eRelay test and fault reset screw terminal 0.0002â¦0.002 inÂ² (0.14â¦1 mmÂ²) flexible AWG 26...AWG 16\u003cbr\u003eRelay test and fault reset screw terminal 0.0002â¦0.002 inÂ² (0.14â¦1.5 mmÂ²) rigid AWG 26...AWG 16\u003cbr\u003eRelay test and fault reset screw terminal 0.0004â¦0.0008 inÂ² (0.25â¦0.5 mmÂ²) flexible AWG 26...AWG 16\u003cbr\u003eSensor screw terminal 0.0002â¦0.002 inÂ² (0.14â¦1 mmÂ²) flexible AWG 26...AWG 16\u003cbr\u003eSensor screw terminal 0.0002â¦0.002 inÂ² (0.14â¦1.5 mmÂ²) rigid AWG 26...AWG 16\u003cbr\u003eSensor screw terminal 0.0004â¦0.0008 inÂ² (0.25â¦0.5 mmÂ²) flexible AWG 26...AWG 16\u003cbr\u003eVoltage presence screw terminal 0.0003â¦0.004 inÂ² (0.2â¦2.5 mmÂ²) flexible AWG 24...AWG 12\u003cbr\u003eVoltage presence screw terminal 0.0003â¦0.006 inÂ² (0.2â¦4 mmÂ²) rigid AWG 24...AWG 12\u003cbr\u003eVoltage presence screw terminal 0.0004â¦0.004 inÂ² (0.25â¦2.5 mmÂ²) flexible AWG 24...AWG 12\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWire stripping length\u003c\/td\u003e\n\u003ctd\u003eAuxiliary power supply: 0.3 in (7 mm) for top connection\u003cbr\u003eFault: 0.3 in (8 mm) for bottom connection\u003cbr\u003eRelay test and fault reset: 0.2 in (5 mm) for bottom connection\u003cbr\u003eSensor: 0.2 in (5 mm) for top connection\u003cbr\u003eVoltage presence: 0.3 in (8 mm) for bottom connection\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTightening torque\u003c\/td\u003e\n\u003ctd\u003eAuxiliary power supply: 5.3 lbf.in (0.6 N.m) top\u003cbr\u003eFault: 5.3 lbf.in (0.6 N.m) bottom\u003cbr\u003eRelay test and fault reset: 2.21 lbf.in (0.25 N.m) bottom\u003cbr\u003eSensor: 2.21 lbf.in (0.25 N.m) top\u003cbr\u003eVoltage presence: 5.3 lbf.in (0.6 N.m) bottom\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e9 mm pitches\u003c\/td\u003e\n\u003ctd\u003e6\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStandards\u003c\/td\u003e\n\u003ctd\u003eEN\/IEC 60947-2 Annex M\u003cbr\u003eEN\/IEC 60755\u003cbr\u003eUL 1053\u003cbr\u003eCAN\/CSA C22.2 No. 144\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWidth\u003c\/td\u003e\n\u003ctd\u003e2.1 in (54 mm)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHeight\u003c\/td\u003e\n\u003ctd\u003e3.2 in (81 mm)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDepth\u003c\/td\u003e\n\u003ctd\u003e2.9 in (74 mm)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Weight\u003c\/td\u003e\n\u003ctd\u003e0.7 lb(US) (0.3 kg)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIP degree of protection\u003c\/td\u003e\n\u003ctd\u003eIP40 on front face: conforming to EN\/IEC 60529\u003cbr\u003eIP30 on side parts: conforming to EN\/IEC 60529\u003cbr\u003eIP20 on connection terminals: conforming to EN\/IEC 60529\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIK degree of protection\u003c\/td\u003e\n\u003ctd\u003eIK07 conforming to EN 50102\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMechanical robustness\u003c\/td\u003e\n\u003ctd\u003eFire resistance IEC 60695-2-1\u003cbr\u003eIK protection 2 joulesIK07 EN 50102\u003cbr\u003eVibrations 13.2...100 Hz0.7 g\u003cbr\u003eVibrations 2...13.2 Hz+\/- 1 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e","brand":"Schneider","offers":[{"title":"Sealed Surplus","offer_id":46839870587102,"sku":"56170-Sealed","price":4590.0,"currency_code":"SEK","in_stock":true},{"title":"Never Used Surplus","offer_id":46667257741534,"sku":"56170","price":0.0,"currency_code":"SEK","in_stock":false},{"title":"Used","offer_id":46667257839838,"sku":"56170-Used","price":0.0,"currency_code":"SEK","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0349\/2973\/7859\/files\/new_schneider_stock_3920e36d-810f-4e0e-ac28-64708acd62c0.png?v=1753948704","url":"https:\/\/plc-direct.com\/en-se\/products\/56170","provider":"PLC Direct","version":"1.0","type":"link"}